Electro Industries/GaugeTech Shark MP200 User manual

V.1.07
June 24, 2019

This page intentionally left blank.

Doc# E180701 i
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
MP200TM in Enclosure Installation and Operation Manual Version 1.07
Published by:
Electro Industries/GaugeTech
1800 Shames Drive
Westbury, NY 11590
Copyright Notice
All rights reserved. No part of this publication may be reproduced or transmitted in
any form or by any means, electronic or mechanical, including photocopying, record-
ing, or information storage or retrieval systems or any future forms of duplication, for
any purpose other than the purchaser's use, without the expressed written permission
of Electro Industries/GaugeTech.
© 2019 Electro Industries/GaugeTech
Shark® is a registered trademark of Electro Industries/GaugeTech. The distinctive
shapes, styles and overall appearances of all Shark® meters are trademarks of
Electro Industries/GaugeTech. MP200TM is a trademark of Electro Industries/Gauge-
Tech.
LonWorks® is a registered trademark of Echelon Corp.
BACnet® is a registered trademark of ASHRAE.
Modbus® is a registered trademark of Schneider Electric, licensed to the Modus
Organization, Inc.

Doc# E180701 ii
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Customer Service and Support
Customer support is available 8:00 am to 8:00 pm, Eastern Standard Time, Monday
through Friday. Please have the model, serial number and a detailed problem descrip-
tion available. If the problem concerns a particular reading, please have all meter
readings available. When returning any merchandise to EIG, a return materials
authorization number is required. For customer or technical assistance, repair or
calibration, phone 516-334-0870 or fax 516-338-4741.
Product Warranty
Electro Industries/GaugeTech warrants all products to be free from defects in material
and workmanship for a period of four years from the date of shipment. During the
warranty period, we will, at our option, either repair or replace any product that
proves to be defective.
To exercise this warranty, fax or call our customer-support department. You will
receive prompt assistance and return instructions. Send the instrument, transporta-
tion prepaid, to EIG at 1800 Shames Drive, Westbury, NY 11590. Repairs will be made
and the instrument will be returned.
This warranty does not apply to defects resulting from unauthorized modification,
misuse, or use for any reason other than electrical power monitoring. The MP200TM in
Enclosure is not a user-serviceable product.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED
OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE. ELECTRO INDUSTRIES/
GAUGETECH SHALL NOT BE LIABLE FOR ANY INDIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES ARISING FROM ANY AUTHORIZED OR
UNAUTHORIZED USE OF ANY ELECTRO INDUSTRIES/GAUGETECH
PRODUCT. LIABILITY SHALL BE LIMITED TO THE ORIGINAL COST OF
THE PRODUCT SOLD.

Doc# E180701 iii
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Use of Product for Protection
OUR PRODUCTS ARE NOT TO BE USED FOR PRIMARY OVER-CURRENT PROTECTION.
ANY PROTECTION FEATURE IN OUR PRODUCTS IS TO BE USED FOR ALARM OR
SECONDARY PROTECTION ONLY.
Statement of Calibration
Our instruments are inspected and tested in accordance with specifications published
by Electro Industries/GaugeTech. The accuracy and a calibration of our instruments
are traceable to the National Institute of Standards and Technology through
equipment that is calibrated at planned intervals by comparison to certified standards.
For optimal performance, EIG recommends that any metering device, including those
manufactured by EIG, be verified for accuracy on a yearly interval using NIST trace-
able accuracy standards. In general, EIG metering devices should not require regular
adjustments to maintain published accuracy.
Disclaimer
The information presented in this publication has been carefully checked for reliabil-
ity; however, no responsibility is assumed for inaccuracies. The information contained
in this document is subject to change without notice.
Symbols Used in This Manual
This warning symbol indicates that the operator must refer to an
important explanation in the operating instructions. The word follow-
ing the symbol indicates the type of warning being given.
Ce symbole d'avertissement indique que l'opérateur doit se référer à
une explication importante dans les instructions d'utilisation. Le mot suivant le symbole
indique le type d'avertissement ne soit donné.
CAUTION! The instructions given must be followed to prevent damage to
equipment.
Les instructions doivent être respectées pour éviter
d'endommager l’équipement.
WARNING! The instructions given must be followed to prevent serious
injury to people.
Les instructions doivent être respectées pour d’éviter de graves
blessures aux personnes.

Doc# E180701 iv
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
About Electro Industries/GaugeTech (EIG)
Founded in 1975 by engineer and inventor Dr. Samuel Kagan, Electro Industries/
GaugeTech changed the face of power monitoring forever with its first breakthrough
innovation: an affordable, easy-to-use AC power meter.
More than forty years since its founding, Electro Industries/GaugeTech, the leader in
power monitoring and control, continues to revolutionize the industry with the highest
quality, cutting edge power monitoring and control technology on the market today.
An ISO 9001certified company (certificate on the EIG website at https://elec-
troind.com/about-electro-industries/), EIG sets the industry standard for advanced
power quality and reporting, revenue metering and substation data acquisition and
control. EIG products can be found on site at mainly all of today's leading manufactur-
ers, industrial giants and utilities.
EIG products are primarily designed, manufactured, tested and calibrated at our facil-
ity in Westbury, New York.

Doc# E180701 TOC-1
Table of Contents
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Table of Contents
Customer Service and Support ii
Product Warranty ii
Use of Product for Protection iii
Statement of Calibration iii
Disclaimer iii
Symbols Used in This Manual iii
About Electro Industries/GaugeTech (EIG) iv
1: Introduction 1-1
1.1: Product Handling 1-1
1.2: Safety Precautions 1-2
1.3: Storage 1-3
1.4: Compliance 1-3
2: Installation 2-1
2.1: Installation Step 1 - Unpack the Enclosure 2-2
2.2: Installation Step 2 - Drill the Wiring Holes 2-4
2.2.1: Removing and Reinstalling the Panel 2-7
2.3: Installation Step 3 - Mount the Enclosure 2-9
2.4: Installation Step 4 - Install the Display 2-14
2.5: Installation Step 5 - Lock the Enclosure 2-18
3. Electrical Wiring 3-1
3.1: Wiring Instructions 3-2
4: Operation 4-1

Doc# E180701 TOC-2
Table of Contents
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
4.1: Overview 4-1
4.2: Troubleshooting 4-1
5. Maintenance 5-1
A. Removing a Meter from Service A-1
A.1: Removing the Meter A-1
A.2: Reinstalling the Meter A-6

Doc# E180701 1-1
1:Introduction
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1.1: Product Handling
Every effort is made to insure that the equipment arrives undamaged and ready to be
installed. Packing is designed to protect internal components as well as the enclosure.
Do not remove protective packing until you are ready to install the equipment.
When you receive the equipment, you should inspect the shipping container for any
obvious signs of rough handling and/or external damage that occurred during trans-
portation. Record any external and internal damage for reporting to the transportation
carrier and EIG. All claims should be as specific as possible and include general order
numbers.
You will find a plastic bag of instruction booklets and/or CDs in the shipping container.
Store these documents in a safe place.
1: Introduction
The MP200TM in Enclosure lets you expand your switchgear capability and/or easily
meter circuits without expensive and time-consuming redesign. Simply mount the
enclosure in any convenient location, next to your switchgear or on a wall, and you are
ready to go, with no downtime.
This is an ideal solution for a retrofit when there is no metering compartment avail-
able. The unit comes standard with a NEMA 1 rated enclosure and is factory wired with
the metering system installed. Standard safety equipment includes voltage fuses and
shorting blocks for current transformers.
The enclosure can be ordered with either the MP200-Y three phase circuit configura-
tion or the MP200-S single phase circuit configuration, and comes standard with
either a 3”x5” or 5”x7” touch-screen display. BACnet® or LonWorks® protocol is
available as an add-on to the existing standard Modbus® capability. See Chapter 6 for
ordering instructions.
CAUTION! READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED IN
THIS DOCUMENT BEFORE ATTEMPTING TO UNPACK, INSTALL, OPERATE,
OR MAINTAIN THIS EQUIPMENT.

Doc# E180701 1-2
1:Introduction
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1.2: Safety Precautions
WARNING! All safety codes, safety standards, and/or regula-
tions must be strictly observed in the installation, operation,
and maintenance of this device.
Hazardous voltages that can cause death or severe personal injury are present inside
enclosure. Follow proper installation, operation, and maintenance procedures to avoid
these voltages.
Avertissement! tous les codes de sécurité, normes de sécurité et règlements
doivent être suivis strictement dans l'installation, le fonctionnement et la
maintenance de cet appareil.
Des tensions dangereuses peuvent provoquer la mort ou des blessures graves. suivre
l'installation adéquate, le fonctionnement et les procédures de maintenance pour
éviter ces tensions.
Completely read and understand the material presented in this document before
attempting installation, operation, or application of the equipment. In addition, only
qualified persons should be permitted to perform any work associated with the
equipment. Any wiring instructions presented in this document must be followed
precisely. Failure to do so could cause permanent equipment damage.
All possible contingencies that may arise during installation, operation, or mainte-
nance, and all details and variations of this equipment do not purport to be covered by
these instructions. If further information is desired by purchaser regarding a particular
installation, operation, or maintenance of particular equipment, contact an Electro
Industries/GaugeTech (EIG) representative.

Doc# E180701 1-3
1:Introduction
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1.3: Storage
Although it has been well packaged, this equipment should not be stored outdoors. If
the equipment is to be stored indoors for any period of time, it should be stored with
its protective packaging in place. Refer to the MP200TM Metering System Installation
and Operation manual, on the enclosed CD, for the meter’s storage requirements.
The temperature rating for enclosure storage is (-20 to +60) oC/(-4 to +140) oF.
1.4: Compliance
UL / cUL Listed, UL508A, File number: E358101.

Doc# E180701 1-4
1:Introduction
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
This page intentionally left blank.

Doc# E180701 2-1
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2: Installation
WARNING! All safety codes, safety standards, and/or regulations shall be
strictly observed in the installation, operation, and maintenance of this
device. This device shall be installed in an un-energized condition
and as per the National Electric Code.
AVERTISSEMENT! Tous les codes de sécurité, normes de sécurité et règlement
doivent être suivis strictement pour l'installation, le fonctionnement et la maintenance
de cet appareil. Cet appareil doit être installé hors tension conformément au
code électrique national (National Electric Code).
Choose a mounting location that offers a flat, rigid mounting surface capable of
supporting the weight of the equipment. The unit weighs 48.5 lbs (22 kg) maximum.
Mount the equipment in a suitable environment. This enclosures is designed for NEMA
1 rated environments and is manufactured of painted steel.
Check to make certain that there are no pipes, wires, or other mounting hazards in
the immediate mounting area that could create a problem. Also make sure you have
enough clearance around the enclosure to run wiring to it safely. EIG recommends at
least 2 feet of clearance around the enclosure. See Section 2.1 for enclosure dimen-
sions.
Carefully remove all packing material from the unit. Even though an equipment
inspection was made when the equipment was received, make another careful inspec-
tion of the enclosure and the devices inside as packing material is removed. Be
especially alert for distorted metal, loose wires, or damaged components. This is
important because wiring can come loose in shipping and could cause a short circuit
or voltage to be on the wrong terminal.
WARNING! Extreme care shall be taken when mounting the enclosure, and
making wire entry holes, to prevent metal chips, filings, and other contami-
nants from entering the enclosure which may damage the equipment and
create a hazardous condition.
AVERTISSEMENT! Attention extrême lors de la monture de l'enceinte et lors de la
mise à terre pour prévenir les articules métalliques, remplissage et autre contaminant
de l'entrée de l'enceinte qui peuvent provoquer une condition dangereuse de l'équipe-
ment.

Doc# E180701 2-2
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.1: Installation Step 1 - Unpack the MP200TM in Enclosure
The MP200TM in enclosure ships in two parts:
• The meter enclosure
• The mountable color display
The display is shipped separately in order to protect it from being damaged during
shipping.
Instructions for the enclosure begin on the next page. Section 2.4 contains
instructions for mounting the display.

Doc# E180701 2-3
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The enclosure components are shown in the image below:
• A: MP200 current inputs (24 of them)
• B: CT shorting blocks (8 of them)
• C: CT connections
• D: Voltage inputs and 5 fuses
• E: Earth ground on inside of enclosure
• F: Ground wire on enclosure door
• G: Cable assembly
• H: Display connectors
• I: Hole for mounting the display
• J: If ordered, optional Add-on Protocol - ProtoCom/ProtoCom-Lon
Figure 2.1: MP200TM in Enclosure as Shipped
J
F
E
H
G
I
D
B
A
C

Doc# E180701 2-4
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.2: Installation Step 2 - Drill the Wiring Holes
Cut the holes you need in the bottom of the enclosure for the power, CT, and
communications wiring. See the figure below for the allowable location.
Figure 2.2: Location for Punch Entries
The drawings show the area in the bottom of the enclosure where wiring holes can be
cut: 1” [25.40mm] from the front of the enclosure, 1.5” [38.10mm] from the right
side of the enclosure, 1.5” [38.10mm] from the back of the enclosure, and 3.75”
[95.25mm] from the left side of the enclosure.
PP
LQ
PP
LQ
3.75in
[95.25mm]
1.00in[25.40mm]
1.50in[38.10mm]
1.50in[38.10mm]
BOTTOM VIEW OF ENCLOSURE
WALL
You can cut holes
inside this area

Doc# E180701 2-5
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
CAUTIONS!
• There are numerous methods for making wire entry holes in the enclosure but it
is imperative that no loose material generated during the process remains in the
enclosure. During installation and cutting the wire holes, all equipment mounted
inside or on the enclosure shall be protected from loose material.
• No matter what procedure is used the installer shall verify that the hole cutting
process will not damage any of the wiring or components installed inside or on
the enclosure.
a. The two recommended procedures for cutting the wire entry holes are as
follows:
• Use a "C" frame punch to cut the wire entry holes. This type of punch
does not require a pilot hole. A typical "C" frame punch is shown below.
Figure 2.3: “C” Frame Punch
• Regular punch:
1. Place a magnet inside the enclosure where the pilot hole is to be cut
and completely cover the area with masking tape (or other very
sticky tape).
2. Drill the pilot hole from the outside and do not let the drill pass more
than ¼" into the enclosure.
3. Remove the tape, magnet, and cuttings and punch the hole.

Doc# E180701 2-6
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
b. After wiring and before energizing, vacuum the inside of the enclosure to
make sure that it is free of foreign material. If a vacuum is not available
use an alternate method to clean the inside of the enclosure. Do not use
compressed air (or pressurized gas) to clean the inside of the enclosure as
this may force cuttings into areas that cannot be seen, creating a hazard-
ous condition.
IMPORTANT! All wire entry into the enclosure shall be accomplished with
the use of recognized fittings or strain reliefs. Bare holes shall not be
used.
NOTE: The panel can be removed to facilitate drilling of wiring holes. See the follow-
ing procedure.

Doc# E180701 2-7
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.2.1: Removing and Reinstalling the Panel
If it will make it easier to drill the wiring holes, you may remove the panel.
Figure 2.4: Removing the Panel
1. If the MP200TM in enclosure is equipped with a ProtoCom/ProtoCom-Lon add-on
protocol unit remove all connections from the ProtoCom/ProtoCom-Lon (I).
2. Disconnect the green ground wires from the door (E).
3. Open the cable clamps on the door (J) and remove the cable assembly (F).
4. Remove the green ground wires on the lower left side of the enclosure (D).
5. Remove the four nuts, one in each corner of the panel [K].
6. Carefully remove the panel from the enclosure.
Drill the wiring holes per the instructions in Section 2.2. You can then re-install the
panel.
1. Place the panel on the four mounting studs in the enclosure and install and tighten
a nut on each of the studs (K).
I
E
D
J
K
F

Doc# E180701 2-8
2: Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2. Connect the green ground wires to the ground stud on the bottom left of the
enclosure (D).
3. Insert the cable assembly (F) into the cable clamps on the door (J).
4. Connect the two green ground wires to the stud on the door (E).
5. If the MP200TM in enclosure is equipped with a ProtoCom/ProtoCom-Lon, attach
all connections to it (I).
Continue to Section 2.3 to mount the enclosure.
Table of contents
Popular Switch manuals by other brands

Brocade Communications Systems
Brocade Communications Systems A7533A - Brocade 4Gb SAN Switch Base Administrator's guide

Cisco
Cisco MDS 9124e specification

Johnson Controls
Johnson Controls F61 series installation instructions

SMC Networks
SMC Networks ZK2-ZSV-A Series Operation manual

netvox
netvox RB02B user manual

Morrell
Morrell SW-UNM-5FE user manual

North American Cable Equipment
North American Cable Equipment IP-POE24M Hardware installation manual

IOGear
IOGear GCS1212TAA4 manual

Conrad
Conrad 97 51 23 operating instructions

Enable-IT
Enable-IT 8808F Installation Manual Guide

Tranberg
Tranberg TEF 1107 user manual

Lenovo
Lenovo ThinkSystem NE0152T installation guide