Code Code Code Code Code Code Code Code
SI016 160kA 120 120V N 1 Phase L-N 2+W+GND A All N Wire Lugs S E NEMA 4
025 250kA 208 208V L1 Phase L-L 2W +GND R Disconnect N Caseless
032 320kA 220 220V SSplit Phase 3W+GND
040 400kA 230 230V Y3 Phase Wye 4W+GND
050 500kA 240 240V D3 Phase Delta 3W+GND
060 600kA 277 277V X 3 Phase Wye 3W+GND
075 750kA 480 480V H 3 Delta Hi-Leg 4W+GND
100 1000kA
3
Surge Connection A B C D E F Weight
160kA Wire lugs 16 12 9 17.25 9.5 0.44 35
250kA Disconnect16 16 9 17.25 10 0.44 45
320kA Wire lugs 16 12 9 17.25 9.5 0.44 45
500kA Disconnect 16 16 9 17.25 10 0.44 55
600kA Wire lugs 20 16 9 21.25 10 0.44 55
750kA Disconnect 20 20 9 21.25 14 0.44 85
Wire lugs 20 20 9 21.25 14 0.44 85
Disconnect 20 24 9 21.25 18 0.44 95
Interceptor Choose Choose Choose Choose Choose Choose Choose
Series Surge Current Voltage Voltage Modes of Type of Monitoring Enclosure
Rating (L-G) Configuration Protection Connection Option Type
EXAMPLE
SI 016 1 2 0 Y A R D E
Liebert Interceptor®II Surge Suppression 160kA - 1000kA.
System B3 6kv/500A B3/C1 C3
Voltage Mode Ringwave Comb.Wave Comb.Wave Comb.Wave
120/208 L-N 328/344 308/312 376/376 452/536
120/208 L-G 340/348 320/316 364/368 444/584
120/208 L-L 464/448 576/568 680/652 792/832
120/208 N-G 344 284 344 468
277/480 L-N 520/536 532/528 800/800 912/952
277/480 L-G 736/760 688/688 760/776 840/896
277/480 L-L 736/776 720/728 1480/1416 1656/1600
277/480 N-G 736 648 760 896
System Voltage L-N L-G N-G L-L
120/240 330V 400V 400V 600V
120/208
240 N/A 800V N/A 800V
230/400 700V 800V 600V 1200V
277/480
480 N/A 1200V N/A 1500V
*Other modes
of protection
available; Call
factory.
UL 1449 Clamping Data (Second Edition)
NEMA LS 1 Test Data (without disconnect/with disconnect)
Chart A – Liebert Interceptor®II Model Selection
Chart B – Liebert Interceptor®II Dimensional Data
1,000kA
How To Specify The Appropriate Model:
All Liebert Interceptor II model numbers begin with the SI prefix. Use Chart A to build your Liebert Interceptor II starting with the Surge Rating column.
Moving left to right, choose the correct configurations from each column for your application. Your completed model number should look similar to the
example below or SI016120YARDE. Refer to Chart B for Liebert Interceptor II dimensional data.
Standard Monitoring
LEDs, Audible Alarm,
Form C Contacts
C Standard Monitoring
Plus Single Surge
Counter
DStandard Monitoring
Plus Dual Surge and
Swell Counters
Connection Type Parallel Connected
Agency Listings UL1449, UL1283, cUL, FCC Part 15 Class B
Operating Voltage Range + / - 15%
Fault Current Rating (AIC) 200kAIC
Operating Frequency Range 47 - 63 Hertz
50 ohm EMI/RFI Attenuation 100kHz 41 dB
1MHz 31 dB
10MHz 35 dB
100MHz 53 dB
Protection Modes All applicable modes standard (Line to Neutral, Line
to Ground, Neutral to Ground and Line to Line)
Response Time <0.5 nanoseconds
Temperature -40 to +60 degrees C
Operating Humidity 0% to 95% noncondensing
Status Indication LEDs, Dry Contacts, Audible Alarm
Enclosure NEMA 4 standard
Altitude 0 to 18,000 feet
Audible Noise Less than 45 dBa
Warranty 10-Years Parts and 5-Years On-Site Labor
*Other enclosure
options available;
Call factory.