EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 1
1. Index
1. Index 1
2. Important User Information 2
2-1. Contact Information 2
2-2. Warranty and Liability 2
2-3. About Instruction Manual 3
2-4. Environment 3
2-5. CE Declaration 4
3. Safety Information 5
3-1. WARNING/CAUTION 5
4. Introduction 7
4-1. Main Features 7
4-2. Package Contents 8
5. Getting Started 9
5-1. Parts Name and Descriptions 9
5-2. Installation 11
5-3. Ventilator Tachomet er 14
6. Maintenance & Troubleshooting 15
6-1. Maintenance 15
6-2. Troubleshooting 16
7. Specification 17
7-1. Main Unit 17
7-2. Dimensions 18
7-3. Cables 19
7-4. Accessories List 19

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 2
2. Important User Information
Thank you for using EKO Products
Make sure to read this instruction manual thoroughly and to understand the contents before starting to operate the
instrument. Keep this manual at safe and handy place for whenever it is needed.
For any questions, please contact us at one of the EKO offices given below:
2-1. Contact Information
EKO INSTRUMENTS CO., LTD.
Asia, Oceania Region
www.eko.co.jp
EKO INSTRUMENTS Co., Ltd.
1-21-8 Hatagaya, Shibuya-ku
Tokyo, 151-0072 Japan
Te l : +81 (3) 3469-6711
Fax: +81 (3) 3469-6719
Europe, Middle East, Africa, South America Region
www.eko-eu.com
EKO INSTRUMENTS Europe B.V.
Lulofsstraat 55, Unit 32,
2521 AL, Den Haag, The Netherlands
Te l : +31 (0)70 3050117
Fax: +31 (0)70 3840607
North America Region
www.eko-usa.com
info@eko-usa.com
EKO INSTRUMENTS USA Inc.
95 South Market Street, Suite 300
San Jose, CA 95113 USA
Te l : +1 408-977-7751
Fax: +1 408-977-7741
2-2. Warranty and Liability
For warranty terms and conditions, contact EKO or your distributor for further details.
EKO guarantees that the product delivered to customer has been verified, checked and tested to ensure that
the product meets the appropriate specifications. The product warranty is valid only if the product has been
installed and used according to the directives provided in this instruction manual.
In case of any manufacturing defect, the product will be repaired or replaced under warranty. However, the
warranty does not apply if:
Any modification or repair was done by any person or organization other than EKO service
personnel.
The damage or defect is caused by not respecting the instructions of use as given on the product
brochure or the instruction manual.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 3
2-3. About Instruction Manual
Copy Rights Reserved by EKO INSTRUMENTS CO., LTD. Making copies of whole or parts of this
document without permission from EKO is prohibited.
This manual was issued: 2016/09/26
Version Number: 2
2-4. Environment
1. WEEE Directive 2002/96/EC
(Waste Electrical and Electronic Equipment)
This product is not subjected to WEEE Directive 2002/96/EC however it should not be mixed with general
household waste. For proper treatment, recovery and recycling, please take this product(s) to designated
collection points.
Disposing of this product correctly will help save valuable resources and prevent any potential negative
effects on human health and the environment, which could otherwise arise from inappropriate waste
handling.
2. RoHS Directive 2002/95/EC
EKO Instruments has completed a comprehensive evaluation of its product range to ensure compliance with
RoHS Directive 2002/95/EC regarding maximum concentration values for substances. As a result all products
are manufactured using raw materials that do not contain any of the restricted substances referred to in the
RoHS Directive 2002/95/EC at concentration levels in excess of those permitted under the RoHS Directive
2002/95/EC, or up to levels allowed in excess of these concentrations by the Annex to the RoHS Directive
2002/95/EC.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 4
2-5. CE Declaration
DECLARATION OF CONFORMITY
We: EKO INSTRUMENTS CO., LTD
1-21-8 Hatagaya Shibuya-ku,
Tokyo 151-0072 JAPAN
Declare under our sole responsibility that the product:
Product Name: Ventilation unit for Pyranometer
Model No.: MV-01
To which this declaration relates is in conformity with the following harmonized
standards of other normative documents:
Harmonized standards:
EN 61326-1:2013 Class A (Emission)
EN 61326-1:2013 (Immunity)
Following the provisions of the directive:
EMC-directive: 2014/30/EU
Low Voltage- directive: 2006/95/EC
Date: Jan. 14, 2016
Position of Authorized Signatory: Deputy General Manager of Quality Assurance Dept.
Name of Authorized Signatory: Shuji Yoshida
Signature of Authorized Signatory:

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 5
3. Safety Information
EKO Products are designed and manufactured with consideration for safety; however, please make
sure to read and understand this instruction manual thoroughly to be able to operate the instrument
safely in the correct manner.
WARNING
CAUTION
Attention to user; pay attention to the instructions given on the
instruction manual with this sign.
HIGH
VOLTAGE
WARNING
High voltage is used; pay special attention to instructions given on
this instruction manual with this sign to prevent electric leakage
and/or electric shocks.
HIGH
TEMPERATURE
WARNING
Touching or getting close to the devise may lead to burn.
3-1. WARNING/CAUTION
1. Setup
The installation base or mast should have enough load capacity for the instrument to be mounted.
Fix the pyranometer securely to the base or mast with bolts and nuts; otherwise, the instrument
may drop due to gale or earthquake, which may lead to unexpected accidents.
Make sure the instrument and the cables are installed in a location where they will not get soaked.
Do not use this product in environment where corrosive gas, such as ammonia and sulfurous acid
gas, are generated. It may cause malfunction.
Do not install in area that cause salt damages. It may cause malfunction by paint peeling off or
corrosion. When installing in area with risk of salt damages, make sure to take following
measures: 1. Wrap the connector with self-fusing tape, 2. Change the fixing screw to bolt screw
made of aluminum, 3. Run the cables in resin pipe or metal pipe treated with salt-resistant paint
such as molten zinc plating, 4. Periodcally clean.
Do not use this instrument in vacuum environment.
If the cable and main unit are in risk for getting damaged by birds and small animals, protect the
cable and the main unit by using: 1. Reflective tape, 2. Repellent, 3. Cable duct, 4. Installing
bird-spike

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 6
2. Fan Operation
Do not let your body parts, clothes, papers, animals and plants get close to the MV-01 while it is in
operation. You m a y be injured by getting your body part or clothing caught into the fan, or may
cause accidents by damaging the fan.
3. Power Supply
Make sure to check the power supply voltage and type (AC/DC) before connecting the fan unit to
the power supply. Connecting the fan unit to other power supplies than specified will lead to
damage and accidents
Use this ventilation unit with 2A fuse connected to the power supply line in series. Without
connecting the fuse, it has risks of generating heat and fire due to large-current flowing by the
power supply when internal damage on the electronic swill occurs.
4. High Temperature
Do not touch metal parts while heater is in operation as it will become high temperature. You may
get burn. Use the MV-01 in place where out of reach of children.
To avoid the temperature increase, always turn on the fan first before turning on the heater.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 7
4. Introduction
EKO’s Ventilation Unit MV-01 can be used in combination with MS-80 pyranometer models (MS-80, MS-80A and
MS-80M). The MV-01 will reduce the need for maintenance and assures the availability of solar irradiance data
when deployed in cold climate regions or desert environments. Due to the compact and integrated design with the
MS-80 pyranometer, the heating and airflow dynamics are optimized. The power consumption of the ventilator is
only 1.9 Watts, which makes it suitable for solar powered systems. When the heater is activated the total power
consumption will be about 8.9 watt, which is sufficient to prevent snow and ice deposition on the sensor (dome and
sun screen).
The pyranometer with ventilator can be mounted in horizontal or tilted plane, which make it suitable for PV
monitoring applications. The Ta c h o output provides a data pulse to monitor the fan speed.
For the pyranometers operated in harsh environments, the irradiance measurements can be easily affected by
environmental factors. In such case the MV-01 will keep the pyranometer dome free of dew, ice and snow. In
combination with the MV-01 ventilator the best possible measures are taken for reliable unattended operation.
4-1. Main Features
Low power consumption (power consumption: 8.9W, fan 1.9W, heater: 7W)
Wide range of operating temperature (-40℃to +70℃), the MV-01 can be operated in many different
areas of the world.
Overheating protection trough temperature fuse
Using the ventilation with long expected life has made possible to offer 2-year warranty.
By measuring the rotation signal (pulse signal) of the MV-01, the rotation frequency of the fan can be
monitored.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 8
4-2. Package Contents
Check the package contents first; if any missing item or damage is noticed, please contact EKO immediately.
Figure 4-1. Attached Fixing Parts and Bots
Table 4-1 Package Contents
Standard Items
Qty.
Remarks
Ventilation Main Unit MV-01
1 set
Constructed with combination of heater unit and fan unit
Power Supply Cable [*]
1pc
Heater Fixing Part A
1pc
Heater Fixing Parts B
2pcs
Heater Fixing Parts C
2pcs
Screws for Fixing Parts
4pcs
M3 x 6mm, 2pc spare screws attached.
Fixing Bolts for Main Unit
2pcs
M6 x100mm, bolts used for fixing the MV-01 main unit in
installation position
Fixing Bolts
5pcs
M5 x 10mm, bolts used for fixing pyranometer to MV-01, Fine pitch
thread
Washers (M6)
4pcs
Nuts (M6)
2pcs
Allen key (M5)
1
Used for fixing Pyranometer to MV-01
Inspection Report
1
Instruction Manual
1
Download from EKO website
Quick Start Guide
1
[*] Standard length of the Power Supply Cable is 10 meters. Contact EKO when longer cables are required.
Pyranometer is not included in this package.
Heater Fixing Parts A Heater Fixing Parts C x2
Screw for Fixing Parts x2 (+spare x2)
Fixing Bolts x5 (M5 x10mm, fine
pitch)
Fixing Bolts for Main Unit x2(M6 x100mm) Washers x4(M6) Nuts x2(M6)
Heater Fixing Parts B x2

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 9
5. Getting Started
5-1. Parts Name and Descriptions
Each part name and its main functions are described below.
Parts Names
A. Heater Unit
B. Temperature Fuse
C. Fan Unit
D. Cable Connector
E. Leveling Screws
Figure 5-1. Parts Names
1. Heater Unit
Heater can be used together with the fan unit to increase the forced air temperature. When the instruments
are used in cold regions and/or snowy regions, turn on the heater unit to prevent snow and ice getting on the
pyranometer dome and sun screen.
*Do not operate the heater in case the ambient temperature will be over 50℃and the heater supply voltage
more than DC13.2V. Thermal fuse may be activated and limits the heater current.
MV-01 cannot be used for the purpose to melt snow. Use the MV-01 constantly before snow starts to fall.
Also the heater should be used with the fan unit. Using heater alone for continuous time may cause the
temperature fuse to go off and require replacing the Heater.
2. Temperature Fuse
The temperatre fuse is applied to prevent excessive temperature increase of the heater for safe operation
and protection of the sensor. The temperature fuse will be activated at a temperature of 115℃and limits the
heater current.
A
E
B
D
C
Table 5-1. Parts Name

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 10
3. Fan Unit
Forced air provide a constant turbulent airflow accross the pyranometer glass dome. The dome will remain
free of condensation, snow and ice. It will rduce the amount of dust that can deposit to the dome.
4. Cable / Connector
MV-01 comes with 10m cable*.
Durable materials are used for cable and connector; pin terminals are attached to the cable ends for easy
connection with DC power supply and data logger.
*If you require a longer cable than the standard 10m and/or round terminals or fork terminals, please contact
EKO. (See [7-4. Accessories] section for optional items)
5. Leveling Screws
Leveling Screws are used for maintaining the pyranometer installed on MV-01 in horizontal position.
The Leveling Screws are not included in this package; use the leveling screws attached on the Pyranometer
MS-80

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 11
5-2. Installation
1. Installing the Pyranometer on MV-01
(1) Remove the three leveling screws from MS-80.
(2) Attach the heater fixing parts A and B (x2) to MS-80 using provided fixing bolts (M5 x 10mm, 3pcs).
*Make sure the position and orientation of fixing parts are correct.
(3) Shift the heater behind and put the MS-80 on the MV-01 from the top and fix the MS-80 to ventilation unit
using provided fixing bolts (M5 x 10mm, 2pcs). Then attach the leveling screws, which were removed
from MS-80, to MV-01.
*Make sure the MS-80 cable connector and MV-01 cable connector are facing towards the same
direction.
(4) Place the heater on the heater fixing parts which are attached to MS-80, and fix it with heater fixing parts
C (x2) in the direction shown on the figure and fixing screws (M4 x 6mm, 2pcs).
(5) Level the MV-01 to horizontal position.
*If installing in the instruments in tilted position, adjust the level on horizontal surface first then install to
the tilted position.
(6) Fix the MV-01 on mounting plate using fixing bolts (M6 100mm, 2pcs).
Then insert cables to MV-01 and MS-80. Attach sun screen on MS-80
(1)
(2)
(3)
(4)
(5)
(6)
Fixing Parts B
Fixing Parts B
Fixing Parts A
Fixing Parts C+Fixing screw
Figure 5-2. Installing the Pyranometer on MV-01

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 12
2. Air Filter Installation (Optional)
Before starting replacing the air filter, make sure the Ventilator Unit power is turned OFF. You may get
burned by the heater and/or get injured by fan if Ventilator Unit is left powered ON. Work in a stable location
to prevent dropping the instruments.
(1) Remove the filter cover locks by inserting flathead screwdriver in the slots (A) under the front (connector)
side of the instrument
(2) Insert a finger from B, and remove the 2 other filter cover locks. Pull the filter cover from the front side
of the instrument.
(3) Place the air filter on the filter cover. Then insert the filter cover from the front side of the instrument and
lock the 4 locks.
3. Wiring
To extend the cable lifetime, place the cable in a cable conduit and make sure that the cables are not
exposed to direct sun light or rain/wind. Fasten the cable does not swing or move by wind blowing. Excess
length of cable should be cut.
1) Make sure the cable connector and the main unit chassis connector are in right position before inserting.
After inserting the cable connector properly, rotate the coupling nut to fix the connector. Do not use
excessive force as the connector will break.
2) Cable wiring
The cable contains following five color wires:
2-1. Power Supply (Fan)
Apply a power supply with a rated specification (DC 12V±10%, 1.9W). Note the input voltage can
drop when longer cable are used. Make sure the polarity is correct; otherwise, the fan will be
damaged(Voltage drop in AWG22 cable: -0.17V/10m)
No.
Wire Color
Connect to
1.
Brown
Fan Power Supply Input (+)
2.
White
Fan Power Supply Input (-)
3.
Blue
Fan Rotation Signal Output (Tacho)
4.
Black
Heater Power Supply Input (no polarity *1)
5.
Gray
Heater Power Supply Input (no polarity)
①
②
Figure 5-3. Air Filter installation

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 13
2-2. Power Supply (Heater)
*1For the purpose of protection of power supply side, apply to connect a fuse in series (2A).
Apply a power supply with a rated specification (DC 12V±10%, 7W). Note the input voltage can
drop when longer cable are used.
The temperature fuse (operating temperature: approx. 115℃) is installed in the heater to prevent
causing fire due to applying voltage more than the heater specification range.
2-3. Ventilator Tachometer Signal
See [5-3. Ventilator Tachometer] for details.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 14
5-3. Ventilator Tachometer
1. Tachometer Signal
The tach output can be monitored and conveys rpm information in the form of a square wave (2 block pulses
per revolution). The frequency of this square wave output is proportional to the rotation of the shaft. The tacho
signal can be measured using a frequency meter or pulse counter (12VDC / Pulse signal ~100Hz /
~3,000rpm).
*Fixed resistance of 2kΩ shown on the above figure is not provided and need to be prepared by customer.
(Fixed resistance more than 2kΩ can be measured.)
1/2
Rotation
100.0 Hz
2kΩ
Frequency
Meter
Fan Power Supply
12.0 Vdc
Figure 5-4. Tachometer Signal
Tel.: +11 3976-4003 • 3999-7737
vendas@romiotto.com.br
www.romiotto.com.br

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 15
6. Maintenance & Troubleshooting
6-1. Maintenance
It is recommended to check and do the following:
Ta b l e 6-1. Maintenance Items
Items
Frequency
How To
Effects
Visual Check
Monthly
Check for any cracks and scratches
on Fan and Heater Units.
Using damaged parts may lead to
electrical shock or performance
degradation. Replace the damaged
parts. For replacing the parts, please
contact your nearest distributor or
EKO directly.
Check Spirit Level
Weekly
Check the pyranometer spirit level;
readjust when necessary.
(applicable only when installed in
horizontal level)
Cause directional response error
Check Cable
Monthly
Check for any damages,
disconnection of cables, and loose
connector.
Damaged cables and/or loose
connectors may lead to malfunction.
Check Installation
Monthly
Check for loose bolts, any damages
to the installation base/plate.
Products may drop due to loosen
bolts and may get damaged.
Check Fan
Operation
Monthly
Check for any obstacles like trash,
plants, and bugs are stuck in the fan;
check for any noise from the fan.
Continuing use of fan with things
stuck in fan may lead to damage
and/or cause fire.
Replace Fan
Every
2 years
Replace the fan. For replacing the
fan, please contact your nearest
distributor or EKO directly.
Continuing use of fan after its lifetime
may lead to fan malfunction,
decrease in rotation frequency, and
operation stop.
Clean Air Filter
(Optional)
Monthly
Clean the air filter
Ventilation capacity will be lower
when the air filter gets soiled.
Replace Air Filter
(Optional)
Within
6 months
Replace the air filter within 6 months.
Ventilation capacity will be lower
when the air filter gets soiled.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 16
6-2. Troubleshooting
Check the following items in case of trouble with the instrument. If any questions should remain, contact EKO
for further technical support.
Ta b l e 6-2. Troubleshooting
Failure
Action
Fan does not rotate
Check for proper connection, supply power and voltage, and make sure there are no
loose connections. Also check for any obstacles like trash, plants and bugs are not stuck
in the fan.
Fan RPM is low
Make sure the supply voltage is appropriate. Long cables cause a supply voltage drop;
adjust to the appropriate voltage level on the plug side.
Check for any trash, plants and bugs are not stuck in the fan.
If air filter is used, clean or replace the air filter
Fan making noise
Check for any trash, plants and bugs are not stuck in the fan.
Heater temperature
does not get hot
Check for proper connection, supply power type and voltage.
Make sure the resistance between heater lines +/- is 21Ω+/-10%. When the temperature
fuse is active, it will be in open circuit condition.

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 17
7. Specification
7-1. Main Unit
Ta b l e 7-1. Main Unit Specification
Characteristics
Details
Compatible Instruments
MS-80/80A/80M
Operating Voltage Range
DC 10.8 to 13.2V
Power Consumption
(When DC12V input)
Fan: 1.9W + Heater: 7W
Operating Temperature Range
-40℃to +70℃(Ambient Temperature)
Temperature increase
(Te m p increase of glass dome)
<0.25℃(when heater is 0W)
>1.0℃(when heater is 7W)
MS-80’s Zero Offset A + B
(Only fan in operation)
<1W/m2
MS-80’s Zero offset A + B
(with fan & heater in operation)
<1W/m2(when heater is 7W)
Tacho output
Pulse / 100Hz / 3000 RPM
Environmental Protection (IP)
IP 54 equivalent (IEC60529)
Standard Cable Length
10m (Optional: 20m, 30m, 50m)
Output Cable (Outer diameter)
AWG22: 0.5mm2x 5pins (Φ6.7mm)
Surface Treatment
Acrylic Painted
Heater Resistance
Approximately 21Ω
Outer Dimension
Φ138mm x 69mm (Fan Unit)
Φ138mm x 141mm (with Pyranometer)
Mass
0.7kg (without cable)
Air Filter Replacement Period
(Optional)
<6 months

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 18
7-2. Dimensions
Below is the dimension of MV- 01.
Table 7-2. Dimensions
MV-01
A. Fixing Holes Pitch
120 mm
B. Body Height (Fan Unit part)
53 mm
C. Leveling Screw Height*
16 mm
D. Overall width
Φ138 mm
*Use leveling screws which are attached on MS-80/80A/80M by attaching them to MV-01
A
B
D
C
Figure 7-1. MV-01 Dimensions

EKO INSTRUMENTS CO., LTD. Ventilation Unit MV-01 Instruction Manual V2
Pg. 19
7-3. Cables
See [5-2. Installation, 2. Wiring] for power supply cable wiring details.
7-4. Accessories List
Ta b l e 7-3. Accessories List
Option Items
Remarks
Output Cable
Cable Length: 20m, 30m, 50m
Terminals: Fork terminal, round terminal
Air Filter Kit
Filter: Polyurethane Foam
No. Wire Color
1. Brown
2. White
3. Blue
4. Black
5. Gray
Figure 7-2. Cable
Tel.: +11 3976-4003 • 3999-7737
vendas@romiotto.com.br
www.romiotto.com.br
Table of contents
Other EKO Fan manuals
Popular Fan manuals by other brands

Fanimation
Fanimation Draco FP3220CH Specification sheet

Turn of the century
Turn of the century Knit owner's manual

Domus Ventilation
Domus Ventilation SVC100B installation instructions

Panasonic
Panasonic WhisperWelcome FV-05VFM2 installation instructions

Cumberland
Cumberland 48 INCH MEGA-FLOW CONE FAN installation manual

Hunter
Hunter Ashbury 87001 owner's manual

DYNABREEZE
DYNABREEZE FA-26144 Instructions & user's manual

enervent
enervent eWind Pelican installation instructions

Lunos
Lunos Silvento ec installation manual

TZS First AUSTRIA
TZS First AUSTRIA FA-5560-4 instruction manual

Hunter
Hunter Gallegos installation manual

Trox Technik
Trox Technik X-GRILLE installation manual