emaux IHP13 User manual

EMAUX WATER TECHNOLOGY CO., LTD
STRIVE FOR CLEAR WATER
www.emauxgroup.com
USER MANUAL
Invertor Heat Pump
Operations manual
EMHE22022507
Model: IHP13/IHP18/IHP21/IHP26/IHP36/IHP36S

If the electric cable appears deteriorated or damaged, it must
be replaced by a qualified technician.
SILENCE TO RELAX YOUR MIND
TABLE OF
CONTENT
PAGE
2
.... PRODUCT OVERVIEW
INVERTOR HEAT PUMP
P1 CONTENT WARNINGS P2
9
1.1 Specifications
1.2 Dimension
2. LOCATION
2.2 How to remove the front cover
2.3 Condensation Draining Hose Installation
2.6 Typical in-ground pool arrangement
10
....
2.4 Water Connection
2.7 Electrical Connection
2.8 Before Starting
2.1 Location and Space Requirement
2.5 Connecting the By-pass Kit
3. DISPLAY AND OPERATION
3.1 Keyboard (it might have different kind of control
panel with the same keyboard functions)
17
....
3.2 Display of Controller
3.3 Structure of Interface Display
3.4 The Main Masks of Controller
3.5 Unit On/Off
3.6 Temperature Setting
3.7 Work Mode Changing (Heating/Cooling)
3.8 Turbo Mode Changing
3.9 Language setting
3.10 I/O Mask (figures & status checking)
3.11 Timezone /Clock setting
3.12 User Figures Setting
3.14 Alarm Checking
3.13 Professional Program Setting
(for professional technician only)
4. MAINTENANCE
5. Troubleshooting
6. ALARM CODE LIST
7. DIAGRAMS
8. TERMS OF THE WARRANTY
28
....
31
....
33
....
36
....
40
....
WARNINGS:
The installation, disassembly and maintenance of this appliance
must be done by a qualified installer. It is forbidden to make any
changes to the structure of the appliance. Failure to comply
with these provisions can cause damage to people, animals or things.
Disconnect the appliance from the power supply at least one
minute before accessing the electrical components. Before
t o u c h i n g t h e e l e c t r i c a l c o m p o n e n t s , i t i s h o w e v e r
recommended to measure the voltage across the terminals to
make sure it is lower than the safety voltage.
Read this manual carefully before using the appliance.
Provide a bipolar switch with a contact opening distance of at
least 3 mm in the vicinity of the appliance, as required by
current regulations.
Use a dedicated electric socket for this appliance. Failure to do
so could cause malfunctions.
The power supply of this appliance must be grounded.

This ap pli ance contains fluorina ted gree nhouse gases:
installation must be carried out by an installer | company
authorized in accordance with the European regulation EU
517|2014.
All the drawings shown in this manual relating to electrical,
hydraulic or gas installation systems must be understood to be
purely illustrative. All the safety devices, auxiliary devices and
the diameters of the electrical, hydraulic and gas pipes must always be
checked by a professionally qualified technician, to make sure they satisfy the
applicable laws and regulations.
P3 PROHIBITION
PROHIBITION:
Water or any kind of liquid is strictly forbidden to be poured into the
product, or may cause electric creepage or breakdown of the product.
Use the proper fuse and breaker. It is forbidden to use copper or steel
wires to replace the fuse or switch.
Do not touch the fins of the evaporative condensing battery, they can
hurt your fingers.
FAILURE TO FOLLOW THESE WARNINGS MAY RESULT IN PROPERTY DAMAGE,
ELECTRIC SHOCK, ENTANGLEMENT OR OTHER SERIOUS INJURY OR DEATH.
Safety Precautions(R32)
Meanings of symbols displayed on heat pump unit
1.Since rotating parts and parts which could cause an electric shock are used in this
product, be sure to read these "Safety Precautions" before use.
WARNING
This unit uses a flammable refrigerant (1132).
If refrigerant leaks and comes in contact with fire or heating part, it
will create harmful gas and
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS
and INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION
MANUAL, and the like.
2.Since the cautionary items shown here are important for safety, be sure to observe
them.
3.After reading this manual, keep it together with the installation manual in a handy
place for easy reference.
4.Be sure to receive a guarantee card from your dealer and check that the purchased data
and shop name, etc. are entered correctly.
WARNING
Incorrect handling could cause serious hazard, such as
death, serious injury, etc. with a high probability.
Incorrect handling could cause serious hazard depending
on the conditions.
CAUTION
Meanings of symbols used in this manual
Meanings of symbols used in this manual
Be sure not to do.
Be sure to follow the instruction.
Never insert your finger or stick, etc.
Never step into the indoor/outdoor unit and do not put anything on them.
Damager of electric shock. Be careful.
Be sure to disconnect the power supply plug from the power outlet.
Be sure to shut off the power.
Risk of fire.
PROHIBITION P4

P5 PROHIBITION PROHIBITION P6
Do not connect the power cord to an intermediate point, use an extension
cord, or connect multiple devices to heat pump.
- This may cause overheating, fire or electric shock.
Make sure the power plug is free of dirt and insert it securely into the outlet.
- A dirty plug may cause fire or electric shock.
Do not bundle, pull, damage, or modify the power cord, and do not apply
heat or place heavy objects on it.
- This may cause fire or electric shock.
Do not turn the breaker OFF/ON or disconnect/connect the power plug
during operation.
- This may create sparks, which can cause fire.
Do not expose your body directly to cool air for a prolonged length of time.
- This could be detrimental to your health.
The unit should not be installed, relocated, disassembled, altered,
or repaired by the user.
- An improperly handled heat pump may cause fire, electric shock,
injury, or water
leakage, etc. Consult your dealer.
- If the power supply cord is damaged, it must be replaced by the
manufacturer or its service agent in order to avoid a hazard.
When installing, relocating, or servicing the unit, make sure that no substance other
than the specified refrigerant (R32) enters the refrigerant circuit.
- Any presence of foreign substance such as air can cause abnormal
pressure rise and may result in explosion or injur y.
- The use of any refrigerant other than that specified for the system will cause
mechanical failure, system malfunction, or unit breakdown.
In the worst case, this could lead to a serious impediment to securing product safety.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance
by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
The appliance shall be stored in a room without continuously operating ignition
sources (for example: open flames, an operating gas appliance or an operating
electric heater).
Do not insert your finger, a stick, or other objects into the air inlet or outlet.
- This may cause injury, since the fan inside rotates at high speeds during
operation.
In case of an abnormal condition (such as a burning smell),
stop the heat pump and disconnect the power plug or turn the breaker OFF.
- A continued operation in the abnormal state may cause a malfunction, f
ire, or electric shock. In this case, consult your dealer.
When the heat pump does not cool or heat, there is a possibility of refrigerant
leakage. If any refrigerant leakage is found,
stop operations and ventilate the room well and consult your dealer
immediately. If a repair involves recharging the unit with refrigerant, ask the
service technician for details.
- The refrigerant used in the heat pump is not harmful. Normally,
it does not leak. However, if refrigerant leaks and comes in contact with fire or
heating part of such a fan heater, kerosene heater, or cooking stove, it will create
harmful gas and there is risk of fire.
The user should never attempt to wash the inside of the indoor
unit. Should the inside of the unit require cleaning, contact your dealer.
- Unsuitable detergent may cause damage to plastic material inside the unit,
which may result in water leakage. Should detergent come in contact with
electrical parts or the motor, it will result in a malfunction, smoke, or fire.
- The appliance shall be stored in a room without continuously operating
ignition sources (for example: open flames, an operating gas appliance or an
operating electric heater).
- Be aware that refrigerants may not contain an odor.
- Do not use means to accelerate the defrosting process or to clean the
appliance, other than those recommended by the manufacturer.
- Do not pierce or burn.
This unit should be installed outdoor or in rooms which exceed the
floor space specified below. GL50: 2.2 m2 or larger
GL60: 2.3 m2 or larger
GL71180: 3.1 m2 or larger

PROHIBITION P8
P7 PROHIBITION
Caution
Do not touch the air inlet or the aluminium fins of the heat pump unit.
- This may cause injury.
Do not use insecticides or flammable sprays on the unit.
- This may cause a fire or deformation of the unit.
Do not expose pets or houseplants to direct airflow.
- This may cause injury to the pets or plants.
Do not expose pets or houseplants to direct airflow.
- This may cause injury to the pets or plants.
Do not place other electric appliances or furniture under the heat pump unit.
- Water may drip down from the unit, which may cause damage or malfunction.
Do not leave the unit on a damaged installation stand.
- The unit may fall and cause injury.
Do not step on an unstable bench to operate or clean the unit.
- This is may cause injury if you fall down.
Do not charge or disassemble the batteries, and do not throw them into a fire.
- This may cause the batteries to leak, or cause a fire or explosion.
Do not use the unit for special purposes, such as storing food, raising animals,
growing plants, or preserving precision devices or art objects.
- This may cause deterioration of quality, or harm to animals and plants.
Do not expose combustion appliances to direct airflow.
- This may cause incomplete combustion.
Before cleaning the unit, switch it OFF and disconnect the power plug or turn
the breaker OFF.
- This may cause injury, since the fan inside rotates at high speeds during
operation.
When the unit will be unused for a long time, disconnect the power plug or turn
the breaker OFF.
- The unit may accumulate dirt, which may cause overheating or fire.
Ensure that the area is well-ventilated when the unit is operated together with
a combustion appliance.
- Inadequate ventilation may cause oxygen starvation.
After the heat pump is used for several seasons, perform inspection and
maintenance in addition to normal cleaning.
Dirt or dust in the unit may create an unpleasant odor, contribute to growth
of fungi, such as mold, or clog the drain passage, and cause water to leak from
the indoor unit. Consult your dealer for inspection and maintenance, which
require specialized knowledge and skills.
Do not operate switches with wet hands.
- This may cause electric shock.
Do not clean the heat pump with water or place an object that contains water,
such as a flower vase, on it.
- This may cause fire or electric shock.
Do not step on or place any object on the unit.
- This may cause injury if you or the object falls down.
Important
Dirty filters cause condensation in the heat pump which will contribute to the growth of
fungi such as mold. It is therefore recommended to filters every 2 weeks.
For Installation
Warning
Consult your dealer for installing the heat pump.
- It should not be installed by the user since installation requires specialized
knowledge and skills. An improperly installed heat pump may cause water
leakage, fire, or electric shock.
Provide a dedicated power supply for the heat pump.
- A non-dedicated power supply may cause overheating or fire.
Do not install the unit where flammable gas could leak.
- If gas leaks and accumulates around the unit, it may cause an explosion.
Earth the unit correctly.
- Do not connect the earth wire to a gas pipe, water pipe, lightning rod, or
a telephone ground wire. Improper earthing may cause electric shock.

477
527
527
P9 PRODUCT OVERVIEW LOCATION P10
Install an earth leakage breaker depending on the installation location of the heat pump
(such as highly humid areas).
- If an earth leakage breaker is not installed, it may cause electric shock
Ensure that the drain water is properly drained.
- If the drain passage is improper, water may drip down from the unit, wetting and
damaging the furniture.
Please prepare the professional tools for R32 refrigerant heat pump before you do
maintenance.
R32
leak
detector
Explosion
- proof
vacuum
pump
Antistatic
gloves
ATTENTION:
Please observe the following rules when installing the
heat pump:
1. Any addition of chemicals must take place in the piping located downstream from the
heat PUMP.
2. Always place the heat pump on a solid foundation and use the included rubber mounts
to avoid vibration and noise.
3. Always hold the heat pump upright If the unit has been held at an angle, wait at least
24 horns before starting the heat pump.
1. PRODUCT OVERVIEW
1.1 Specifications
Code
Model
Heating
Capacity in
o
A27 C /
o
W27 C (kW)
COP
Range
Heating
Capacity in
o
A15 C/
o
W26 C (kW)
COP
Range
Operating
Temp.
Heating
Input
Power (kW)
Rated
Heating
Running
Current (A)
Power Supply
Compressor
Noise
(Min-
Max)
dB(A)
Water
Connections
(mm)
Water Flow
Volume
3
(m /h)
31000001
IHP13
3.5-13.5
6-16
2-9.5
4.5-8
-15 C
0.22-
2.2
1-10
220~230V/1Ph/50Hz
Full DC
Inverter
42-50
50/48.3
4-7
31000002
IHP18
4.5-18
6-16
2.5-12
4.5-8
-15 C
0.35-
3.2
1.8-15
220~230V/1Ph/50Hz
Full DC
Inverter
42-50
50/48.3
5-8
31000003
IHP21
5-21
6.1-16.1
3-14.5
4.6-8.1
-15 C
0.4-3.4
1.8-15.5
220~230V/1Ph/50Hz
Full DC
Inverter
42-52
50/48.3
5-8
31000004
IHP26
7-26
6-15.5
4-18
4.5-8.1
-15 C
0.5-4.3
2.3-21
220~230V/1Ph/50Hz
Full DC
Inverter
43-53
50/48.3
5-8
31000005
IHP36
9-36
6-16
6-24
4.5-8
-15 C
0.75-6
3.4-27.3
220~230V/1Ph/50Hz
Full DC
Inverter
46-54
50/48.3
6-10
31000006
IHP36S
9-36
6-16
6-24
4.5-8
-15 C
0.75-6
1.3-10.7
380~415V/3Ph/50Hz
Full DC
Inverter
46-54
50/48.3
6-10
Code Model
Net
Weight
(KG)
Gross
Weight
(KG)
Net
Dimensions
(without front cover)
(mm)
Packing
Dimensions
(without front
cover)
(mm)
Net dimensions
(with front cover)
(mm)
Packing
Dimensions
(without front
cover) (mm)
31000001
31000002
31000003
31000004
31000005
31000006
IHP13
IHP18
IHP21
IHP26
IHP36
IHP36S
50
55
75
78
120
120
58
63
85
85
135
135
970*370*650
970*370*650
1115*430*850
1115*430*850
1115*430*1350
1115*430*1350
1170*415*800
1170*415*800
1200*520*990
1200*520*990
1200*520*1350
1200*520*1350
970*470*650
970*470*650
1115*530*850
1115*530*850
1115*530*1350
1115*530*1350
1170*515*800
1170*515*800
1200*620*990
1200*620*990
1200*620*1500
1200*620*1500
1.2 Dimension
Size(mm)
IHP13/IHP18
IHP21/IHP26
IHP36/IHP36S
A B C D E F G H
650
850
1350
942
1102
1102
305
350
540
96
106
96
400
460
460
380
440
440
700
800
800

P11 LOCATION
1. The air source heat pump must be installed outdoors. It cannot be installed indoors.
2. Never install the unit in a closed room with a limited air volume in which the air
expelled from the unit will be reused, or close to garden plants that could block the air
inlet. Such locations impair the continuous supply of fresh air, resulting in reduced
efficiency, performance and possibly preventing sufficient heat output.
3.During normal operations, the heat pump evaporator fins produce condensation water.
The amount of condensation produced varies according to ambient conditions. The
higher the air humidity, the higher the amount of condensation produced (several
liters per day). The lower heat pump panel acts as a condensation collection tray. Keep
the drain hole clean.
4. The heat pump must be positioned to avoid damages caused by water or condensation
leaks. Install suitable drainage outlets or collection containers.
5. The heat pump must be fixed and installed on a flat, solid, vibration free and level
support (cement slab or prefabricated platform). Do not install the heat pump on
unstable ground.
6. Make sure the pump is not subject to rain water flows from nearby building roofs.
Protruding roofs without gutters could pour significant amounts of water and/or
debris on the heat pump which could damage it. If necessary, install gutters or
discharge outlets to protect the heat pump.
7. Make sure the heat pump is not within the range of any sprinkler or irrigation systems.
If necessary, install suitable protections.
2.2 How to remove the front cover
Lift the front panel up
Loosen the screw
2.3 Condensation Draining Hose Installation
NOTE: The air drawn into the heat pump is strongly cooled by the operation of the heat
pump for heating the pool water, which may cause condensation on the evaporator fins.
The amount of condensation may be as much as several litres per hour at high relative
humidity. This is sometimes mistakenly regarded as a water leak.
1. Slightly tilt the unit to reveal the bottom panel.
2. Attach the drain hose connector (9) to the bottom panel.
3. Attach the wider end of the drain hose (10) to the hose connector and place the other
end into a suitable discharge area.
LOCATION P12
2.1 Location and Space Requirement
2. LOCATION

2.4 Water Connection
The following retail components (not included) are recommended for the hydraulic
connections:
1.Cut-of valves upstream and downstream from the heat pump to facilitate maintenance
and/or heat pump bypass from the pool water circulation system.
2.A non-return or check valve, installed between the pool and the heat pump outlet
fitting, to prevent water reflux.
All chemical feeder or water treatment devices must be installed downstream from the
heat pump and non-return (check) valve. It is important to install a check valve to prevent
chemical saturated water reflux which could damage the heat pump and void the
warranty.
The water circulation system must be arranged observing the following general layout:
Poo→Pump→Filter →Heat Pump→ Non-return/Check Valve →Chemical→
Treatment→ Pool
2.5 Connecting the By-pass Kit
2.6 Typical in-ground pool arrangement
Valve 1:
Slightly closed
(Water pressure increase with just 100 to 200gr)
Valve 2:
Completely open
Valve 3:
Half way open
NOTE: Operation without a bypass or with improper bypass adjustment may result in
sub-optimal heat pump operation and possibly damage to the heat pump, which renders
the warranty null and void.
Although the heat pump is electrically isolated from the rest of
the swimming pool system, this only prevents the flow of
electrical current to or from the water in the pool. Grounding
the heat pump is required for protection against short-circuits inside the unit.
Always provide a good grounding connection outlet. If not sure, contact a
qualified electrician for assistance.
P13 LOCATION LOCATION P14

2.7 Electrical Connection
Caution:
1. Use a properly sized main electrical switch.
The power supply for the heat pump must be grounded.
Electrical wiring must be done by a qualified technician.
The electrical wiring must be carried out in compliance with local regulations. The
electrical wiring must be done with the unit with local regulations.
Wiring must be securely fastened.
Do not let the wiring touch together.
Make sure that the main power supply complies with the name plate on the unit.
Make sure that the power, wiring and power socket comply with the power of the
appliance.
To connect the appliance to the power supply, proceed as the wiring diagram of the unit.
Cable Wiring:
1.Open the wiring block
box (marked white) on
the side of the machine.
2.Fix the other side on
joints inside the electric
box follow 'L", 'N",
'Earth" symbols.
Water Pump Wiring:
1.Open the wiring block
box (marked white) on
the side of the machine.
2.Fix the other side on
joints inside the electric
box follow 1", “2"
symbols (Max 200W for
this dry contact if it is
connected to water
pump directly).
2.8 Before Starting
Make sure the pool is filled with water to the correct level, the skimmer and suction
fittings are below the water level.
To heat the pool water, the filter pump must be running to cause the water to circulate
through the heat pump. The heat pump will not start up if the water is not circulating,
therefore the heat pump must operate together with the filter pump.
After all the water connections have been attached and checked, carry out the following
procedure:
1. Switch on the filter pump. Check for leaks and verify that water is flowing from and to
the swimming pool.
2. Press the On /Off button on the control unit panel to activate it, the display shows the
water inlet and outlet temperatures. The unit will start up after the time delay expires
(see "Time Delay" section).
3. After a few minutes, check whether the air blowing out of the heat pump fan is cooler.
4. When the filter pump is turned off, the heat pump should also turn of automatically, if
not, then adjust the flow switch (performed by specialist technician only).
5. Allow the heat pump and the filter pump to run 24 hours a day until the desired water
temperature is reached. The heat pump will stop running at this point. After this, it will
restart automatically (as long as the filter pump is running) whenever the swimming
pool water temperature drops 2 degrees below the set temperature.
6. To set the water temperature and program the heat pump, see "Display Control Panel
Operation" section for details.
Depending on the initial temperature of the pool water and the ambient air temperature,
it may take several days to heat the pool water to the desired temperature. A good solar
pool cover can reduce the heating time.
Time Delay
The heat pump has a built-in 1 to 2-minute start-up delay to protect the control circuit
components and avoid excessive restart cycles. The unit will restart automatically
P15 LOCATION LOCATION P16

P17 DISPLAY AND OPERATION DISPLAY AND OPERATION P18
3. DISPLAY AND OPERATION
after this time delay expires. Even a brief power interruption will trigger this time delay
and prevent the unit from restarting
immediately. Additional power interruptions during this delay period do not affect the 1
to 2-minute duration of the delay.
Water Flow Switch
The heat pump is equipped with a flow switch to protect it from running without
adequate water flow rate. It will turn on when the pump runs and shut it off when the
pump shuts off. If the pool water level is higher than 1m above or below the heat pump's
automatic flow switch adjustment knob, your specialist technician may need to adjust the
initial start-up water flow rate.
the same keyboard functions)
3. 1 Keyboard (it might have different kind of control panel with
3. 2 Display of Controller
This is the main screen when the unit is power on. Parameters setting by pressing keys

3. 4 The Main Masks of Controller
This is the main screen when the unit is power on. Parameters setting by pressing keys
3. 3 Structure of Interface Display
Press key to enter next stage interlace, press key to next mask in same stage.
P19 DISPLAY AND OPERATION DISPLAY AND OPERATION P20

3.5 Unit On/Off
TYou can turn the unit On/Off in Unit On Off mask page.
TYou can turn the unit On/
Off in Unit On Off mask page.
Press key then
Press key to turn the unit
ON/OFF
3.6 Unit On/Off
You can set the temperature in this main mask by pressing key
3.7 Work Mode Changing (Heating/Cooling)
You can change the Heating/Cooling work mode by pressing key
Please turn the unit OFF before you do this setting changing.
3.8 Turbo Mode Changing
"TB” is shown if
turbo mode is on
You can change different language by pressing key press key "Esc" to exit this page
3.9 Language setting
"TB” is shown if
turbo mode is on
3.10 I/O Mask (figures & status checking)
You can check the figures and status of the unit by pressing key
Figures and status might be different if model or settings different.
P21 DISPLAY AND OPERATION DISPLAY AND OPERATION P22

Keep pressing key
P23 DISPLAY AND OPERATION DISPLAY AND OPERATION P24

You can set the Date, Clock and Timezone of unit running.
3.11 Timezone /Clock setting
You can set the user figures after go into this setting page.
3.12 User Figures Setting
P25 DISPLAY AND OPERATION DISPLAY AND OPERATION P26

You can set the professional figures with Login Password.
Call your technical support to find the password.
Press key to start program setting.
(for professional technician only)
3.13 Professional Program Setting
You can set the advanced parameters of the unit (it need password to login).
3.14 Alarm Checking
4. MAINTENANCE
General Recommendations
1. Check the water supply circulation system regularly for water leakage and air entering
into the system, as the performance and reliability of the unit will be reduced.
2. Clean the pool water and filtration media regularly to maximize the performance and
to prevent damage to the heat pump.
3. Regularly check all the panels and screws are securely attached.
Restore water flow to the heat pump, open the valves at the bypass kit and make sure
filter pump is ON.
MAINTENANCE P28
P27 DISPLAY AND OPERATION

Disposal and Decommissioning
Collecting recyclable material, both those used for packaging (cardboard, nylon, etc.)
and those replaced during routine and major maintenance is recommended. Suitable
collection of waste material for recycling, processing and environmentally compatible
disposal contributes in avoiding possible negative efects on the environment, health
and promotes the reuse and/or recycling of device materials. Incorrect product
disposal by the user may be punishable by current national laws.
When the unit reaches the end of its working life and must be removed and/or replaced,
follow the instructions below:
1. Refrigerant gas must be collected by specialized technicians and sent to collection
centers.
2. Compressor lubricant oil must be collected by specialized technicians and sent to
collection centers.
3. The housing and other parts, if unusable, should be dismantled and divided according
to their material type (for example, copper, aluminium, plastic, etc.) and must be sent
to collection centers.
Winterizing
Failure to winterize could cause damage to the heat pump and void the warranty.
1. Turn of the heat pump and unplug the power cable from the main electrical outlet. Or
turn of the electrical power at the main circuit breaker panel.
2. Shut of the water supply (bypass kit) to the heat pump.
3. Disconnect the IN and OUT water connections and drain out all the water from the heat
pump. Use air to blow out any standing water inside the unit.
4. Reconnect the IN and OUT connections loosely to prevent debris entering the water
connections.
5. Drain out all the water at the bottom of the heat pump panel.
6. Protect the heat pump from dirt accumulation. Do not wrap the heat pump with plastic
or other material that can hold heat and/or humidity inside the device. Use the
included protective cover.
Spring Startup
If the heat pump has been winterized, perform the following steps when starting the
system in the spring:
1. Remove the protective cover and inspect the unit for any debris or structural
problems.
2. Tighten the IN and OUT water connections securely.
3. Check the pool water chemical is balanced, see Pool Water Chemistry" section.
4. Restore water flow to the heat pump, open the valves at the bypass kit and make sure
filter pump is ON.
5. Restore electrical power to the heat pump and test the RCD.
POOL WATER CHEMISTRY
Special care must be taken to keep your pool water chemical balanced within the
following limits:
If the concentration of one or more of the above readings becomes too high, irrevocable
damage to your heat pump may occur. Failure to keep the pool water chemical between
the limits will void the warranty.
Consult with your local swimming pool dealer for water treatment recommendation.
Preferred Water Chemistr y Reading
Minimu
Ideal
Maximum
Free Chlorine
0
0.5 - 3.0 ppm
5.0 ppm
Combined Chlorine
0
0 ppm
0.2 ppm
pH
7.2
7.4-7.6
7.8
Total Alkalinity
40 ppm
80
120 ppm
Calcium Hardness
50 ppm
100-250 ppm
350 ppm
Stabilizer (Cyanuric Acid)
10 ppm
20 - 40 ppm
50 ppm
P29 MAINTENANCE MAINTENANCE P30

5. TROUBLESHOOTING
Fault
Cause
Solution
The appliance doesn’t
start
1. No power supply.
Check the power supply.
2. The fuse on the gas side control board has
tripped or the switch is open.
Verify that the circuit is not open and that it is properly
grounded. Replace the fuse and reset the switch. Check
that the circuit is stable and that the connections are well
done.
3. Some protection has intervened.
Identify the protection intervened, restore it and restart
the appliance.
4. Slow wiring.
Check the electrical wiring and tighten the connections.
5. Compressor broken.
Replace the compressor.
The fan doesn’t work
1. Wiring motor not connected.
Check the wiring motor.
2. Fan motor fault.
Replace the fan motor.
Low heating performance
1.The plate heat exchanger is dirty.
Clean the plate heat exchanger.
2.Ventilation is insufficient.
Remove the objects that prevent air circulation.
3. Insufficient refrigerant.
Check that there are no leaks in the appliance and system, if
necessary, repair them. Replace the refrigerant with new product
4.Temperature out of range
Check that the setpoint temperature is not too high in heating or
Abnormal noise from the
pump or no water
circulation while the
pump is running
1.Water loss in the circuit.
Check the filling tap, fill the circuit with the right amount of
water.
2.Air in the hydraulic circuit.
Remove air from the circuit.
3.The valves in the hydraulic circuit are not fully
open.
Verify that all valves are fully open.
4. The water filter is dirty or clogged.
Clean the filter or replace it.
Compressor
discharge
pressure too high
1. Too much refrigerant.
Replace the refrigerant with new product and correct quantity.
2.Air in the refrigerant circuit.
Replace the refrigerant with new product and correct
3.Inadequate water flow.
Check the water flow in the circuit, if necessary, use a more
performing pump.
4. Too high Temperature
Make sure that the water supply temperature sensor works
properly.
Suction pressure too low
1. Dirty filter drier.
Replace the filter drier.
2. Electronic expansion valve blocked.
Repair or replace it.
3. Loss of refrigerant.
Check that there are no leaks in the appliance and in the
system, if necessar y, repair them. Replace the refrigerant with
new product and in the correct quantity.
The appliance does not
complete the defrost
cycle
1. Expansion battery sensor fault.
Check the position and value of the temperature sensor, if
necessary, replace it.
2. Ventilation is insufficient.
Eliminate objects that prevent air circulation. If necessar y,
clean the evaporation battery.
P31 TROUBLESHOOTING TROUBLESHOOTING P32

6. ALARM CODE LIST
Alarm
Code
Description
Possible Cause
Solution
AL54
Power+ alarm:
Undervoltage
The DC voltage of the intermediate
circuit is below the limits
envisioned due to:
insufficient power supply voltage;
fault inside the drive.
In the event of temporary cut-off of the power
supply, reset the alarm and re-start the drive.
Check the power supply voltage.
AL55
Power+ alarm:
Drive over
temperature
The temperature inside the drive
has exceeded the maximum level
allowed.
Check that the quantity and flow of cooling air
are regular. Check that there is not dust in the
heat sink. Check the environment temperature.
Ensure that the switching frequency is not too
AL56
Power+ alarm:
Drive under
temperature
The temperature of the drive is
inferior to the minimum level
allowed.
Warm up the ambient where the drive is
installed.
AL57
Power+ alarm:
Overcurrent HW
The drive has detected an
instantaneous current supplied that
is too
high due to:
sudden strong load increase;
Check the load, the dimension of the motor and
the cables. Check the motor parameters.
AL58
Power+ alarm:
Reserved
AL59
Power+ alarm:
Reserved
AL60
Power+ alarm:
CPU error
Loss of data in memory
Reset alarm. In case of persistence call for
assistance
AL6I
Power+ alarm:
Parameter default
Execution of reset parameter
default command;
Parameters user setting corrupted
Set parameters again
AL62
Power+ alarm:
DC bus ripple
Input power supply phase loss
Check the input power supply phases to the
drive
AL63
Power+ alarm:
Data communication
fault
Data reception failure
Check the serial connection. Switch the drive off
and back on again. In case of persistence call for
assistance.
AL64
Power+ alarm:
Drive thermistor
Internal fault
Reset alarm. In case of persistence call for
AL65
Power+ alarm:
Reserved
AL66
Power+ alarm:
Reserved
AL67
Power+ alarm:
Motor phase
fault (**)
Motor cable disconnected
Check the connections of the motor cable
AL68
Power+ alarm:
Reserved (for
future use)
AL69
Power+ alarm:
Speed fault
Wrong parameters values or
unsuited load
Switch the drive off and back on again and check
the parameters are
properly set. Check the motor load.
AL70
Power+ alarm:
PFC module
error
PFC overcurrent
Reset alarm. In case of persistence call for
assistance
AL71
Power+ alarm:
Power supply
over voltage
Too high AC power supply voltage
Check input power supply and if inductive load
generating
over voltage are connected to the line
AL72
Power+ alarm:
Power supply
Too low AC power supply voltage
Check input power supply
AL73
Power+ alarm:
Reserved
AL74
Power+ alarm:
Reserved
AL75
Power+ alarm:
Ground fault
The drive has detected a ground
current too high
Check ground insulation of the motor and wires
AL76
Power+ alarm:
CPU sync error
Overload CPU
Reset alarm. In case of persistence call for
assistance
AL77
Power+ alarm:
CPU sync error2
Loss of data in memory
Reset alarm. In case of persistence call for
assistance
AL78
Power+ alarm:
Drive overload
The current supplied has exceeded
the drive rated current over the
maximum time accepted
Check the load, the dimension of the motor and
the cables. Check the motor parameters.
Alarm
Code
Description
Possible
Cause
Solution
AL01
Too many mem writings
Program is over writing
Reset the unit and alarm, clean the old version
program.
AL02
Retain mem write error
Memory writing error
Reset the unit and alarm, update to a new
version program and clean the old
AL03
Inlet probe error
Water inlet temp. sensor fail or loose
connection
Check the wire connection or replace a new
sensor
AL04
Outlet probe error
Water outlet temp. sensor fail or loose
connection
Check the wire connection or replace a new
sensor
AL05
Ambient probe error
Ambient temp. sensor fails or loose
connection
Check the wire connection or replace a new
sensor
AL06
Condenser coil temp
Condenser coil temp. sensor fail or loose
connection
Check the wire connection or replace a new
sensor
AL07
Water flow switch
Water flow sensor fail or loose
connection
Check the water flow volume is big enough or
not, check flow switch sensor
AL08
Phase sequ.prot.alarm
Phase wrong or
Check the power input wiring
AL09
Unit work hour warning
The unit over running time
Contact your technical support
AL10
Pump work hour warning
The water pump over running time
Contact your technical support
AL11
Comp.work hour warning
The compressor over running time
Contact your technical support
AL12
Cond.fan work hourWarn
The condenser fan motor over running
time
Contact your technical support
AL13
Low superheat - Vlv.A
Superheat of EEV1 is too low
Contact your technical support
AL14
Low superheat - Vlv.B
Superheat of EEV2 is too low
Contact your technical support
AL15
LOP - Vlv.A
EEV1 LOP alarm
Contact your technical support
AL16
LOP - Vlv.B
EEV2 LOP alarm
Contact your technical support
AL17
MOP - Vlv.A
EEV1 MOP alarm
Contact your technical support
AL18
MOP - Vlv.B
EEV2 MOP alarm
Contact your technical support
AL19
Motor error - Vlv.A
Motor of EEV1 alarm
Contact your technical support
AL20
Motor error - Vlv.B
Motor of EEV2 alarm
Contact your technical support
AL21
Low suct.temp. - Vlv.A
Low suction temp. alarm for EEV1
Contact your technical support
AL22
Low suct.temp. - Vlv.B
Low suction temp. alarm for EEV2
Contact your technical support
AL23
High condens.temp.EVD
High condenser temp. alarm for EEV
Contact your technical support
AL35
BLDC-alarm:
Pressure different too much when start
Contact your technical support
AL36
BLDC-alarm:
Compressor stop
Contact your technical support
AL37
BLDC-alarm:
Compressor run out of operating range
Contact your technical support
AL38
BLDC-alarm:
Compressor fail in start
Contact your technical support
AL39
BLDC-alarm:
Compressor fail in start
Contact your technical support
AL40
BLDC-alarm:
Pressure different too low when running
Contact your technical support
AL41
BLDC-alarm:
Discharge temp. is too high
Contact your technical support
AL51
Power+ alarm:
Overcurrent
The drive has detected a current supplied
that is too high due to:
sudden strong load increase;
acceleration that is too high;
wrong parameters values or
inadequate motor.
Check the load, the dimension of the motor
and the cables. Decrease acceleration, check
the motor parameters.
AL52
Power+ alarm:
Motor
overload
The current supplied has exceeded the
motor rated current over the maximum
time accepted
Check the load, the dimension of the motor
and the cables. Check the motor parameters.
AL53
Power+ alarm:
Overvoltage
The DC voltage of the intermediate circuit
has exceeded the limits envisioned due to:
- deceleration that is too high; - high over-
voltage peaks on
the power supply network
Decrease deceleration.
P33 ALARM CODE LIST ALARM CODE LIST P34

7. DIAGRAMS
7.1 Wiring Diagram
Alarm Code
Description
Possible Cause
Solution
AL79
Power+ alarm:
Safety
inter vention
AL114
Power+ alarm:
Drive connection alarm
Check the wiring connection between
Power Drive and controller
AL115
EEV alarm:
Superheat of EEV is too low
Contact your technical support
AL116
EEV alarm:
EEV LOP alarm
Contact your technical support
AL117
EEV alarm:
EEV MOP alarm
Contact your technical support
AL118
EEV alarm:
High condenser temp. alarm for EEV
Contact your technical support
AL119
EEV alarm:
Low suction temp. alarm for EEV
Contact your technical support
AL120
EEV alarm:
Motor of EEV alarm
Contact your technical support
AL121
EEV alarm:
PID of EEV alarm
Contact your technical support
AL122
EEV alarm:
EEV Emergency stop alarm
Contact your technical support
AL123
EEV alarm:
EEV temp. different protection
Contact your technical support
AL124
EEV alarm:
EEV pressure different protection
Contact your technical support
AL125
EEV alarm:
EEV range error
Contact your technical support
AL126
EEV alarm:
EEV position error
Contact your technical support
AL127
EEV alarm:
EEV serial No. error
Contact your technical support
AL128
Low press alarm
Low pressure protection
Check refrigerant is enough or not
AL129
High press alarm
High pressure protection
Check water volume is enough or not,
check water or air temp. is high or not
AL130
Disc.temp.probe error
Discharge temp. sensor fail or loose
connection
Check discharge temp. check the wire
connection or replace a new sensor
AL131
Suct.temp.probe error
Suction temp. sensor fail or loose
connection
Check suction temp. check the wire
connection or replace a new sensor
AL132
Disc.press.probe error
Discharge pressure sensor fail
Check the running pressure, increase
the water volume or decrease the
setting temp.
AL133
Suct.press.probe error
Discharge pressure sensor fail
Check the running pressure, the
refrigerant is enough or not.
AL134
Tank temp.probe error
Water tank temp. sensor fail or
loose connection
Check water tank temp. check the
wire connection or replace a new
sensor
AL135
EVI SuctT.probe error
EVI suction temp. sensor alarm
Check EVI suction temp. check the
wire connection or replace a new
sensor
AL136
EVI SuctP.probe error
EVI suction pressure sensor alarm
Check EVI suction pressure, check
the wire connection or replace a new
sensor
AL137
Flow switch alarm
Water flow sensor fail or loose
connection
Check the water flow volume is big
enough or not, check flow switch
sensor wire connection
High temp. alarm
Water outlet temp. is too high
Check the water flow volume is big
enough or not, decrease the setting
temp.
AL139
Low temp. alarm
Water outlet temp. is too low
Check the water flow volume is big
enough or not, increase the setting
temp.
AL140
Temp.delta alarm
Temp. different is too much
between water inlet and outlet
Check the water flow volume is big
enough or not
AL152
Power freq.alarm
Frequency of power supply is
unstable
Stop and check the power supply
P35 ALARM CODE LIST DIAGRAMS P36

P37 DIAGRAMS DIAGRAMS P38
This manual suits for next models
11
Table of contents
Other emaux Heat Pump manuals
Popular Heat Pump manuals by other brands

Walter Roller
Walter Roller Silent Line WPV Mounting instructions

Heiko
Heiko Thermal 6 installation manual

Bryant
Bryant 548J Product data

Tivok
Tivok T-HP60AB Installation and operation manual

Cornelius
Cornelius UC-40 Installation and service manual

AAON
AAON ProFit WV Series Installation operation & maintenance