Titan 75LC Transient Voltage Surge Suppressor (TVSS)
Instruction Bulletin
EFI Electronics Corporation
1751 South 4800 West
Salt Lake City, UT 84104
1-800-877-1174
www.efinet.com
Electrical equipment should be serviced only by qualified personnel. No responsibility is
assumed by EFI Electronics for any consequences arising out of the use of this material. This
document is not intended as an instruction manual for untrained persons.
8224-0005C 11/01
General Specifications
Max Surge Current 40kA
Housing Open Type
Product Weight 1 lb
Connection Method Terminals/Spade Lugs Sized for #22 to #12 AWG Wire
Terminal Capacity #22 to #14 AWG Stranded Wire
Terminal Torque 30 lb-in. (3.3 N.M)
Mounting Method DIN Rail or Flange Mounting
Circuit Type Series Hybrid
Thermal Fusing Yes
Sine Wave Tracking Yes
EMI/RFI Noise Rejection Up to -75 dB
Operating Temperature -40˚to +140˚F (-40˚to +60˚C)
Operating Frequency 50/60 Hz
Diagnostics Green LED, Form C Dry Contacts (optional)
Product Standards to UL 1449-2nd Ed, UL 1283, CSA C22.2 No. 0-M91
and No. 8-M1989. IEC 61643-1
Diagnostic Operation
•LED ON = Normal operation.
•LED OFF = Fault. Check line voltage, breakers and connections. If OK,
replace unit. (see Figure 3)
•Remote Monitoring (Dry Contact option) (see Figure 4). A three-pin
socket and plug are provided to allow the customer to wire one set of
normally open (NO) and normally closed (NC) “Dry”Contacts to a
remote monitoring indicator. The customer must provide power for this
indicator, keeping within the specifications shown in Figure 4.
The SPD’s internal electrical relay energizes only in the event of a
fault within the SPD.
NOTE: The supplied three-pin plug can accept up to #16 AWG
(1.5mm2) wire.
Model Rated Load Current Nominal Line Voltage
75LC120-5S(DC) 5 A 120 V
75LC120-10S(DC) 10 A 120 V
75LC120-15S(DC) 15 A 120 V
75LC120-20S(DC) 20 A 120 V
75LC230-5S(DC) 5 A 230 V
75LC230-10S(DC) 10 A 230 V
75LC230-15S(DC) 15 A 230 V
75LC230-20S(DC) 20 A 230 V
DC = indicates Dry Contact option
1. Turn off all power supplying this equipment before working on or
inside equipment.
2. Mount the SPD as shown in Figure 1.
3. Confirm SPD is rated for your system by comparing the L-N voltage
measurements to the Rated Line Voltage on the product label (120V
or 230V). (see Figure 2)
4. Insure that the in-line circuit breaker rating and wire size are per National
and Local Codes and match the current rating on the SPD label.
5. Connect as shown in Figure 2.
TROUBLESHOOTING