iglu Aleut User manual

USER MANUAL
GEOTHERMAL HEAT PUMPS IGLU® Aleut

2
TABLE OF CONTENTS
INTRODUCTION ......................................................................................................................3
CONCEPTS AND SYMBOLS...................................................................................................3
IMPORTANT INFORMATION...................................................................................................4
SAFETY INSTRUCTIONS ...................................................................................................................................4
SAFETY................................................................................................................................................................5
ENVIRONMENTAL PROTECTION......................................................................................................................5
IN CASE OF FAILURE.........................................................................................................................................6
PURPOSE............................................................................................................................................................6
HOW DOES A GEOTHERMAL HEAT PUMP WORK? .......................................................................................6
PRODUCT PACKAGING AND TRANSPORTATION..........................................................................................6
SELECTION OF THE INSTALLATION PLACE ...................................................................................................7
LOGO ILLUMINATION .............................................................................................................7
IGLU® HOME MOBILE APPLICATION....................................................................................7
INSTALLATION OF THE APPLICATION.............................................................................................................7
LOGIN AND REGISTRATION..............................................................................................................................8
ADDING A NEW DEVICE....................................................................................................................................8
MAIN APPLICATION WINDOW...........................................................................................................................9
TEMPERATURES SETTINGS.......................................................................................................................... 10
SYSTEM ERROR AND FAILURE INDICATIONS ............................................................................................ 10
LIST OF SYSTEM ERRORS AND FAULTS..................................................................................................... 11
INFORMATION SECTION................................................................................................................................ 14
SETTINGS SECTION ....................................................................................................................................... 14
THERMAL DISINFECTION............................................................................................................................... 16
SYSTEM STATUS ............................................................................................................................................ 16
STATISTICS SECTION..................................................................................................................................... 16
CONTROL PANEL .................................................................................................................17
Technical data of IGLU Aleut fixed capacity heat pumps........................................................19
Technical data of IGLU® Aleut WT fixed capacity heat pump with integrated water heater...20
Technical data of IGLU® Aleut WTI variable capacity heat pump with integrated water heater
................................................................................................................................................21
INFORMATION CONCERNING THE EU DECLARATION OF CONFORMITY............................................... 22

3
INTRODUCTION
Thank you for purchasing an IGLU® Aleut geothermal heat pump!
Our team hopes you will be satisfied with your new device and enjoy efficient heating, hot water and practically
free cooling for a long time.
In this manual you will find information on how to use and maintain the purchased geothermal heat pump
correctly. Keep this manual in a safe place for future reference.
IGLU® heat pumps are designed and selected for each facility to ensure maximum heating, cooling and hot
water preparation in the building.
IGLU® heat pumps are equipped with a convenient control system that allows to control the functions of the
heat pump, select individual settings and help to quickly find and eliminate faults. The device can also be
controlled via a mobile application. All you have to do is download the user-friendly IGLU® Home app (see,
page 8).
It is important to pay attention to the safety requirements that must be observed in order not prevent
injuries and enjoy the device for a long time.
CONCEPTS AND SYMBOLS
Water heater (boiler) is a device that performs a very important function –it prepares hot water.
Thermal disinfection (thermal shock) is a process in which the temperature of hot water in a water heater is
raised to at least 66°C and maintained for at least 1 hour. Thermal disinfection is used to prevent legionellosis,
i.e., to kill bacteria of the genus Legionella.
Glycol (heat carrier) –antifreeze that is used to fill up the heating system (outdoor circuit).
Heating water is a liquid harmless to the environment and health that is used to fill the indoor part of the heating
system (internal circuit).
Outdoor circuit is a part of a geothermal heating/cooling system located in the ground for the
collection/transmission of underground thermal energy. It can be horizontal or vertical (geothermal wells).
COP –coefficient of performance. The instantaneous ratio of thermal energy produced to electricity consumed to
produce that heat.
SCOP –seasonal coefficient of performance.
Electricity consumption –electricity consumption during the operation of the heat pump.
Thermal energy produced –heat energy produced during the operation of a heat pump.
“WARNING!” SYMBOL
Warning of minor heating system faults or parameter deviations. Errors are not critical, the system can continue
to operate.
“ATTENTION!” SYMBOL
System failure warning. The heat pump is stopped.

4
IMPORTANT INFORMATION
The safety requirements are intended to protect consumers and ensure the long-term operation of the heat
pump. By purchasing the device, users confirm that they undertake to use it in accordance with the
manufacturer’s requirements and rules. Users involved in the operation of the heat pump must be familiar with
and comply with all safety requirements. Failure to follow these operating instructions will void the
manufacturer’s warranty and other guarantees and obligations. All work related to the transport, installation,
start-up, activation and maintenance of the heat pump must be carried out by qualified personnel, using suitable
tools and test equipment. The work must be carried out in accordance with all safety requirements.
The copyright of these operating instructions belongs to IGLU TECH UAB.
SAFETY INSTRUCTIONS
Storage conditions
The device must be stored in a vertical position only, so that the compressor is always at the bottom.
Installation and reconstruction
Only a heating system maintenance company may be authorised to install or reconstruct the device.
Customer recommendation
Functional check. We recommend that you check the functioning of the device regularly, at least once a year*.
Contact us for functionality check by e-mail help@iglutech.eu.The extended warranty for the device is valid
even in cases where preventive maintenance is not performed regularly.
Liability and guarantees:
The manufacturer undertakes to rectify the device free of charge within a period of two years, provided that
the user has not violated the technical requirements and operating conditions specified in the user manual.
The product has a 24-month warranty upon submission of the purchase documents.
The product warranty is extended up to 60 months, under the following mandatory conditions:
there is an additional cost of 5% of the pump price (payable immediately at the time of ordering);
it is mandatory to connect the pump to our server for remote monitoring.
If the heat pump does not operate in proper conditions or is not used properly, the present rules and
requirements are not followed or the checks are not performed, the manufacturer shall not bear liability for the
operation of the product. The heat pump operator must take precautions to prevent accidents and injuries to
bystanders. The user is responsible for the safety of the heating system and compliance with environmental
protection requirements.
If a fault is detected, it is necessary to react promptly, within a reasonable time and as provided in this user
manual, because failure to rectify a fault in a timely manner may result in other faults or damage.
If the fault or other actions were carried out by an unqualified worker and in prejudice to the rules, the
manufacturer cannot be held liable for the consequences and the warranty obligations may no longer apply.
The warranty does not apply to normal wear and tear, external damage due to improper maintenance or
negligence.
Only a qualified person may transport, connect, activate and
maintain the heat pump.

5
SAFETY
The device is safe to use as intended. The construction and design of the device comply with all safety
regulations. Prior to starting work, any person involved must read and be familiarised with the operating
instructions. This also applies if the person concerned has already worked on such or similar equipment or has
been trained by the manufacturer. Any person carrying out installation work must meet the health and safety
requirements. This is especially true when using personal protective equipment.
DANGER!
Danger of fatal injuries due to electric shock!
The electrical connection may only be installed by a qualified electrician.
Prior to opening the device, disconnect the system from the power supply
and prevent it from being switched on again!
WARNING!
Work on the device and its components may only be carried out by qualified specialists (heating,
refrigeration, coolant technicians and electricians).
WARNING!
Observe the safety signs on and inside the device.
WARNING!
The unit contains coolant!
If the coolant leaks, it poses risk to people
and the environment, therefore, you must:
–
turn off the system;
–
make sure the installation room is well ventilated;
–
inform the manufacturer’s customer service.
ATTENTION!
For safety reasons, never disconnect the device from the power supply unless the device is open.
Do not use pure water in the outdoor circuit.
ENVIRONMENTAL PROTECTION
Environmental protection is a priority of IGLU TECH UAB. Product quality, cost-efficiency and environmental
protection are equally important to us. Therefore, we strictly adhere to environmental requirements. In order to
protect the environment and take into account financial possibilities, we use the best technologies and materials
in our production.
Packaging. When designing packaging, we take into account the countries’ local waste recycling systems,
which ensure optimal reuse. All packaging materials are environmentally friendly and recyclable.
Disposal. Obsolete devices contain recyclable materials. The structural elements can be easily disassembled.
The structural elements must be sorted for processing and recycling.
Glycol (antifreeze mixture) should not be discarded into the drains. Collect glycol and dispose of properly in
accordance with applicable regulations, standards and directives.

6
IN CASE OF FAILURE
If the illuminated IGLU® logo on the front panel or the IGLU® Home mobile application reports system errors
(see, page 8), please contact us immediately and report any error by specifying:
date of purchase of the device;
error that occurred;
environmental conditions (indoor and hot water tank temperature).
You can register a heat pump fault by e-mail h[email protected], by calling +370 523 94949 or on our
website here.
IGLU TECH UAB CUSTOMER SERVICE CONTACTS
Tel.: +370 523 94949
PURPOSE
Geothermal heating is an alternative building heating system that uses free, underground heat. With the
help of a ground-to-water heat pump, this geothermal energy is extracted and used for heating, cooling and hot
water preparation in buildings.
Advantages of IGLU® Aleut heat pumps
Uses inexhaustible and ecological underground energy
Next-generation technologies and solutions ensure maximum efficiency and minimum cost
One device performs three functions –room heating, cooling and hot water preparation
Comfort at home can be controlled from anywhere in the world
HOW DOES A GEOTHERMAL HEAT PUMP WORK?
The principle of operation of a geothermal heat pump is similar to that of a refrigerator. Only in this case cold
output is directed outdoor or into soil, and the heat to the household.
The liquid (glycol) circulating in the outdoor circuit is heated by the heat accumulated in the ground, lake or
groundwater. As it flows through the heat pump, the liquid enters another closed system. It contains a coolant
called freon (refrigerant), which turns into gas at very low temperatures. The high-pressure compressor greatly
increases the temperature of the gaseous freon. The condenser supplies heat to the home heating system and
at the same time the freon becomes liquid again, ready to transform into gas again and store more thermal
energy.
PRODUCT PACKAGING AND TRANSPORTATION
IMPORTANT! After purchasing a heat pump:
Inspect the delivered product for external damage incurred during delivery;
In the event of delivery defects, submit a claim to the company that sold the device immediately.
The heat pump may only be transported and stored in an upright position. The device can only be temporarily
tilted, not laid down. The device can be stored at a temperature no lower than -10°C.

7
SELECTION OF THE INSTALLATION PLACE
When choosing the place of installation of the heat pump, mind that the heat pump produces a certain
level of noise (see, “Technical data according to European Commission Regulation No 813/2013”).
The device must be mounted on a flat and stationary surface with a permissible load of at least
300 kg/m2. Minor surface irregularities can be compensated by adjusting the feet of the device.
The ambient temperature near the heat pump must be between 10°C and 35°C, and the relative
humidity must not exceed 80%.
There must be no aggressive chemicals in the environment.
The heat pump should not be installed close to walls; the front of the unit should always be accessible
(see, Installation Manual “Heat pump installation drawing”).
A drainage system must be provided in the room where the unit is installed.
LOGO ILLUMINATION
The IGLU® Aleut heat pump has an illuminated IGLU®
logo on the front panel. The logo can be illuminated in
three different colours –blue, yellow or red. Each of them
has a corresponding meaning:
blue –heat pump on, normal operation;
yellow –warning about non-critical failure of the
heat pump or slight deviation of parameters from the
norm; the heat pump continues to operate, but it is
necessary to react promptly, within a reasonable
period of time;
red –heat pump failure, operation is stopped.
IGLU® HOME MOBILE APPLICATION
IGLU® Aleut geothermal heat pumps are controlled via the IGLU® Home
app. It allows to control the device and monitor the operating parameters
of the heating system, electricity consumption, thermal energy produced
and instantaneous or seasonal coefficient of performance in real time.
INSTALLATION OF THE APPLICATION
Download and install the IGLU® Home app.
The iOS version is available here.
The Android version is available here.
You can also download the app by scanning the QR codes on page 8.

8
App Store Google Play
LOGIN AND REGISTRATION
When you open the IGLU® Home app for the first time, you will
need to log in or register by clicking the Login or Register
buttons (Window 1).
When the registration window opens, enter the following
information (Window 2):
Name;
Surname;
Phone number;
E-mail address;
Password.
Please also read the Privacy Policy and indicate that you agree
to the terms specified.
To complete the registration, click the button:
When the login window opens, enter the following
information (Window 3):
E-mail address;
Password.
You can log in by clicking the button:
If you forgot your password, click Remind password.
ADDING A NEW DEVICE
Upon successful registration, you will be directed to the Add New
Device window (Window 4), where you need to:
Enter the address of installation of the heat pump;
Give the device a name to make it easier to distinguish between the devices in use;
Enter the serial number according to the scanned QR code (you will find the QR code on the device).
Window 1
Window 2
Window 3
Window 4

9
After entering this information, click “Add a device”.
MAIN APPLICATION WINDOW
When you log in to the application, you will see the following information at the top of the main window:
outside temperature;
last data update time (data is automatically updated every 10 seconds); data can also be updated
manually by swiping a finger from top to bottom;
system error and failure notifications.
In the real-time settings bar, you will see:
how much kW of electricity is being used;
how much kW of heat energy is being produced;
what is the coefficient of performance (COP) (the ratio of thermal energy produced to electricity
consumed to produce that heat).
IMPORTANT!
The IGLU® Home application is supported by the latest versions of iOS and Android OS, but may
not work properly with some mobile phone models. E.g.: OnePlus, Xiaomi. This list is not
exhaustive.
Outside temperature
System failure notification
Last data usage time
Room temperature settings
Actual room air temperature
Set room air temperature
Set temperature reduction
Real-time settings bar
Water preparation temperature settings
Actual water temperature
Set water temperature
Set temperature increase
STATISTICS section
SETTINGS section
INFORMATION section

10
Window 5
TEMPERATURES SETTINGS
In the main window you can set the desired room air and hot water temperatures
(Window 5). This is carried out at follows:
by clicking on one of the symbols, the settings of which you want to change
(the activated function turns blue);
use +/- buttons to increase or decrease the indoor air or hot water
temperature;
the numbers above indicate the current temperature and the numbers below
indicate the set temperature (set for the system);
the settings can be “locked” by clicking on the symbol again.
SYSTEM ERROR AND FAILURE INDICATIONS
If the symbol in the right corner of the main window is flashing or –
the system indicates a system error or fault. In the event of a system fault (bright
triangle), the heat pump will continue to operate, but every effort should be made to
rectify the fault. In the event of a system fault (dark triangle), the heat pump operation
will stop.
By clicking on the flashing symbol you will be redirected to the Active
Messages window (Window 6), where you will see a list of system errors and faults.
The full list of the meanings of these messages and possible causes is provided
below, as well as instructions on the actions the user should take.
When a non-critical issue is resolved, the error message disappears
automatically (without confirmation). After of elimination of other errors or a system
failure, they can only be confirmed from the local control panel. See, section Control
Panel on page 16. The fault is confirmed by pressing the Report button on the control
panel for >4 seconds.
Window 6

11
LIST OF SYSTEM ERRORS AND FAULTS
ITEM
POSSIBLE CAUSE
ACTION
Incoming glycol
temperature sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Outgoing glycol
temperature sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Outgoing heating
water temperature
sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Incoming heating
water temperature
sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Water heater
temperature sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Room temperature
sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Outdoor temperature
sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
LP low pressure
Low refrigerant pressure during
operation.
Clean the outdoor circuit filter. Check that the
outdoor circuit pump is operating properly.
Check for air in the outdoor circuit system.
Possible freon deficiency.
Low glycol flow in the outdoor circuit.
Check the heating water pressure in the
outdoor circuit, rate 1-2 bar. Clean the dirt
trap. If the problem persists, contact
customer service.
HP high pressure
High refrigerant pressure during
operation.
Clean the internal circuit filter. Check that the
internal circuit pump is operating properly.
Check for air in the internal circuit system.
Low heating water flow in the internal
circuit.
Check the heating water pressure in the
internal circuit, rate 1-2 bar. Clean the dirt
trap. If the problem persists, contact
customer service.
Compressor thermal
protection
Overvoltage, low voltage.
Contact customer service.

12
Voltage and phase
control
Bad phase sequence. One or two
phases are missing.
When the problem is resolved, the error
disappears automatically.
Hot water preparation
time too long
Three-way valve failure.
Contact customer service.
Large temperature
difference in the
outdoor circuit
Low glycol flow in the outdoor circuit.
Clean the outdoor circuit filter.
If the problem persists, contact customer
service.
Large temperature
difference in the
internal circuit
Low heating water flow in the internal
circuit.
Clean the internal circuit filter.
If the problem persists, contact customer
service.
Tank temperature
sensor
Temperature sensor or connection
failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Communication
between controllers
Control unit failure.
Contact customer service.
Low pressure sensor
Pressure sensor failure.
Contact customer service.
High pressure sensor
Pressure sensor failure.
Contact customer service.
Exhaust temperature
sensor
Temperature sensor failure.
Contact customer service.
Valve controller failure
Control unit failure.
Contact customer service.
Solar collector sensor
Sensor or connection failure.
Contact customer service.
When the problem is resolved, the error
disappears automatically.
Valve configuration
Incorrect EEV valve configuration.
Contact customer service.

13
FC not ready
The frequency converter is not ready
for operation. E.g., oil return to the
compressor.
Contact customer service. When the problem
is resolved, the error disappears
automatically.
External alarm
External failure (DI). If it is provided
that the heat pump can be stopped
from an external signal.
Eliminate the external fault signal.
Possible refrigerant
leakage
Possible refrigerant leakage.
Contact customer service.
Blocking of the
outdoor circuit
circulation pump
(jamming)
Blocking of the outdoor circuit
circulation pump (jamming).
Clean the intake or supply nozzle of the
outdoor circuit pump. If the problem persists,
contact customer service.
Electrical failure of the
outdoor circuit
circulation pump
Electrical failure of the outdoor circuit
circulation pump.
Contact customer service.
High temperature in
the outdoor circuit
circulation pump
electronics
High temperature in the outdoor
circuit circulation pump electronics.
If the operating mode was extreme: after
switching off the heat pump, wait for the
outdoor circulation pump to cool down. If the
problem persists, contact customer service.
Operation failure of
the outdoor circuit
circulation pump
Operation failure of the outdoor circuit
circulation pump.
Contact customer service.
Blocking of the
internal circuit
circulation pump
(jamming)
Blocking of the internal circuit
circulation pump (jamming).
Clean the intake or supply nozzle of the
internal circuit pump. If the problem persists,
contact customer service.
Electrical failure of the
internal circuit
circulation pump
Electrical failure of the internal circuit
circulation pump.
Contact customer service.
High temperature in
the indoor circuit
circulation pump
electronics
High temperature in the internal
circuit circulation pump electronics.
If the operating mode was extreme: after
switching off the heat pump, wait for the
internal circulation pump to cool down. If the
problem persists, contact customer service.
Operation failure of
the internal circuit
circulation pump
Operation failure of the internal circuit
circulation pump.
Contact customer service.
Electric heater
protection has tripped
Electric heater protection has tripped.
Contact customer service.
Thermal disinfection
failed
The required disinfection temperature
has not been reached for too long.
Contact customer service.
Risk of freezing
The temperature dangerously close to
the possible freezing point.
In order not to damage the device, piping
and heating system, measures must be
taken to raise the ambient temperature.
Supply temperature
too high
Supply temperature too high.
Contact customer service.
Controller
communication failure
The connection between the
controller modules is lost.
Contact customer service.

14
Internal circuit
circulating pump
power measurement
failure
Fault in the power measurement
chain of the internal circuit’s
circulating pump.
Contact customer service.
Outdoor circuit
circulating pump
power measurement
failure
Fault in the power measurement
chain of the outdoor circuit’s
circulating pump.
Contact customer service.
Compressor
frequency converter
failure
Compressor frequency converter
failure. Details are displayed on the
frequency converter screen.
Contact customer service.
Internal circuit flow
sensor failure
Internal circuit pressure sensor is
defective.
Contact customer service.
Failure of analogue
measurement from
frequency converter
Measurement failure of the frequency
converter’s power measurement
circuit.
Contact customer service.
INFORMATION SECTION
Clicking on the Information icon on the bottom bar will take you to
the information window (Window 7) where you can:
register system failure;
visit the manufacturer’s website;
access this User Manual.
SETTINGS SECTION
Clicking on the Settings icon on the bottom bar will take you
to the System window (Window 8), where you will see:
the name of the currently selected device;
water heater settings;
system status;
disconnect function.
You can move to the next window by pressing “<” and return
by pressing “>”.
After selecting My Device, in the window that opens (Window 9)
you can:
see the name of the currently selected device and select
another device from the list of devices;
see information related to the device (serial number,
name, address at which the heat pump is installed);
edit the information of the selected device;
add new device.
Clicking the Edit Selection button will take you to the device
edit window (Window 10) where you can update:
Window 7
Window 8
Window 9
Window 10

15
device address;
name of the device.
After making adjustments, click the Save button.
In the SETTINGS section, clicking the “>” button will take you
to an additional window (Window 11) where you can:
turn the device on/off;
change the language of the IGLU® Home app.
Window 12
Window 11

16
THERMAL DISINFECTION
When a water heater is installed in the system and an electric
heating element is integrated, the system periodically
performs thermal disinfection. In the water heater settings
window (Window 12) you can see information on the time of
the next thermal disinfection.
Clicking the Thermal Disinfection takes you to the
disinfection time setting window (Window 13), where you can
select the desired disinfection time.
In the Disinfection Time window, you can select:
the day of the week or days when you want the water
heater to be disinfected;
the time you want the water heater to be disinfected.
After selecting the days of the week and the preferred time,
click Set.
SYSTEM STATUS
In the System Status window (Window 14) you can see the
device settings, such as:
temperature of the glycol delivered to the ground;
temperature of the glycol returning from the ground;
temperature of the supplied heating water;
temperature of the returning heating water.
STATISTICS SECTION
Clicking the Chart icon on the bottom bar will take you to the
Statistics.Home heating, (Window 15) where you will see
daily, weekly, monthly or yearly energy consumption statistics,
heat production statistics and coefficient of performance.
IMPORTANT! When you select the annual statistics view, you will see the seasonal coefficient of
performance (SCOP) below the graph.
The blue bar shows how many kilowatt-hours of electricity were consumed during the selected period,
and black –the number of kilowatt-hours of heat produced. Click on a column to see its exact value.
Pressing “>” will take you to the water heating statistics window.
In the window “Statistics. Water heating.”(Window 16) you can see daily, weekly, monthly or yearly energy
consumption and heat production statistics.
The blue bar shows how many kilowatt-hours of electricity were consumed during the selected period,
and black –the number of kilowatt-hours of heat produced. Click on a column to see its exact value.
Window 13
Window 14
Window 15
Window 16

17
Window 1
Window 2
Window 5
Window 6
CONTROL PANEL
The control panel comes with the IGLU® Aleut heat pump.
The main panel window (Window 1) displays:
outside temperature;
water temperature;
set room air temperature.
You can also see if there are active system alerts or faults. If
the WARNING! symbol appears in the main panel window, click
the icon to view the messages. Follow the instructions in the
“List of system errors and warnings” table.
After rectifying the system error or fault, confirm it with the Report
button on the control panel by holding it for > 4 seconds (Windows
3 and 4)
Clicking on the IGLU logo at the bottom in the main window
(Window 1) will take you to the device status window
(Window 2).
In the device status window (Window 2) you can:
turn the device off or on;
activate the cooling function;
set the heating mode;
determine the time of thermal disinfection.
Navigation between windows in the control panel is performed
using the “<” and “>” buttons.
In the heating mode window (Window 5) you can select
one of the 2 automatic heating modes:
economical (holiday) –hot water is not prepared and the
temperature in the rooms is maintained at 14 °C;
comfort –hot water temperature in models with integrated
water heater is increased to 65 °C (if an electric heating
element is integrated). If there is no electric heating
element, the hot water temperature is increased to the
maximum permissible temperature. It depends on the installed water heater capacity and technical
characteristics.
and change the operating mode to:
•
automatic operation –the mode is set automatically to summer or winter according to the outdoor
temperature;
•
summer operation –only hot water is prepared automatically;
•
winter operation –rooms are heated automatically and higher priority is given to preparation of hot
water.
In the water temperature window (Window 6) you can:
Window 3
Window 4

18
see the current hot water temperature;
set the preferred hot water temperature.
In the room temperature window (Window 7) you can:
see the current room temperature;
set the preferred room temperature.
In the thermal water disinfection setting window
(Window 8) you can select:
day or days of the week on which the disinfection
will be carried out;
time at which disinfection will take place.
In the system window (Window 9), select the language of
the operator panel.
In the settings window (Window 10) you can see:
exhaust temperature;
temperature supplied by glycol;
glycol return temperature;
condensation;
temperature of the supplied heating water;
exhaust pressure;
water heater temperature;
temperature of the returning heating water.
Window 7
Window 8
Window 9
Window 10

19
Technical data of IGLU Aleut fixed capacity heat pumps
Units
5 kW
7 kW
9 kW
11 kW
13 kW
Brine/water used
Thermal power (B0/W35)1)
kW
5.24
7.25
9.22
10.95
13.07
Thermal power (B0/W45)1)
kW
4.89
6.85
8.67
9.98
12.30
COP (B0/W35)1)
-
4.37
4.42
4.45
4.52
4.54
COP (B0/W45)1)
-
3.37
3.42
3.47
3.41
3.47
SCOP (B0/W35)
-
5.55
5.66
5.72
5.86
5.77
SCOP (B0/W45)
-
4.14
4.22
4.26
4.37
4.3
Brine circuit
Rated flow (DT = 3K)2)
m3/h
1.50
2.0
2.50
3.00
3.50
Permissible external pressure drop2)
kPa
45
80
91
90
85
Maximum pressure
bar
4
Volume (internal)
l
5
Operating temperature
°C
from -10 to +20
Connection (Cu)
mm
28
Compressor
Type
Spiral “Scroll”
Mass of refrigerant R 407C3)
kg
1.20
1.30
1.35
1.40
1.50
Maximum pressure
bar
45
Heating system
Rated flow (DT = 7K)
m3/h
1.00
1.50
2.00
2.00
2.20
Min. flow temperature
°C
15
Max. flow temperature
°C
60
Max. permissible operating pressure
bar
4.0
Connection (Cu)
mm
28
Power network connection values
Electrical connections
400 V 3 N ~ 50 Hz
Inertial fuse (with electric heater 3 kW)
A
10/16/20
16/16/20
16/20/25
16/25/25
20/25/32
Compressor rated power (B0/W35)
kW
1.19
1.64
2.06
2.56
3.06
Max. current with inrush current limiter4)
A
4.10
5.20
6.80
8.23
10.10
Type of protection
IP
X1
General information
Permissible ambient temperatures
°C
from +10 to +35
Sound power level5)
dBA
42
Dimensions (width x depth x height)
mm
600 x 600 x 1100
Weight (without packaging)
kg
102
110
115
130
135
1) With internal pump according to EN 14511
2) With ethylene glycol
3) Greenhouse potential, GWP100 = 1774
4) WPS 6-1: Max. current without inrush current limiter
5) According to EN 3743-1

20
Technical data of IGLU® Aleut WT fixed capacity heat pump with
integrated water heater
Units
5 kW
7 kW
9 kW
11 kW
13 kW
16 kW
Brine/water used
Thermal power (B0/W35)1)
kW
5.24
7.25
9.22
10.95
13.07
15.45
Thermal power (B0/W45)1)
kW
4.89
6.85
8.67
9.98
12.30
14.75
COP (B0/W35)1)
-
4.37
4.42
4.45
4.52
4.54
4.46
COP (B0/W45)1)
-
3.37
3.42
3.47
3.41
3.47
3.52
SCOP (B0/W35)
-
5.55
5.66
5.72
5.86
5.77
5.77
SCOP (B0/W45)
-
4.14
4.22
4.26
4.37
4.3
4.3
Brine circuit
Rated flow (DT = 3K)2)
m3/h
1.50
2.0
2.50
3.00
3.50
4
Permissible external pressure drop2)
kPa
45
80
91
90
85
85
Maximum pressure
bar
4
Volume (internal)
l
5
6
Operating temperature
°C
from -10 to +20
Connection (Cu)
mm
28
Compressor
Type
“Scroll”
Mass of refrigerant R 407C3)
kg
1.20
1.30
1.35
1.40
1.50
1.50
Maximum pressure
bar
30
Heating system
Rated flow (DT = 7K)
m3/h
1.00
1.50
2.00
2.00
2.20
2.20
Min. flow temperature
°C
15
Max. flow temperature
°C
60
Max. permissible operating pressure
bar
4.0
Hot water tank volume
l
200
Capacity material
-
Stainless steel 1,4404
Connection (Cu)
mm
28
Power network connection values
Electrical connections
400 V 3 N ~ 50 Hz
Inertial fuse (with electric heater 3 kW/6
kW/9 kW)
A
10/16/20
16/16/20
16/20/25
16/25/25
20/25/32
20/25/32
Compressor rated power (B0/W35)
kW
1.19
1.64
2.06
2.56
3.06
3.46
Max. current with inrush current limiter4)
A
4.10
5.20
6.80
8.23
10.10
11.8
Type of protection
IP
X1
General information
Permissible ambient temperatures
°C
from +10 to +35
Sound power level5)
dBA
42
45
Dimensions (width x depth x height)
mm
700 x 700 x 1750
Weight (without packaging)
kg
187
195
200
215
220
230
1) With internal pump according to EN 14511
2) With ethylene glycol
3) Greenhouse potential, GWP100 = 1774
4) WPS 6-1: Max. current without inrush current limiter
5) According to EN 3743-1
Table of contents
Other iglu Heat Pump manuals
Popular Heat Pump manuals by other brands

York
York YAFT026 installation manual

Carrier
Carrier RHV090-120 installation instructions

Vaillant
Vaillant flexoTHERM exclusive VWF 57/4 230V Installation and maintenance instructions

CPA
CPA BLUEFIRE Series user manual

Daikin
Daikin ARQ installation manual

Gree
Gree Vita GWC09ATCXB-D3DNA3A/I Operation manual