non-heating mode light in yellow (red) colour (in this mode all the protections are active).
Heating mode is determined by the selected configuration and settings made by the user.
4.4. Protections and blockings
4.4.1. PROTECTION from overheating
When water temperature exceeded 90 ° C the water pump swith on for a period of 10
minutes whether of heating mode or not.
When water temperature exceeded 100 ° C is displayed message exceeded temperature
accompanied by a sound signal.
When water temperature exceeded over105 114 ° C (set of produces) triggered emergency
thermal protection. Electromechanical thermostat switched off the boiler.
REACTION: The system goes into mode Auto Off. The display shows message switched
thermal protection accompanied by a sound signal and the pump indicator lights red.
Protection does not regenerate itself. Manually unblock only after eliminate the cause of
activation.
4.4.2. PROTECTION against low level of the water in the boiler body
Because of various reasons (evaporation, leakage), the quantity of water in the pipes and
radiators may decrease and the water level in the boiler body may drop under the one
admissible for their safe operation.
The protection swithes on when having a low water level for period of 10 seconds
REACTION: All heaters and the pump are immediately compulsory switched off. Massage
for low water level is showing on the display accompanied by a sound signal and the pump
indicator lights red.
Upon recovery of the level, the operation mode could be changed.
Protection against low water level can be switched off by including a jumper 1
(JP1), located on the main board of boiler unit.
4.4.3. PROTECTION against water freezing in the boiler body, pipes and radiators.
REACTION: Upon drop of the temperature of water in the boiler body below 15oC, the
circulation pump is switched on compulsory to constant operation. If in such status
temperature lower than 6oC should be measured, all heaters are smoothly switched on (100%
power). This shall continue until raise of the temperature above 9oC. Then the heating is
switched off again smoothly, but the pump is continuing to work while the temperature is
staying below 15oC.
Upon triggering the OVERHEATING protection, the action of the protection against
freezing is blocked.
4.4.4. Cut off temperature sensor boiler
REACTION: In the absence of boiler temperature sensor, broken wire or short circuit the
wires on the display shows message for broken or short circuit sensor accompanied by an
sound signal and pump indicator lights red. The system goes into the Auto Off mode, heaters
gradually excluded.
4.4.5. Maximum downtime of the pump
For a stay of the pump for a period exceeding 24 hours, it includes over 10 minutes.
4.4.6. Low battery
On the main board of the boiler is installed 3-volt lithium battery serves to power the clock.
With a decline in battery voltage below 2.7 volts is displayed message for a low battery and
the pump indicator lights red. It is necessary to reset the battery with the same type new one.