You have to replace all burnt fuses.
Overload protection: when the continuous draw exceeds rated Watts, the inverter will shut down, at the same time, an
alarm will sound and the indicator light will turn on.
Short circuit protection: when the output side is short circuited, the inverter will shut down, an alarm will sound and
the indicator light will turn on.
Temperature control: If the temperature in the unite reaches 45°C the fan will start and cool down the device.
Over-temperature protection:when the inside temperature is over 75°, the inverter will shut down, an alarm will
sound and the indicator light will turn on.
16. SERVICE ENVIRONMENT
Ambient temperature: -20~+50℃
Storage temperature: -40~+85℃
Relative humidity: 0~85% Non-condensing
17. PROBLEM CAUSES
PROBLEM POSSIBLE CAUSE SOLUTION
The inverter is switched on but
the LED does not work. No
response. No alarm.
Open circuit. No DC input. Fuse
faulty.
1. Check entry circuit continuity
2. Check that the battery fuse is right.
3. Check if all circuit connections are correct.
4. Check the on/off button wiring.
The inverter is switched on and
the LED works. No AC output. No
alarm.
Reversed of polarity connection on
input side and internal fuses have
been burnt.
1. Check and correct the polarity of input
connections and replace the internal fuse. (NOTE:
Reversing the polarity may cause irreversible
damage to the circuit)
Unusual Low output AC voltage Poor battery. Internal mosfet faulty.
Drive circuit faulty.
1. Reverse the potentiometer on drive panel to
get right output voltage.
2. Ensure enough and full battery power..
3. Contact the technical support.
The alarm sounds 1 (2) time per
time, after 2 seconds, same beeps
again. (Without any load)
Poor battery. Connection cable is
too thin or too long.
1. Ensure enough and full battery power.
2. Use the original cable.
The alarm sounds 1 time per
time, after 2 seconds, same beeps
again.
The input voltage is very low. DC12V
inverter: 10-10.5V DC24V inverter:
20-21V
1. Ensure enough and full battery power.
2. Check that the battery cables are suitable for
transporting the DC voltage. Use a thicker or
shorter cable.
3. Setting DC input circuit connections
The alarm sounds 2 times per
time, after 2 seconds, same beeps
again.
The input voltage is too low and the
inverter stop working.
1. Ensure enough and full battery power.
2. Check that the battery cables are suitable for
transporting the DC voltage. Use a thicker or
shorter cable.
3. Checking DC input circuit connections.
The alarm sounds 3 times per
time, after 2 seconds, same beeps
again.
The input voltage is too high. DC12
inverter: higher than 15.5V;DC24V
inverter: higher than 30V
1. Check that the voltage at the input DC
terminals does not exceed 15v
2. Make sure that the maximum voltage of the
battery controller does not supply voltages
higher than 15v(30V)
3. Check that we are not using a panel or wind
turbine not regulated for battery charging