Elster PFA Manual

6.2.1.6 Edition 03.11
Technical Information · GB
www.kromschroeder.com
• 19" module for easy transmission of activation signals and feedbacks from
burner control units via fieldbus cable
• Remote maintenance and diagnostics facilities
• Saves installation and wiring costs
• Units can be exchanged during bus mode operation thanks to industrial plug
connector system
• Bus interface remains in operation when PFA is switched off (standby mode)
• Certification for PROFIBUS DP
Field bus interface PFA
Module subrack BGT

PFA, BGT · Edition 03.11
2
t = To be continued
Contents
Field bus interface PFA
Module subrack BGT.............................. 1
Contents........................................2
1 Application.....................................3
1.1 Examples of application. . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 PFA 700 with PFU 760, staged On/Off burner control . . . . . .5
1.1.2 PFA 700 with PFU 760L, staged High/Low burner control . .5
1.1.3 PFA 710 with PFU 780, stage-controlled main burner with
alternating pilot burner..................................6
1.1.4 PFA 710 with PFU 780, stage-controlled main burner with
permanent pilot burner .................................6
2 Certification....................................7
2.1 EC type-tested and certified . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Approval for Russia.............................7
3 Function.......................................8
3.1 Safety-related control signals . . . . . . . . . . . . . . . . . . . . . 8
3.2 Air valve......................................8
3.3 BCSoft........................................9
3.4 Configuration, Master-Slave procedure . . . . . . . . . . . . 9
3.5 Addressing ...................................9
3.6 Network technology . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7 Configuration.................................10
3.7.1 Bus communication ...............................10
3.8 Program status ...............................12
3.9 Fault signalling ............................... 12
3.10 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.10.1 PFA 700 and BGT SA-9U/1DP700. . . . . . . . . . . . . . . . . . . . 13
3.10.2 PFA 710 and BGT SA-8U/1DP . . . . . . . . . . . . . . . . . . . . . . . 14
3.10.3 Flame control using an electrode . . . . . . . . . . . . . . . . . . . 15
3.10.4 Flame control with UV sensor UVS . . . . . . . . . . . . . . . . . . 15
3.10.5 Flame control with UV sensor for continuous operation
UVD 1 ...............................................15
4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Scanning the parameters . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Manual operation............................. 17
4.3.1 PFA 700 .........................................18
4.3.2 PFA 710 .........................................19
5 Selection .....................................20
5.1 PFA .........................................20
5.1.1 Selection table................................... 20
5.1.2 Type code ...................................... 20
5.2 BGT.........................................20
5.2.1 Selection table .................................. 20
5.2.2 Type code...................................... 20
6 Project planning information . . . . . . . . . . . . . . . . . . . . . 21
6.1 Installation ...................................21
6.2 Old-new PFA exchange . . . . . . . . . . . . . . . . . . . . . . . . 21
6.3 Wiring.......................................22
6.3.1 Safety-related control signals . . . . . . . . . . . . . . . . . . . . . . 22
6.3.2 EMC........................................... 22
6.3.3 PROFIBUS plug connector . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.4 Manual operation.............................22
7 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.1 PROFIBUS plug connector . . . . . . . . . . . . . . . . . . . . . . . 23
7.2 Opto-adapter and BCSoft . . . . . . . . . . . . . . . . . . . . . . . 23
7.3 “Changed parameters” stickers . . . . . . . . . . . . . . . . . . 23
8 Technical data.................................24
8.1 PFA 700, PFA 710 ..............................24
8.1.1 Operating controls ............................... 24
8.2 BGT.........................................25
8.2.1 Dimensions..................................... 25
9 Legend ......................................26
Feedback ......................................27
Contact........................................27

PFA, BGT · Edition 03.11
3
Application
1 Application
In module subrack BGT, up to nine burner control units can be
inserted together with the PFA700, while with the PFA710, the
maximum is eight burner control units.
The BGT is provided with a backplane with screw terminals for
simple, reliable wiring.
The conventional wide-spread systems used in industrial fur-
nace and kiln construction require bridging of large distances
for signal processing.
The field bus interface PFA is used in conjunction with the
pre-wired module subrack BGT for interworking of burner
control units PFU to industrial communication networks us-
ing PROFIBUS DP to control and monitor burners in industrial
furnaces and firing systems, e.g. in the iron and steel, glass
and ceramics, or plastics and chemical industries.
As a standardized fieldbus system, the PROFIBUS DP consider-
ably reduces development, installation and commissioning
costs compared to conventional wiring.
The use of a standard bus system offers massive benefits com-
pared to manufacturer-specific bespoke solutions. Time-tested
hardware components, standardized connection methods
and a series of tools of bus diagnostics and optimization are
available on the market from a whole range of manufacturers.
The widespread use of the system ensures that the planning
and service personnel are very familiar with how the system
operates and how to handle it and can therefore operate the
system efficiently.
PFA 700 with BGT SA-9U/1DP700
For interworking of up to nine burner control units PFU 760
for directly ignited burners to communication networks using
PROFIBUS DP. The PFA700 is plugged into the module subrack
with printed-circuit board and rear terminal strip, together with
the burner control units.
PFA 710 with BGT SA-8U/1DP710
For interworking of up to eight burner control units PFU780
for pilot and main burners to communication networks using
PROFIBUS DP. The PFA710 is plugged into the module subrack
with printed-circuit board and rear terminal strip, together with
the burner control units.

PFA, BGT · Edition 03.11
4
Application
Bogie hearth forging furnace in the metallurgical industry
Walking beam furnace with overhead firing
Intermittent shuttle kiln in the ceramics industry

PFA, BGT · Edition 03.11
5
Application
1.1 Examples of application
1.1.1 PFA 700 with PFU 760, staged On/Off burner control
DI
L1, N, PE
P
BUS
PFU 760
PFU 760
PFU 760
PFU 760
PFU 760
PFU 760
PFU 760
PFU 760
PFU 760
PFA 700
BUS
VR..R
VAG
TZI
UV
PLC
The burner can be started with reduced capacity.
A UV sensor monitors the flame signal from the burner. UV
sensor UVD 1 is used for continuous operation, UV sensor UVS
for intermittent operation.
1.1.2 PFA 700 with PFU 760L, staged High/Low burner
control
VR..R
TZI
GIK..B
VAS..N
DI
L1, N, PE
P
BUS
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFU 760L
PFA 700
BUS
PLC
The burner starts at low-fire rate. When the operating state is
reached, the PFU 760L advises the control unit. The PLC can
now pulse the air valve in order to control the burner capacity.

PFA, BGT · Edition 03.11
6
Application
1.1.3 PFA 710 with PFU 780, stage-controlled main burner
with alternating pilot burner
VR..L
VAG
t
1
2
ϑ1
ϑ2
UV
02–0402–04 06–08 06–08
VBY
TZI
2
1
DI
L1, N, PE
P
BUS
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFA 710
BUS
PLC
Control: main burner ON/OFF
The main burner can be started with reduced capacity after
the operating signal from the pilot burner has been detected.
The pilot burner is switched off automatically after the main
burner has started up. When the main burner is switched off,
the pilot burner automatically switches on again.
A UV sensor monitors the flame signal from pilot and main
burners. UV sensor UVD 1 is used for continuous operation,
UV sensor UVS for intermittent operation.
1.1.4 PFA 710 with PFU 780, stage-controlled main burner
with permanent pilot burner
VR..R
VAG
VBY
TZI
t
1
2
0402–04 06–08 06–08 04
2
1
ϑ1
ϑ2
DI
L1, N, PE
P
BUS
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFU 780
PFA 710
BUS
PLC
Control: main burner ON/OFF
The main burner can be started with reduced capacity after
the operating signal from the pilot burner has been detected.
Pilot and main burners can be operated simultaneously. Both
are ionization-controlled independently.
Control: main burner High/Low
The main burner starts at low-fire rate. When the operating
state is reached, the PFU780L advises the control unit. The
PLC can now pulse the air valve in order to control the capacity
of the main burner.

PFA, BGT · Edition 03.11
7
2 Certification
2.1 EC type-tested and certified
– Low Voltage Directive (2006/95/EC) in conjunction with EN
60730,
– Electromagnetic Compatibility Directive (2004/108/EC) in
conjunction with the relevant standards relating to radia-
tion.
2.2 Approval for Russia
Certified by Gosstandart pursuant to GOST-R.

PFA, BGT · Edition 03.11
8
3 Function
DI
L1, N, PE
P
BUS
…
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFA
BUS
…
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFU
PFA
BUS
PROFIBUS-DP
PLC
The field bus interface PFA 700 integrates up to nine burner
control units PFU 760 into industrial communication networks
using PROFIBUS DP. The PFA 700 is plugged into the pre-wired
module subrack BGT SA-9U/1DP700, together with the burner
control units.
The field bus interface PFA 710 integrates up to eight burner
control units PFU 780 into industrial communication networks
using PROFIBUS DP. The PFA710 is plugged into the pre-wired
module subrack BGTSA-8U/1DP710, together with the burner
control units.
To the rear of the module subrack, there is a D-Sub socket for
connection to PROFIBUS DP and connection terminals in order
to send input and output signals to ignition transformers, gas
and air valves or UV sensors, for example, via the individual
burner control units PFU.
PROFIBUS DP
PROFIBUS is a manufacturer-independent, open fieldbus stand-
ard for diverse applications.
PROFIBUS DP is a bus variant for communication between
automation systems and distributed peripherals at the field
level, optimized for speed and low connection costs.
On PROFIBUS DP, the individual bus stations are connected
via a 2-core shielded cable as standard.
The bus system transfers the control signals for starting, re-
setting and for controlling the air valve to purge the furnace
or kiln or for cooling in start-up position and heating during
operation from the control system (PLC) to the PFA. In the op-
posite direction it sends information on the operating status.
3.1 Safety-related control signals
Control signals for the safety interlocks and digital input are
transferred independently of the bus communication by sepa-
rate cables.
3.2 Air valve
The air valves used to purge the furnace or kiln can either be
activated via the PROFIBUS or via a separate cable (to terminal
strip X10 of the BGT – at 24 V DC to terminal 12 or 13, or at
mains voltage to terminal 18).
It is possible to use the PROFIBUS to communicate that purging
is being carried out (by connecting mains voltage to terminal
17 of terminal strip X10 of the BGT).

PFA, BGT · Edition 03.11
9
3.3 BCSoft
The Windows software BCSoft allows extended access to
individual statistics, visualization of the process values and
the parameterization of the field bus interface via an optical
interface. Unit parameters can be adjusted to the specific
application.
3.4 Configuration, Master-Slave procedure
PROFIBUS DP is structured as a Master-Slave system. This al-
lows mono-master or multi-master systems to be implemented.
A distinction is made between three device types:
– DP Masters Class 1 (DPM1)
DPM1 devices are central controllers which exchange
data with the distributed stations (slaves) on the basis of a
defined cycle. This includes, for instance, the PLC, PC, CNC
or VME systems with which the PROFIBUS DP is operated.
– DP Masters Class 2 (DPM2)
DPM2 devices are programming, project planning or
operator-control devices. They are used for configuration
and commissioning of the system or for system operation
and visualization in ongoing operation.
– DP slaves
The devices which transmit input information from the
periphery to the master and which issue output informa-
tion from the master to the periphery are referred to as
“slaves”.
This also includes the PFA.
3.5 Addressing
A maximum of 126 units (masters and slaves) can be con-
nected to a PROFIBUS DP system. Each station is assigned an
individual PROFIBUS address which can be set between 0 and
126 using two code switches on the PFA board.
0
8
7
6
5
4
3
2
1
0
E
D
C
B
A
9
8
7
6
5
4
3
2
1
F
9
114 dec
Function

PFA, BGT · Edition 03.11
10
3.6 Network technology
All devices are connected in a bus structure (line). Up to 32
stations (masters or slaves) can be connected in a single seg-
ment. The beginning and end of each segment is fitted with
an active bus terminator. Both bus terminators must have a
permanent power supply to ensure error-free operation. The
power supply for the bus terminator is provided by the PFA. The
bus terminator can be connected in the bus connection plug.
If more than 32 stations are implemented or if there is a need
to expand the network area, repeaters (amplifiers) must be
used to link the individual bus segments.
3.7 Configuration
When planning a PROFIBUS DP system, unit-specific param-
eters of each station are to be taken into account.
To allow for simple and standardized planning, the parameters
of the PFA have been summarized in a so-called device master
data file (GSD). The file structure is standardized so that it can
be read by the planning devices of different manufacturers.
The GSD file is supplied on a CD with the PFA. The GSD file can
also be ordered at www.docuthek.com. The steps required to
copy the file are described in the instructions for the automa-
tion system.
3.7.1 Bus communication
Input/output bytes: The programmer can choose the data to
be transferred.
Input bytes
(PFA ▶ master)
Output bytes
(master ▶ PFA)
PFA 700 5 bytes 3 bytes
PFA 710 5 bytes 5 bytes
Baud rate: up to 1500 kbit/s.
The max. range per segment depends on the baud rate:
Baud rate [kbit/s] Range
[m] [ft]
93.75 1200 3937
187.5 1000 3280
500 400 1312
1500 200 656
The specified ranges may be increased by using repeaters.
No more than three repeaters should be connected in series.
The specified ranges relate to bus cable type A (two-core,
shielded and twisted), e.g.:
Siemens, Order No.: 6XV1830-0EH10, or
Lapp cable unitronic, Order No.: 2170-220T.
t

PFA, BGT · Edition 03.11
11
PFA 700
Input bytes (PFA ▶ master)
Bit Byte 0 Byte 1 Byte 2 Byte 3 Byte 4
0
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 9
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 9
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 9
3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2 1
4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3 2
5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4 3
6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5 4
7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA PFA
Output bytes (master ▶ PFA)
Bit Byte 0 Byte 1 Byte 2
0
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 9
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 9
2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4 1
5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5 2
6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6 3
7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7 4
PFA 710
Input bytes (PFA ▶ master)
Bit Byte 0 Byte 1 Byte 2 Byte 3 Byte 4
0
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
1
1
2
PFU 1
1
2
PFU 3
1
2
PFU 5
1
2
PFU 7 1
2
1
2PFU 1
1
2PFU 3
1
2PFU 5
1
2PFU 7 2
3PFU 1 PFU 3 PFU 5 PFU 7 3
4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8 4
5
1
2
PFU 2
1
2
PFU 4
1
2
PFU 6
1
2
PFU 8
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
6
1
2
PFU 2
1
2
PFU 4
1
2
PFU 6
1
2
PFU 8
7PFU 2 PFU 4 PFU 6 PFU 8 PFA
Output bytes (master ▶ PFA)
Bit Byte 0 Byte 1 Byte 2 Byte 3 Byte 4
01
2
PFU 1 1
2
PFU 3 1
2
PFU 5 1
2
PFU 7
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
1
1
2PFU 1
1
2PFU 3
1
2PFU 5
1
2PFU 7 1
2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 1
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 3
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 5
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 7 2
3 3
41
2
PFU 2 1
2
PFU 4 1
2
PFU 6 1
2
PFU 8 4
5
1
2PFU 2
1
2PFU 4
1
2PFU 6
1
2PFU 8
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFA
6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 2
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 4
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 6
1, 2
ϑ
A
P
A
P
DI
on
on
on
PFU 8
7

PFA, BGT · Edition 03.11
12
3.8 Program status
DISPLAY Program status
-
-PFA switched off
Programming mode
0.0. (blinking dots) Manual mode
OP Normal operation
PB Profibus fault
3.9 Fault signalling
Fault message (blinking) DISPLAY
Bus fault P
Undervoltage in power pack 32
Bus module fault E
In manual mode, two dots blink on the display.
Function

PFA, BGT · Edition 03.11
13
3.10 Connection diagrams
3.10.1 PFA 700 and BGT SA-9U/1DP700
For the explanation of symbols, see page 26 (Legend).
15b
30a
32b
N
L1
8b
11b
12b
PFA 700
C
16b
1c
9c
VP
1. PFU
9. PFU
RxD/TxD-P
RxD/TxD-N
DGND
0 V
+24 V
…
10c
1. PFU
9. PFU
…
2
1a
9a
1. PFU
9. PFU
…
10a
18a
1. PFU
9. PFU
…
19a
23a
1. PFU
5. PFU
…
20c
23c
6. PFU
9. PFU
…
0 Vex
+24 Vex
1
2
3
4
1
2
3
4
14b
18b
21b
22b
23b
24b
I/O
18c
BGT SA-9U/1DP700 (8 440 229 1)
N
PE
+24 Vex
0 Vex
19b
20b
1
2
3
4
5
6
7
8
9
10
X10
11
12
13
30e
14
17
18
19
20
21
22
X10
N
X9.6
X9.3
X9.5
K2
K1
COM
k2
k3
k5
k4
E1 E2 E3 E4
1
30c
PFU 19c
17b
24 V
L1
PROFIBUS DP
25b
26b
K4
K5
K3
V1
V2
N
X1.6
V1
V2
+24 Vex
+24 Vex
+24 Vex
..8, ..7,
..6, ..5,
..4, ..3,
..2
max. 1 A, 24 V
PROFIBUS DP
PFU 7xx
1…9
UVS 1
2
3
9
22e
16c
26e
30a
32c
230 V
F1
18e
2a
4a
2e
4e
2c
4c
sk1
PFU 760
v2
v1
6a
6e
c1
c2
10c
12c
10a
12a
30e
22a
2
1
1
2
28c
26a
14a
14e
10e
12e
24c
20c
18a
l
Z I
1
1
22e
16c
26e
30a
32c
230 V
F1
18e
2a
4a
2e
4e
2c
4c
sk1
PFU 760
v2
v1
6a
6e
c1
c2
10c
12c
10a
12a
30e
22a
2
1
1
2
28c
26a
14a
14e
10e
12e
24c
20c
18a
l
DI
2
Z I
1
11
15
16
1
2
3
4
5
6
X1
7
8
1
2
3
4
5
6
X9
7
8
DI
2
k1
X10.21 X1.3
X1.5
UVS 1
2
3X10.21
Function

PFA, BGT · Edition 03.11
14
3.10.2 PFA 710 and BGT SA-8U/1DP
For the explanation of symbols, see page 26 (Legend).
15b
30a
32b
N
L1
8b
11b
12b
PFA 710
C
16b
1c
8c
VP
1. PFU
8. PFU
RxD/TxD-P
RxD/TxD-N
DGND
0 V
+24 V
...
10c
1. PFU
8. PFU 2
1a
8a
1. PFU
8. PFU
...
10a
17a
1. PFU
8. PFU
...
19a
23a
1. PFU
5. PFU
...
20c
22c
6. PFU
8. PFU
...
0 Vex
+24 Vex
1
2
3
4
1
2
3
4
14b
18b
21b
22b
23b
24b
I/O
17c
BGT SA-8U/1DP710 (8 440 229 2)
N
PE
+24 Vex
0 Vex
19b
20b
1
2
3
4
5
6
7
8
9
10
X10
11
12
13
30e
14
17
18
19
20
21
22
X10
N
X8.6
K2
K1
COM
k2
k3
k5
k4
E1 E2 E3 E4
1
30c
PFU 19c
17b
24 V
L1
PROFIBUS DP
25b
26b
K4
K5
K3
V1
V2
N
X1.6
V1
V2
+24 Vex
+24 Vex
+24 Vex
..7, ..6,
..5, ..4,
..3, ..2,
max. 1 A, 24 V
PROFIBUS DP
PFU 7xx
1…8
8
22e
16c
26e
30a
32c
230 V
F1
18e
2a
4a
2e
4e
2c
4c
sk1
PFU 780
v2
v1
6a
6e
c1
c2
10c
12c
10a
12a
30e
22a
2
1
1
2
28c
26a
14a
14e
10e
12e
24c
20c
18a
l
Z I
1
1
22e
16c
26e
30a
32c
230 V
F1
18e
2a
4a
2e
4e
2c
4c
sk1
PFU 780
v2
v1
6a
6e
c1
c2
10c
12c
10a
12a
30e
22a
2
1
1
2
28c
26a
14a
14e
10e
12e
24c
20c
18a
l
DI
2
Z I
1
11
15
16
1
2
3
4
5
6
X1
7
8
1
2
3
4
5
6
X8
7
8
DI
2
...
2
1
1
2
1b
1. PFU
7. PFU 7b
...
27a
8. PFU
27c
27b
24a
26a
1. PFU
2. PFU
3. PFU
...
5. PFU 24c
26c
6. PFU
...
8. PFU
k1
X8.3
X8.5
UVS 1
2
3X10.21
X1.3
X1.5
UVS 1
2
3X10.21
Function > Connection diagrams

PFA, BGT · Edition 03.11
15
Function
3.10.3 Flame control using an electrode
V1
V2
1
2
3
4
5
6
X1…9 (BGT SA-9U)
X1…8 (BGT SA-8U)
7
8
DI
2
1
N
PE
L1
16c
18e
20c
22e
26a
28c
22a
28a
3.10.4 Flame control with UV sensor UVS
V1
V2
1
2
3
4
5
6
X1…9 (BGT SA-9U)
X1…8 (BGT SA-8U)
7
8
DI
2
1
N
PE
L1
16c
18e
20c
22e
26a
28c
22a
28a
UVS 1
2
3
11
12
13
14
17
18
19
20
21
22
X10
15
16
3.10.5 Flame control with UV sensor for continuous
operation UVD 1
V1
V2
1
2
3
4
5
6
X1…9 (BGT SA-9U)
X1…8 (BGT SA-8U)
7
8
DI
2
1
N
PE
L1
16c
18e
20c
22e
26a
28c
22a
28a
UVD 1 1
2
3
4
5
6
0 V
24 V DC, 200 mA

PFA, BGT · Edition 03.11
16
4 Parameters
Description Parameter Value range Factory default
setting Adjustable*
Manual mode limited to 5 minutes 34 0; 1 1
Manual operating mode 43 1; 2; 3; 4 1
Last fault 81 Pb; 32; bE* – –
Second to last occurring fault 82 Pb; 32; bE* – –
Third to last occurring fault 83 Pb; 32; bE* – –
Fourth to last occurring fault 84 Pb; 32; bE* – –
Fifth to last occurring fault 85 Pb; 32; bE* – –
Sixth to last occurring fault 86 Pb; 32; bE* – –
Seventh to last occurring fault 87 Pb; 32; bE* – –
Eighth to last occurring fault 88 Pb; 32; bE* – –
Ninth to last occurring fault 89 Pb; 32; bE* – –
Tenth to last occurring fault 90 Pb; 32; bE* – –
* Fault messages appear in the display,
see page 12 (Fault signalling).

PFA, BGT · Edition 03.11
17
4.1 Scanning the parameters
During operation, the 7-segment display shows the program
status.
The individual parameters of the PFA can be called up on the
display by repeatedly pressing the Reset/Information button
(for 2seconds).
In the event of a fault, the PFA halts the program run, the display
blinks and it then displays the cause of the fault in coded form.
The PFA indicates “––” when the mains switch has been
switched off. This signals standby mode. The bus interface is
still operational to maintain the function of the communica-
tion system.
4.2 Changing parameters
The PFA is protected by a password to prevent unauthorized
changes to the parameter settings. After entering the pass-
word, the parameter settings can be modified. Be aware of
possible effects on the safe functioning of the system. The
factory default password is 1234.
4.3 Manual operation
The PFA can be started in manual mode for burner adjustment
or for fault-finding.
When switching on, press the Reset/Information button until
the unit reverts to manual mode. Two dots blink on the dis-
play. In this operating mode, the burner control unit operates
independently of the status of the bus and the inputs (apart
from the pre-purge input and the safety interlocks).
In the factory default setting, manual mode is limited to 5
minutes (parameter 34 = 1). During this time, the burner can
be adjusted, for example. If parameter 34 is set to 0, the time
limitation will be removed. Emergency operation is now pos-
sible, for example in the event of a lengthy bus fault. (In the
event of a bus fault, P will blink on the display).
Using the opto-adapter and the BCSoft software (see page 23
(Opto-adapter and BCSoft)), the operating mode parameters for
manual mode can be changed. On parameterization, ensure
that the program sequence matches the application. Select the
parameters so that the burner can be operated as intended
in all operating phases.
t

PFA, BGT · Edition 03.11
18
4.3.1 PFA 700
Default operating mode parameters
Parameter 43 = 1
0.0. 0.3.
00 4
PFA
0× 1×
PFU 760
PFA 700
10e
10a A
The PFA 700 is programmed at the factory so that voltage is
applied to all burner control units PFU for the start-up signal
of all burners and the external air valve control.
Adjusted operating mode parameters
Parameter 43 = 2
PFA 700 with PFU 760, ON/OFF operating mode – example
of application, see page 5 (PFA 700 with PFU 760, staged On/
Off burner control).5 (PFA 700 with PFU 760, staged On/Off
burner control)
0.0. 0.3. 0.0. 0.3.
00 04 00 04
PFA
0× 1× 2× 3×
PFU
PFA
10e
30e
10a A
P
Parameter 43 = 3
PFA 700 with PFU 760L, ON/OFF operating mode – example
of application, see page 5 (PFA 700 with PFU 760, staged On/
Off burner control).
0.0. 0.1. 0.3. 0.0. 0.1. 0.3.
00 P0 4 00 P0 4
PFA
0× 1× 2× 3× 4× 5×
PFU
PFA
10e
30e P
10a A
Parameter 43 = 4
PFA 700 with PFU 760L, High/Low operating mode – example of
application, see page 6 (PFA 710 with PFU 780, stage-controlled
main burner with alternating pilot burner).
0.0. 0.1. 0.3. 0.4. 0.3. 0.4.
00 P0 04 A4 04 A4
PFA
0× 1× 2× 3× 4× 5×
PFU
PFA
10e
30e P
10a A
Parameters > Manual operation

PFA, BGT · Edition 03.11
19
4.3.2 PFA 710
Default operating mode parameters
Parameter 43 = 1
0.0. 0.1. 0.2. 0.3.
00 P0 04
PFA
0× 1× 2× 3×
14a
PFU 780
PFA 710
10e
1
2
10a A
The PFA 710 is programmed at the factory so that voltage is
applied to all burner control units PFU for the start-up signal
of all burners and the external air valve control.
Adjusted operating parameters
Parameter 43 = 3
PFA 710 with PFU 780L, ON/OFF operating mode – example of
application, see page 6 (PFA 710 with PFU 780, stage-controlled
main burner with permanent pilot burner).
0.0. 0.1. 0.0. 0.1.0.2. 0.3.
00 P0 04 8 00 P0
PFA
0× 1× 2× 3× 4× 5×
14a
PFU
PFA
10e
30e
1
2
10a A
P
Parameter 43 = 4
PFA 710 with PFU 780L, High/Low operating mode – example of
application, see page 6 (PFA 710 with PFU 780, stage-controlled
main burner with permanent pilot burner).
0.0. 0.1. 0.2. 0.3. 0.4. 0.3. 0.4.
00 P0 04 08 A8 08 A8
0× 1× 2× 3× 4× 5× 6×
14a
PFU
PFA
10e
30e
1
2
10a A
P
PFA
Parameters > Manual operation

PFA, BGT · Edition 03.11
20
5 Selection
5.1 PFA
5.1.1 Selection table
Type 700 710 T N Z*
PFA
* If “none”, this specifi cation is omitted.
= standard,
= available
Order example
PFA 700T
5.1.2 Type code
Code Description
PFA Field bus interface
700
710
For connecting:
PFU 760
PFU 780
T
N
Mains voltage: 220/240 V AC
110/120 V AC
Z* Special version
* If “none”, this specifi cation is omitted.
5.2 BGT
5.2.1 Selection table
Type SA -8U -9U /1DP700 /1DP710
BGT 1) 2)
1)
Only in conjunction with -9U.
2)
Only in conjunction with -8U.
Order example
BGT SA-8U/1DP710
5.2.2 Type code
Code Description
BGT 19" module subrack
SA Standard and PFA 700/PFA 710
-8U
-9U
Slots for: 8 PFU
9 PFU
/1DP700
/1DP710
1 PFA 700, PROFIBUS DP bus interface
1 PFA 710, PROFIBUS DP bus interface
This manual suits for next models
1
Table of contents
Other Elster Recording Equipment manuals