Edwards SIGA-CC1S Assembly instructions

© 2017 United Technologies Corporation 1 / 6 P/N 3100152-EN • REV 11 • ISS 16MAR17
SIGA-CC1S Auto-Sync Output Module
Installation Sheet
Description
The SIGA-CC1S Auto-Sync Output Module is an addressable
module that is used to connect the following circuits:
• Audible and visible notification appliance circuits
(synchronized or unsynchronized)
• Speaker circuits
• Two-way telephone communication circuits (three-state or
four-state)
Upon command from the loop controller, the module connects
the riser to the output circuit.
The module requires one address on the signaling line circuit
(SLC). Addresses are assigned electronically. There are no
address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
• Normal: Green LED flashes
• Alarm/active: Red LED flashes
Personality codes
Use the personality codes described below to configure the
SIGA-CC1S module. See Table 1 for listing information.
Table 1: Personality codes
Code Description UL 864 CAN/ULC-
S527 EN 54-18
5 Signal - supervised
output (Class B)
6 Telephone - three-state
(Class B)
25 Signal – supervised auto
sync output (Class B)
26 Telephone - four-state
(Class B)
Personality code 5: Signal - supervised output (Class B).
Configures the SIGA-CC1S module as a riser selector for
audible and visible notification appliance circuits or for
single-channel audio circuits. The output circuit is monitored for
open or shorted wiring. If a short exists, the module will not
activate in order to prevent shorting the riser. The module will
activate once the short is cleared.
Personality code 6: Telephone - three-state (Class B).
Configures the module as a riser selector for a three-state
firefighter’s telephone. When a telephone handset is plugged
into its jack or lifted from its hook, the module generates its
own ring-tone signal, making a separate ring-tone riser
unnecessary. The module sends this signal to the control panel
to indicate the presence of an off-hook condition, and waits for
the system operator to respond to the call. When the system
operator responds, the ring-tone signal is disabled.
Personality code 25: Signal - supervised auto sync output
(Class B). Factory default. Configures the module to provide
synchronization of compatible fire alarm signals across multiple
zones. Operation is the same as Personality code 5 with the
addition that the module provides a sync signal for connecting
synchronized temporal horn/strobes.
Note: The use of nonsynchronous fire alarm signals with or
instead of compatible synchronized fire alarm signals does not
comply with UL 1971.
Personality code 26: Telephone - four-state (Class B).
Configures the module as a riser selector for a four-state
firefighter telephone. Operation is the same as Personality
code 6 except that the module can distinguish when a
telephone is off-hook and when the circuit is shorted, which
causes a trouble condition.

2 / 6 P/N 3100152-EN • REV 11 • ISS 16MAR17
Installation
Install this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
• The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
• This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
To install the module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
2. Connect the field wires. See “Wiring” below.
3. Using the self-tapping screw, attach the wall plate to the
module. See Figure 1.
4. Using the four machine screws, attach the wall plate and
module to the electrical box.
Figure 1: Installing the SIGA-CC1S module
(1) Compatible electrical box
(2) SIGA-CC1S module
(3) Wall plate
(4) #6-32 × 5/8 machine screw
(4X)
(5) #4 × 1/2 self-tapping screw
Protection from transient spikes
For installations in which the output circuit connects to
electromechanical bells or horns, install a bipolar transient
protector (P/N 235196P) to protect the module from transient
spikes caused by switching inductive loads. Locate bells and
horns at least 6 ft. (1.8 m) from the module.
To install a bipolar transient protector:
1. Install the transient protector across the output circuit
inside the electrical box with the module. See Figure 2.
Figure 2: Bell circuit showing bipolar transient protector
placement
(1) Normal state (2) Active state
Wiring
Wiring this device in accordance with applicable national and
local codes, ordinances, and regulations.
General wiring notes
• Refer to the Signature loop controller installation sheet for
SLC wiring specifications. Refer to the firefighter phone
installation sheet for additional details.
• Each terminal on the module is limited to a single
conductor.
• Test resistors are supplied with the SIGA-CC1S to prevent
trouble signals on unused circuits during installation.
When connecting field wires, remove the test resistors and
install a UL/ULC Listed 47 kΩEOLR at the end of the
circuit.
• The module does not support conventional smoke
detectors.
Riser wiring notes
• For maximum line impedance, refer to the installation
manual for the fire alarm panel. Maximum circuit
capacitance is 0.1 µF.
• If the riser is used for more than one notification zone,
install in accordance with the survivability from attack by
fire requirements in NFPA 72 National Fire Alarm and
Signaling Code.
• Circuit and riser wiring is different when four-state
firefighter telephones are installed on three-state circuits.
Before replacing a SIGA-CC1S module, tag the wires to
ensure correct reconnection.
• The SIGA-CC1S module does not supervise the riser; the
fire alarm control panel provides this function.
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Strip 1/4 in. (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
When stripping wire ends, exposing more wire may cause
a ground fault; exposing less wire may result in a faulty
connection.
3. Connect the field wires. See Figure 3 through Figure 5.
(1)
(2)
(3)
(4)
(5)
10 9
(
1
)
(
2
)

P/N 3100152-EN • REV 11 • ISS 16MAR17 3 / 6
Figure 3: Wiring diagram for NAC (personality code 5 and 25)
(1) Signal polarity is shown when the circuit in supervisory state.
Polarity reverses when the circuit is active.
(2) Supervised.
(3) Power-limited, unless connected to a nonpower-limited source. If
the source is nonpower-limited, eliminate the power-limited mark
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be
capable of handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(4) For synchronized signals you must use synchronized temporal
horn/strobes and personality code 25. Any other combination
will not produce synchronized signals.
(5) 47 kΩEOLR.
(6) Signaling line circuit (SLC) to next device.
(7) AUX riser (to next module or riser supervisory device).
(8) Power-limited regulated, power supply UL/ULC listed for fire
protective signaling systems.
(9) AUX riser (from previous device).
(10) Signaling line circuit (SLC) from previous device. Supervised
and power-limited.
(6)
+
+
(7)
+
+
(1)(2)(3)(4)
(
3
)(
8
)
(9)
(10)
+(5)

4 / 6 P/N 3100152-EN • REV 11 • ISS 16MAR17
Figure 4: Wiring diagram for audio (personality code 5)
(1) Signal polarity is shown when the circuit in supervisory state.
Polarity reverses when the circuit is active.
(2) Supervised.
(3) Power-limited unless connected to a nonpower-limited source. If
the source is nonpower-limited, eliminate the power-limited mark
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be
capable of handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(4) Unshielded twisted pair.
(5) 47 kΩEOLR (P/N EOL-47).
(6) Signaling line circuit (SLC) to next device.
(7) Audio riser (to next module or supervisory end of line device).
(8) Unshielded twisted pair. Use shielded twisted pair when
installed in the same conduit as with a telephone riser.
(9) Audio riser (from previous device).
(10) Signaling line circuit (SLC) from previous device. Supervised
and power-limited.
(5)
(1)(2)(3)(4)
+
+
+
+
(6)
(7)
(9)
(10)

P/N 3100152-EN • REV 11 • ISS 16MAR17 5 / 6
Figure 5: Class B telephone (personality codes 6 and 26)
Three-state telephone circuit (personality code 6)
Four-state telephone circuit (personality code 26)
(1) Telephone circuit. The plus and minus symbols indicate
signal polarity.
(2) Supervised.
(3) Power-limited unless connected to a nonpower-limited
source. If the source is nonpower-limited, eliminate the
power-limited mark and maintain a minimum of 0.25 in.
(6.4 mm) space from power-limited wiring. For other
mounting methods, see enclosure and bracket installation
sheets to maintain separation of power-limited and
nonpower-limited wiring. The wire size must be capable of
handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.4 mm) space or by a nonconductive sleeve or
nonconductive barrier from all other conductors. Refer to
the NFPA 70 National Electrical Code for more details.
(4) Required if distance from the SIGA-CC1S to the phone is
greater than 5 ft. Shield must be continuous, insulated, and
isolated from ground, except for the connection to chassis
ground in the control panel.
(5) 47 kΩEOLR.
(6) Signaling line circuit (SLC) to next device.
(7) Telephone riser (to next module or end-of-line supervisory
device).
(8) Use shielded twisted pair. Shields must be continuous and
grounded at the panel end.
(9) Telephone riser (from previous device).
(10) Signaling line circuit (SLC) from previous device.
Supervised and power-limited.
(5)
(1)(2)(3)
(6)
(7)
(9)
(10)
(4)
+
–
+
–
+
–
+
–
+
–
+
–
(1)(2)(3)
(10)
(9)
(6)
(7)
(5)
(4)
(3)(8)

6 / 6 P/N 3100152-EN • REV 11 • ISS 16MAR17
Specifications
Operating voltage range 15.20 to 19.95 VDC
Current
Standby
Activated
310 µA
150 µA
Maximum line impedance Refer to the control panel installation
manual
Ground fault impedance 10 kΩ
Output ratings (special
applications)
24 VDC
25 VRMS audio
70 VRMS audio
EOL resistor value
Circuit resistance
Circuit capacitance
2 A
50 W
35 W
47 kΩ
Refer to the control panel installation
manual
0.1 µF max.
EOLR 47 kΩ(P/N EOL-47)
Circuit designation
Signaling line circuits
Telephone riser circuits
Notification line circuits
Class A, Style 6 or Class B, Style 4
Class B, Style 4
Class B, Style Y
LPCB/CPR electrical box
Requirements
Minimum size W × H × D
Plastic box with cover plate, no gaps
or unused holes
3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm)
Compatible electrical boxes 2-1/2 in. (64 mm) deep dual-gang box;
4 in. square box 1-1/2 in. (38 mm)
deep box with a dual-gang cover
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93%, noncondensing
Storage temperature range −4 to 140°F (−20 to 60°C)
Regulatory information
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired operation.
North American
standards
CAN/ULC-S527, UL 864
EN 54 EN 54-18: 2005 Input/output devices
EU compliance
CPR certificates 0832-CPR-F0841
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information, see:
www.recyclethis.info.
Contact information
For contact information, see www.edwardsfiresafety.com.
Table of contents
Other Edwards I/O System manuals
Popular I/O System manuals by other brands

Lenovo
Lenovo ideacentre 610s Hardware Maintenance Manual

Solid State Logic
Solid State Logic Multichannel Digital Audio Interface... reference guide

SpinCore Technologies
SpinCore Technologies DDS-I-300 owner's manual

NI
NI R Series Getting started guide

QTS
QTS AN-X2-ABDHRIO user manual

KonNad
KonNad C2000-A2-SDD8020-DD3 user manual