Thank you for choosing the Eaton Logic Controller (ELC) series products.
The ELC-CAPBDP is a PROFIBUS DP distributed I/O adapter module that
connects ELC I/O modules to PROFIBUS DP networks. The adapter
provides I/O and module diagnostic information to PROFIBUS DP scanners.
The power is supplied by a 24VDC power supply. The right side of
ELC-CAPBDP is where the digital and analog I/O modules connect, and the
RS-485 COM port is a standard Modbus master port that can be connected
to Modbus slave stations.
aThis instruction sheet provides information on the electrical
specifications, functionality, installation and wiring for this module. It
should be read and understood before attempting to install or use the
module.
aAdditional information can be found in the ELC series Programming
Manual.
aThe ELC should be kept in an enclosure away from airborne dust,
humidity and vibration.
aDO NOT disconnect equipment unless power has been switched off or
the area is known to be non hazardous.
aDO NOT connect AC power to any of the DC input / output terminals, as
it will damage them. Check all wiring prior to power up.
aEnsure that the ground terminal is correctly grounded in order to
prevent electromagnetic interference.
aDO NOT touch the internal circuit in one minute after the power is
switched off.
Functions
Supports PROFIBUS DP cyclic data transmission.
Auto-detects baud rates; supports Max.12Mbps.
Self-diagnosis
Able to connect to a maximum of 8 specialty I/O modules and 32 digital
I/O modules (max. 256 points) on the right side bus.
The RS-485 COM port is able to connect to a maximum of 16 standard
Modbus slave stations.
Supports a maximum of 100 bytes of input data and 100 bytes of output
data.
Product Profile & Dimension
1
2
3
5
6
9
8
7
4
10
11
12
13
14
15
16
17
ELC-CAPBDP
Unit: mm

- 2 -
1.
POWER indicator
10.
Nameplate
2.
NET indicator
11.
I/O module connection port
3.
RS-485 indicator
12.
DIN rail slot (35mm)
4.
RUN/STOP switch
13.
I/O module fixing clip
5.
RUN indicator
14.
DIN rail fixing clip
6.
ALARM indicator
15.
RS-485 COM port
7.
Address setup switch
16.
I/O module fixing notch
8.
PROFIBUS DP COM port
17.
DC24V power supply interface
9.
I/O module positioning hole
Switch Definition: RUN/STOP
Status
Explanation
RUN
Æ
STOP
1. Specialty I/O modules switch from RUN to STOP
2.
All Y points on the digital output modules are
turned OFF
3.
Modbus function disabled
4. RUN LED turns off
STOP
RUN
STOP
Æ
RUN
1. ELC-CAPBDP re-detects the number of digital I/O
points and specialty I/O modules.
2. Special
ty I/O modules
switch from STOP to RUN.
3. Enable
digital I/O modules.
4. Modbus function
enabled.
5. RUN LED turns on.
Address Setup Switch
The two rotary address setup switches, x160and x161, set up the node
address of the ELC-CAPBDP on the PROFIBUS DP network in
hexadecimal format. The range is 0 ~ F (see below for more details).
Address
Explanation
0
x16
1
x16
H’1 ~ H’7D
Valid PROFIBUS addresses
H’0 or
H’7E ~ H’FF
Invalid PROFIBUS addresses. NET LED will flash
red if the node address falls within this range.
Example: If you need to set the node address of ELC-CAPBDP to 26
(decimal), set switch x161to “1” and x160to “A”. 26 (decimal) = 1A (hex) =
1×161᧧A×160.
Note:
1. Please switch off the power supply before setting up the node address of
the ELC-CAPBDP module. Re-power the module after the setup is
completed.
2. Changing the value on the switches during the operation of
ELC-CAPBDP is invalid. The switches are read at power up only.
3. Use slot type screwdriver to set up the switch.
Function Specifications
PROFIBUS DP Port
Interface
DB9 connector
Transmission method
High-speed RS-485

- 3 -
Transmission cable
Shielded twisted pair cable
Electrical isolation
500VDC
Communication
Message type
Cyclic data exchange
Module name
ELC-CAPBDP
GSD document
ETON09B9.GSD
Product ID
09B9
Serial transmission
speed supported
(auto-detection)
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps;
3Mbps; 6M
bps; 12Mbps (bits per second)
Electrical Specifications
Power supply voltage
24VDC
Insulation voltage
500VDC
Power consumption
2.5W
Weight
90g
Environmental Specifications
Noise immunity
ESD(IEC 61131-2,IEC 61000-4-2): 8kV Air Discharge
EFT(IEC 61
131-2,IEC 61000-4-4): Power Line:
2kV,Digital
Input:
2kV
Communication
I/O: 2kV
Conducted Susceptibility Test
(EN61000-4-6, IEC 61131
-2
9.10)
: 150kHz ~ 80MHz,10V/m
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Storage/operation
Operation: 0°C ~ 50°C (temperature), 50 ~ 90% (humidity),
pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Shock/vibration
immunity
International standards: IEC 61131-2,IEC 68-2-6 (TEST Fc)/
IEC 61131-2& IEC 68-2-27 (TEST Ea)
Certificates
Definition of PROFIBUS DP Port
PIN
PIN name
Definition
16
5
9
1
-
Not defined
2
-
Not defined
3
Rxd/Txd-P
Sending/receiving data P(B)
4
-
Not defined
5
DGND
Data reference potential
6
VP
Power voltage –positive
7
-
Not defined
8
Rxd/Txd-N
Sending/receiving data N(A)
9
-
Not defined

- 4 -
Installation
Connecting to the PROFIBUS DP Port
Insert the PROFIBUS DP bus connector into the PROFIBUS DP port on
ELC-CAPBDP. Screw it in tightly to ensure the ELC-CAPBDP and the
PROFIBUS DP connectors are properly connected.
Installing ELC-CAPBDP & I/O Modules on DIN Rail
1. Use 35mm DIN rail.
2. Open the DIN rail clips on ELC-CAPBDP and I/O module. Insert
ELC-CAPBDP and I/O module on the DIN rail.
3. Clip up the DIN rail clips on ELC-CAPBDP and I/O module to fix them
on the DIN rail.
LED Indication and Trouble shooting
There are 5 LED indicators on ELC-CAPBDP: POWER, NET, RS-485, RUN
and ALARM.
POWER Indicator
POWER LED displays whether the power supplied to the ELC-CAPBDP is
correct.
LED Status
Indication
How to deal with
Green light on
Normal
--
Off
No power
Check the power supply.

- 5 -
NET Indicator
NET LED displays whether the communication between ELC-CAPBDP and
PROFIBUS DP master is working.
LED Status
Indication
How to deal with
Green light on
Normal
--
Red light on
ELC
-
CAPBDP is not
connected to the
master.
1. Check if ELC-CAPBDP is connected to
PROFIBUS DP bus.
2.
Check if the communication cable
between ELC-CAPBDP and
PROFIBUS
DP master is correct.
3.
Check if the address of the
ELC-CAPBDP
is consistent with the one
set in the master configuration software,
Red light
flashes
ELC
-CAPBDP
configuration error.
1. Check if the PROFIBUS address of
ELC-CAPBDP is between 1 and 125
(decimal).
2.
Check if the I/O mod
ules connected to
the ELC-CAPBDP
and their order are
consistent with the software
configuration.
RUN Indicator
RUN LED displays whether ELC-CAPBDP is operating or in stop status.
LED Status
Indication
Green light on
ELC-CAPBDP is operating.
Off
ELC-CAPBDP is in stop status.
ALARM Indicator
ALARM LED displays whether the right-side specialty I/O modules are
working normally and the power supply is sufficient.
LED Status
Indication
How to deal with
Off
Normal
--
Red light on
24VDC power supply is
insufficient.
Check if the power supply is
overloaded.
Red light slowly
flashes
(on 0.5s and off
0.5s)
Error in
a specialty I/O
module
Please refer to the descriptions
for the
error codes in the
appropriate
specialty
I/O module
manual
.
Red light fast
flash
es
(on 0.3s and off
0.3s)
Special
ty I/O module is
off
-line.
1. Check that the power to the
specialty I/O module is
correct.
2.
Check that the connections
between ELC-
CAPBDP and
specialty module is correct.
RS-485 Indicator
RS-485 LED displays whether the RS-485 communications between the
ELC-CAPBDP and other Modbus devices is working properly.
LED Status
Indication
How to deal with
Green light on
Normal
--

- 6 -
LED Status
Indication
How to deal with
Green light
flashes
The Modbus function has
not been enabled, or no
Modbus slave is configured
--
Red light on
All Modbus slaves are
off
-line.
Check if the RS-485 cable is
properly connected
, and the
communication format is correct.
Red light flashes
The RS-485
communications to one or
more
of the connected
Modbus devices is
not
working properly.
Check if
one or more of the
connected
RS-485 devices is
not
respond
ing or is responding
incorrectly.
Table of contents
Other Eaton I/O System manuals

Eaton
Eaton xComfort CBEU-02/02 User manual

Eaton
Eaton SONIX Io User manual

Eaton
Eaton 105U-2 User manual

Eaton
Eaton 105U-3-5W User manual

Eaton
Eaton 105U-1 User manual

Eaton
Eaton ECIO-DN User manual

Eaton
Eaton Cutler-Hammer SV9IOC105 User manual

Eaton
Eaton ELC-EX08NNDR User manual

Eaton
Eaton XN-1RS232 User manual

Eaton
Eaton 105U-2-5W User manual