EKM Omnimeter I User manual

eKM Metering Inc.
EKM Metering Inc. – www.ekmmetering.com – info@ekmmetering.com – (831)425-7371
• Nominal Voltage Ranges:
120V to 480V, 2-wire, Single-phase, One Line & Neutral
120V to 480V, 3-wire, Single-phase, 2 Lines & Neutral
120V to 415V, 3-wire, 3-phase, 3 Lines, No Neutral
120V to 480V, 4-wire, 3-phase, 3 Lines and Neutral
• Range of allowable environmental conditions: Pollution Degree 2,
Measurement Category III, Altitude rating 2000 meters max. Maximum
Temperature Range: -30 Deg. C to 70 Deg. C. Tamper Detection Class 1.
• The equipment is protected throughout by
double insulation as indicated by this symbol:
• Accuracy Class 0.5
• Rated Frequency: 50Hz/60Hz
• Red LED on the meter face ashes 800 times/kWh. 1 ash = 1.25Wh.
• Received California Type Approval for revenue grade metering
Safety Precautions:
• Meter should be installed by a qualied electrician.
• Turn off all power supplying the equipment before preforming any
wiring. Use a properly rated volt meter to conrm power is off.
• Use of this device inconsistent with this manual can cause permanent
damage to the unit and/or serious harm to the operator.
Tools/Materials List:
• Volt meter
• Small standard screwdriver
• Wire stripper
• DIN-Rail
•16-22 AWG stranded copper wire
• Inline fuse holder with maximum 1Amp fuse
• Use a Type 4 Enclosure (with appropriate conduit and ttings) if meter
will be installed outdoors
Installation Instructions
For All Systems:
1. Disconnect or switch power off before attempting to install, connect,
disconnect or service the meter or the external current transformers
(CTs). ALL POWER MUST BE DISCONNECTED!
2. Mount the meter using 35mm DIN Rail in a protected indoor location.
If installing outdoors, a UL Listed Type 4 Enclosure is required.
3. IMPORTANT: Distinguish and then identify the Neutral and the Line(s)
(‘hot’ wire(s), usually black or red). Label the Neutral and then,
depending on your electrical system, assign labels as described below.
4. Tightening torque of terminals:
All terminals: 4.4 in-lb. (0.5 Nm)
120V, 2-Wire, Single Phase:
1. Label Line 1 as L1.
2. Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow). (Fig 2)
3. Black CT wire connects to Port 1 on the Omnimeter. White CT wire
connects to Port 2. (Fig 2)
4. With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
5. To power the meter and get a voltage reference: Use a maximum 1.0
Amp inline fuse on L1. Connect one fuse holder pigtail to the breaker,
lug or an appropriate line-tap device, and connect the other pigtail to
16-22 AWG UL rated stranded copper wire for connection to the meter.
6. L1 connects to Port 7 on the Omnimeter, Neutral to Port 10. (Fig 2)
7. Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power can
be turned back on.
8. Meter will then begin cycling through meter values. For details go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
9. A video of proper install of a 120V system can be found here:
http://www.youtube.com/watch?v=ky9sgr1LTMk
120/240V, 120/208V, Single Phase, 3-Wire:
1. Label L1 and L2. (Arbitrarily assign labels.)
2. You will be using 2 CTs for this install. Label them CT1 and CT2.
3. Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow).
4. Fit CT2 around L2.
(Fig 1)
(Fig 2)
EKM-Omnimeter I v.3 Spec Sheet
12345678910
L1
L2/N
CT1
1 1
1
78
100
.
66.5
Load
current
Basic error %
Class 0.5 Class 1
0.05
I
b1.0
1.0
1.0
+
–
0.5
+
–
1.0
+
–
1.0
+
–
0.5
+
–
0.5
+
–
1.5
+
–
1.0
+
–
1.5
+
–
1.5
+
–
1.0
+
–
1.0
+
–
0.5(L)
0.8(C)
0.5(L)
0.8(C)
0.1
I
b~
Imax
0.1
I
b
0.2
I
b~
Imax
Power
factor
COSθ
120V, 240V
Single-Phase
2-Wire
Load
Blk Wht
Fuse

eKM Metering Inc.
EKM Metering Inc. – www.ekmmetering.com – info@ekmmetering.com – (831)425-7371
Black wire from CT1 connects to Port 1 on the Omnimeter. White wire
from CT1 connects to Port 2. (Fig3)
Black wire from CT2 connects to Port 3. White wire from CT2 connects
to Port 4. (Fig 3)
With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
To power the meter and get a voltage reference: Use a maximum 1
Amp inline fuse on L1 and L2. Connect one fuse holder pigtail to the
breaker, lug, or an appropriate line-tap device. Connect the other
pigtail to 16-22 AWG UL rated stranded copper wire.
Tap into L1 with a small stranded copper wire. This L1 tap connects to
Port 7 on the Omnimeter with a 1A fuse inline. (Fig 3)
Tap into L2 with a small stranded copper wire. This L2 tap connects to
Port 8 on the Omnimeter with a 1A fuse inline. (Fig 3)
Neutral connects to Port 10.
Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power
can be turned back on.
Meter will then begin cycling through meter values. For details go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
A video of a proper install of a 120V/240V system can be found here:
http://www.youtube.com/watch?v=ky9sgr1LTMk
Label L1, L2 and L3. (Arbitrarily assign labels.)
You will be using 2 CTs for this install. Label them CT1 and CT3.
Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow).
Fit CT3 around L3.
Black wire from CT1 connects to Port 1 on the Omnimeter. White wire
from CT1 connects to Port 2. (Fig 4)
Black wire from CT3 connects to Port 5 on the Omnimeter. White wire
from CT3 connects to Port 6. (Fig 4)
With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
To protect the meter, use a maximum 1.0 Amp inline fuse on each line.
To power the meter and get a voltage reference:
Tap into L1. Connect one fuse holder pigtail to the breaker, lug or an
appropriate line-tap device, and connect the other pigtail to16-22
AWG UL rated stranded copper wire for connection to the meter. This
L1 tap connects to Port 7 on the Omnimeter. Tap into L2 and L3 and
repeat the connection process. L2 tap connects to Port 8. Be sure to
add a jumper to Port 10. (Fig 4) L3 tap connects to Port 9.
Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power
can be turned back on.
Meter will then begin cycling through meter values. For details, go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
A video of a proper 120V-208V, 3-Wire, 3-Phase system can be found
here: http://www.youtube.com/watch?NR=1&v=upNgFNV6EDM
Label L1, L2 and L3. (Arbitrarily assign labels.)
You will be using 3 CTs for this install. Label them CT1, CT2 and CT3.
Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow).
Fit CT2 around L2.
Fit CT3 around L3.
Black wire from CT1 connects to Port 1 on the Omnimeter. White wire
from CT1 connects to Port 2. (Fig 5)
Black wire from CT2 connects to Port 3 on the Omnimeter. White wire
from CT2 connects to Port 4. (Fig 5)
Black wire from CT3 connects to Port 5 on the Omnimeter. White wire
from CT3 connects to Port 6. (Fig 5)
With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
Use a max 1.0 Amp inline fuse on each line to protect the meter.
To power the meter and get a voltage reference: Tap into L1 at the
breaker panel. Connect one fuse holder pigtail to the breaker, lug or an
appropriate line-tap device, and connect the other pigtail to 16-22
AWG UL rated stranded copper wire for connection to the meter. L1
connects to Port 7. Tap into L2 and L3 and repeat the connection
process. L2 connects to Port 8. L3 connects to Port 9. Neutral
connects to Port 10. (Fig 5)
Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power can
be turned back on.
Meter will then begin cycling through meter values. For details, go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
A video of proper install of a 120V-208V, 3-Phase, 4-Wire system can be
found here: http://www.youtube.com/watch?v=DeKiZddR0K8
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
120V-480V, 3-Phase, 4-Wire:
120V-415V, 3-Phase, 3-Wire: (Fig 3)
(Fig 4)
(Fig 5)
12345678910
L1
L2
L3
N
CT1
CT2
CT3
12345678910
Line1
Line2
Line3
CT1
CT3
12345678910
L1
L2
N
CT1
CT2
Blk Wht
Fuse
120~480V
Line to Line
3-Phase
4-Wire
Load
120~415V
Line to Line
3-Phase
3-Wire
Load
120/240V
120/208V
Single-Phase
3-Wire
Load
Blk Wht
Fuse
Blk Wht
Fuse
Note: 3-phase, 3-wire, 480v electrical systems cannot be metered with
this meter model. For 3-phase, 480v electrical systems, the Omnimeter
must have a true neutral in order to meter accurately and avoid being
damaged by high voltages. In cases where there is no neutral on the
system being metered, it may be possible to run a neutral from the
transformer or electrical panel, to the Omnimeter. Again, this meter
must have a true neutral in order to meter 3-phase, 480 volt, electrical
systems. This would make it a 3-phase 4-wire system and would also
require a 3rd current transformer.

Label L1, L2 and L3. (Arbitrarily assign labels.)
You will be using 3 CTs for this install. Label them CT1, CT2 and CT3.
Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow).
Fit CT2 around L2.
Fit CT3 around L3.
Black wire from CT1 connects to Port 1 on the Omnimeter. White wire
from CT1 connects to Port 2. (Fig 5)
Black wire from CT2 connects to Port 3 on the Omnimeter. White wire
from CT2 connects to Port 4. (Fig 5)
Black wire from CT3 connects to Port 5 on the Omnimeter. White wire
from CT3 connects to Port 6. (Fig 5)
With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
Use a max 1.0 Amp inline fuse on each line to protect the meter.
To power the meter and get a voltage reference: Tap into L1 at the
breaker panel. Connect one fuse holder pigtail to the breaker, lug or an
appropriate line-tap device, and connect the other pigtail to 16-22
AWG UL rated stranded copper wire for connection to the meter. L1
connects to Port 7. Tap into L2 and L3 and repeat the connection
process. L2 connects to Port 8. L3 connects to Port 9. Neutral
connects to Port 10. (Fig 5)
Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power can
be turned back on.
Meter will then begin cycling through meter values. For details, go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
A video of proper install of a 120V-208V, 3-Phase, 4-Wire system can be
found here: http://www.youtube.com/watch?v=DeKiZddR0K8
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
eKM Metering Inc.
EKM Metering Inc. – www.ekmmetering.com – info@ekmmetering.com – (831)425-7371
RS-485 and Pulse Output:
• Terminal 11 (A) connects to RS-485+ or T+ on the RS-485 network. Terminal 12 (B) connects to RS-485- or T-. Terminal 13 (G) is used for the RS-485
network (signal) ground if needed. Observe proper RS-485 network topology. Twisted pair wiring is recommended. Shielded twisted pair may be
benecial in electrically noisy environments or for very long runs. RS-485 supports up to 256 devices on up to 4000 feet wire. Terminating resistors
may be benecial.
• Terminals 14 and 15 are for pulse output. Pulse rate: 800 Impulse/kWh when set to 200A. Polarity sensitive. Maximum 27VDC, 27mA.
• Red LED on the meter face ashes 800 times/kWh(1 ash = 1.25Wh) when set to 200A.
All EKM meters, including the Omnimeter I v.3, have a Pulse Output. The Pulse Output pulses at a rate of 800 pulses per kilowatt hour when set to use
200 amp current transformers. This is the same rate that the red LED ashes on the meter face — 800 times/kWh. These are unpowered electronic dry
contact pulses that can be counted by standard electronic pulse counters. Pulse counters can be located up to 200 feet away from the Omnimeter.
*Note: Some Omnimeter I v.3 meters have a slightly different conguration for the pulse output terminals. These meters are identiable by a sticker on
the meter case showing the different conguration. In the case of these meters, please follow the direction of the sticker, not of this spec sheet.
Working Principle:
When the meter is working, the energy consumed by the user is transformed into voltage and current signals, which are sampled by sample circuits. A
pulse signal is then produced by a specialized IC. The Pulse signal is directly proportional to power consumption. The MCU records and stores the
corresponding energy use. The LCD screen displays the energy use. Recorded information and data can be transferred using the RS485 interface.
Data:
The LCD display shows 15 pieces of data: total energy consumption(kWh), reverse kWh, voltage L1,voltage L2,voltage L3, current(Amps) L1, current L2,
current L3, power(watts) L1, power L2, power L3, total power(watts), COSθ(power factor) L1, COSθ L2, and COSθ L3. Every ve seconds the LCD screen
will display a new piece of data. The meter also provides max demand(kW) data and the demand period can be set to one of three intervals:
15minutes, 30 minutes, or 60 minutes. The max demand can be reset to zero in software over RS485. The meter has four time-of-use tariffs(T1, T2, T3,
T4) to calculate the power during different time periods, and it can set up to four time periods per day, and specify the number of the tariff for that
period(from T1 to T4). The meter time can be set using the RS485 interface. By design the kWh cannot be reset. The meter will go at least 30 years
without power and still keep its kWh readings. In other words, the memory will not be erased if there is no power. See Figure 8 for meter display values:
Transport and Handling:
The meter should be handled with care, as there are precision components inside that could break and/or cause faulty readings should the meter
become damaged. The process of transportation, handling, and installation should be done according to the transportation and storage rule of
GB/T15464-1995. Keep the meter in the original packaging when stored. The storage temperature range should be 0–40ºC. The relative humidity
should be ≤85%. There should be no toxic chemicals present and no corrosive substances or gases in the air. The meters should be stacked on a
platform no more than ten units high.
Warranty:
Within two years from the date of sale, and on the condition that the user abide by the specications and installation instructions listed here, and the
sealing is kept completely intact. If the meter does not correspond with the rule of the enterprise standard, the meter shall be repaired free or replaced.
16 15 14 13 12 11
SO RS485
_+GA
B
#
11
12
13
14
15
LCD Display Data
Watts L3
Watts Total
Cosϴ L1 (Power Factor)
Cosϴ L2
Cosϴ L3
#
06
07
08
09
10
LCD Display Data
Amps L1
Amps L2
Amps L3
Watts L1
Watts L2
#
01
02
03
04
05
LCD Display Data
Total kWh (forward + reverse)
Reverse kWh
Volts L1 (Line 1)
Volts L2
Volts L3
(Fig 8)
CT Ratio Impulse Constant
100/26.6 1600
200/26.6 800
400/26.6 400
800/26.6 200
1500/26.6 106.67
3000/26.6 53.33
5000/26.6 32
(Fig 7)
(Fig 6)
Other EKM Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Dwyer Instruments
Dwyer Instruments 450A-1 Specifications-installation and operating instructions

Bresser
Bresser 7004020CM3000 instruction manual

Teledyne
Teledyne 430 user manual

Bante Instruments
Bante Instruments Bante900P instruction manual

Shot-Scope
Shot-Scope V2 user guide

AccuEnergy
AccuEnergy Acuvim-L Series user manual

Megger
Megger DLRO10HD user guide

EDT directION
EDT directION QC355TX user manual

UniData Communication Systems
UniData Communication Systems Starflow QSD manual

F.W. Bell
F.W. Bell 5200 Series instruction manual

Parker
Parker C3000 Instructions and Safety Considerations

Toro
Toro Turf Guard Installation setup manual