Empire FAW55IPXLP-2 Quick start guide

Page 1
FAN TYPE VENTED
WALL FURNACE MODELS:
FAW55IPXLP-2FAW55IPXNAT-2
WARNING
FIRE OR EXPLOSION HAZARD
If the information in these instructions is
not followed exactly, a re or explosion
may result causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas
supplier, call the re department.
— Installation and service must be
performed by a qualied installer,
service agency or the gas supplier.
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
WARNING
If not installed, operated and maintained
in accordance with the manufacturer's
instructions, this product could expose you
to substances in fuel or from fuel combustion
which can cause death or serious illness.
INSTALLATION INSTRUCTIONS
AND OWNER’S MANUAL
UL FILE NO.
MH46706

45053-0-0523Page 2
TABLE OF CONTENTS
Introduction..................................................................................................................................3-4
Safety Information For Users Of Propane Gas .............................................................................. 5
Installation .................................................................................................................................6-10
Lighting Instructions ..................................................................................................................... 11
Service And Maintenance Suggestions...................................................................................12-13
Troubleshooting............................................................................................................................ 14
S8600H Troubleshooting Guide ..............................................................................................15-16
Venting ......................................................................................................................................... 17
Parts List ...................................................................................................................................... 18
Parts View .................................................................................................................................... 19
Master Parts Distributors.............................................................................................................. 20
How To Order Repair Parts .......................................................................................................... 20
Appliance Service History .......................................................................................................21-22
Warranty....................................................................................................................................... 23
SECTION PAGE

45053-0-0523 Page 3
INTRODUCTION
Introduction
Always consult your local BuildingDepartment regarding regulations,
codes or ordinances which apply to the installation of a vented
wall furnace.
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installermusthaveownerlloutandmailwarrantycardsupplied
with furnace.
3. Installer should show owner how to start and operate furnace.
WARNING
Any change to this furnace or its control can be dangerous.
This is a heating appliance and any panel, door or guard
removed for servicing an appliance must be replaced prior
to operating the appliance.
General Information
ThisseriesisdesigncertiedinaccordancewithAmericanNational
Standard / CSA Standard Z21.86 and CSA 2.32 by the Canadian
Standards Association, as a Fan Type Vented Wall Furnace and
must be installed according to these instructions.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
AllcorrespondenceshouldrefertocompleteModelNo.,SerialNo.
and type of gas.
ACCESSORIES
Part No. Description
SOR-1 Register,sideoutlet,xedregister
SOK-1 Sideoutlet,10”(254mm)maximumextension,
xedregister
ROK-1 RearOutlet,10”(254mm)maximumextension,
adjustable register
DV-651DB Vent enclosure, 14” (356mm) [for room up to 96
1/2” (245cm) in height]
DV-665DB Vent enclosure, 24” (610mm) [for rooms up to
106 1/2” (270.5cm) in height]
DV-666DB Vent enclosure, 36” (914mm) [for rooms up to
118 1/2” (301cm) in height]
DV648DBD 4”(102mm)Oval-to-Roundueadapterkit
CONVERSION KITS
Part Number Description Used On
682160 PropanetoNatural FAW55IPXLP-2
682269 NaturaltoPropane FAW55IPXNAT-2
NOTICE: Duringinitialringofthisunit,itspaintwillbakeoutand
smokewilloccur.Topreventtriggeringofsmokealarms,ventilate
the room in which the unit is installed.
Installation on Rugs and Tile
If this appliance is installed directly on carpeting, tile or other
combustiblematerialotherthanwoodooringtheapplianceshall
beinstalledonametalorwoodpanelextendingthefullwidthand
depth of the appliance.
Thebasereferredtoabovedoesnotmeanthere-proofbaseas
usedonwoodstoves.Theprotectionisforrugsthatareextremely
thickandlightcoloredtile.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed
so that all burners and burner ignition devices are located not less
than18”(457mm)abovetheoor.
Such equipment shall be located, or protected, so it is not subject
to physical damage by a moving vehicle.
Specications
Model FAW55IPX
BTU/HR (KW/H) 55,000 (16.1)
Height 82 3/8” (2092mm)
Width 16” (406mm)
Depth 11 1/2” (292mm)
Gas Inlet 1/2” (13mm) Pipe
Vent Collar 4” (102mm) Type B Oval
CFM 400
Well Head Gas Installations
Some natural gas utilities use “well head” gas. This may affect
the Btu output of the unit and promote sooting. Units shall not be
converted to use well head gas.

45053-0-0523Page 4
INTRODUCTION (CONT’D)
• Due to high temperatures the appliance should be located
out of trafc and away from furniture and draperies.
• Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
• Young children should be carefully supervised when they
are in the same room as the appliance.
• Clothing or other ammable material should not be placed
on or near the appliance.
• Any safety screen or guard removed for servicing
an appliance must be replaced prior to operating the
appliance.
• Keep burner and control compartment clean.
• Installation and repair should be done by a QUALIFIED
SERVICE PERSON. The appliance should be inspected
before use and at least annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials, etc. It
is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• DO NOT put anything around the furnace that will obstruct
the ow of combustion and ventilation air.
• DO keep the appliance area clear and free from combustible
material, gasoline and other ammable vapors and liquids.
• DO examine venting system periodically and replace
damaged parts.
• DO make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
• CAUTION: Pilot hole cover must be kept tightly closed
during operation.
• DO NOT use this heater if any part has been under water.
Immediately call a qualied service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
• This furnace must not be connected to a chimney ue
serving a separate solid-fuel burning appliance.
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANELS INSTALLED.
WhenanexistingCategory1heaterisremovedorreplaced,
the original venting system may no longer be sized to
properly vent the attached appliances. Instructions shall
also indicate effects of an improperly sized venting system
(formationofcondensate,leakage,spillage,etc.)andshall
specify the following test procedure:
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system
are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code, CSA B149.1 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deciencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close replace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do operate a summer
exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the ame of a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with National Fuel Gas Code, ANSI Z223.1/
NFPA 54 and/or Natural Gas and Propane Installation
Code, CSA B149.1.
9. After is has been determined that each appliance
connected
to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-red
burning appliance to their previous conditions of use.

45053-0-0523 Page 5
SAFETY INFORMATION FOR USERS OF PROPANE GAS
Propane is a ammable gas which can cause res and explo-
sions. In its natural state, propane is odorless and colorless.
You may not know all the following safety precautions which
can protect both you and your family from an accident. Read
them carefully now, then review them point by point with the
members of your household. Someday when there may not
be a minute to lose, everyone's safety will depend on knowing
exactly what to do. If, after reading the following information,
you feel you still need more information, please contact your
gas supplier.
PROPANE GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas
because of the odorant put in the Propane Gas. That’s your
signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Closeallgastankorcylindersupplyvalves.
• Propane Gas is heavier than air and may settle in low areas
such as basements. When you have reason to suspect a gas
leak,keepoutofbasementsandotherlowareas.Stayout
untilreghtersdeclarethemtobesafe.
• Use your neighbor's phone and call a trained Propane Gas
servicepersonandtheredepartment.Eventhoughyoumay
not continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, lettheservicemanandreghterscheckforescaped
gas. Have them air out the area before you return. Properly
trainedPropane Gas service peopleshould repair the leak,
thencheckandrelightthegasapplianceforyou.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odorofthechemicalputintothegas.Youmustndoutifyoucan
smelltheodorantinpropane.Smokingcandecreaseyourabilityto
smell. Being around an odor for a time can affect your sensitivity or
abilitytodetectthatodor.Sometimesotherodorsintheareamask
the gas odor. People may not smell the gas odor or their minds are
onsomethingelse.Thinkingaboutsmellingagasodorcanmake
it easier to smell.
The odorant in Propane Gas is colorless, and it can fade under some
circumstances.Forexample,ifthereisanundergroundleak,the
movementofthegasthroughsoilcanltertheodorant.Odorants
inPropaneGasalsoaresubjecttooxidation.Thisfadingcanoccur
ifthereisrustinsidethestoragetankorinirongaspipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will
takesomeoftheodorantoutofthegas,reducingitsodorintensity.
Propane Gas may stratify in a closed area, and the odor intensity
could vary at different levels. Since it is heavier than air, there may
be more odor at lower levels.Always be sensitive to the slightest gas
odor.Ifyoudetectanyodor,treatitasaseriousleak.Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of Propane Gas.Your local Propane
Gas Dealer can give you a "Scratch and Sniff" pamphlet. Use
ittondoutwhatthepropaneodorsmellslike.Ifyoususpect
thatyourPropaneGashasaweakorabnormalodor,callyour
Propane Gas Dealer.
• Ifyouarenotqualied,donotlightpilotlights,performservice,
ormakeadjustmentstoappliancesonthePropaneGassystem.
Ifyouarequalied,consciouslythinkabouttheodorofPropane
Gas prior to and while lighting pilot lights or performing service
ormakingadjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the Propane Gas odor. Do not try to
lightpilotlights,performservice,ormakeadjustmentsinan
area where the conditions are such that you may not detect
theodoriftherehasbeenaleakofPropaneGas.
• Odorfade,duetooxidationbyrustoradsorptiononwallsof
newcylindersandtanks,ispossible.Therefore,peopleshould
beparticularlyalertandcarefulwhennewtanksorcylinders
areplacedinservice.Odorfadecanoccurinnewtanks,or
reinstalledoldtanks,iftheyarelledandallowedtosettoo
longbeforerelling.Cylindersandtankswhichhavebeenout
of service for a time may develop internal rust which will cause
odorfade.Ifsuchconditionsaresuspectedtoexist,aperiodic
sniff test of the gas is advisable. If you have any question about
the gas odor, call your Propane Gas Dealer. Aperiodic sniff
test of the Propane Gas is a good safety measure under any
condition.
• If, at any time, you do not smell the Propane Gas odorant and
youthinkyoushould,assumeyouhavealeak.Thentakethe
same immediate action recommended above for the occasion
when you do detect the odorized Propane Gas.
• Ifyouexperienceacomplete"gasout,"(thecontainerisunder
novaporpressure),turnthetankvalveoffimmediately.Ifthe
container valve is left on, the container may draw in some air
throughopeningssuchaspilotlightorices.Ifthisoccurs,some
new internal rusting could occur. If the valve is left open, then
treatthecontainerasanewtank.Alwaysbesureyourcon-
tainer is under vapor pressure by turning it off at the container
beforeitgoescompletelyemptyorhavingitrelledbeforeitis
completely empty.

45053-0-0523Page 6
Ventilation and Combustion Air
Wall furnaces shall be installed in a location in which the facilities
for ventilation permit satisfactory combustion of gas and proper
venting under normal conditions. In buildings of conventional frame,
brick,orstoneconstructionwithouttightstormwindowsanddoors,
inltrationisnormallyadequatetoprovideairforcombustionand
draft hood dilution.
Whereappliancesareinstalledinconnedandunconnedspaces
within a building, the building being of unusually tight construction,
air for combustion and ventilation must be obtained directly from
outdoors or from such spaces that freely communicate with the
outdoors. Under these conditions, the conned and unconned
spaces shall be provided with two permanent openings, one near
the top of the enclosure and one near the bottom; each opening
shall have a free area of not less than one square inch (6,45cm2)
per 2,000 BTU hr. (.6KW/H) of total input.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performedonlybyaqualiedagency.Theterm“qualiedagency”
meansanyindividual,rm,corporationorcompanywhicheitherin
person or througha representative is engaged inand is responsiblefor
(a) the installation or replacement of gas piping or (b) the connection,
installation,repairorservicingofequipment,whoisexperiencedin
suchwork,familiarwithallprecautionsrequiredandhascomplied
with all the requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA
54,* Natural Gas and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc., 11
West 42nd St., New York, N.Y. 10036.
Clearances
1. In selecting a location for installation, it is necessary to provide
adequate accessibility clearances for servicing and proper
installation.
2. The FAW-55 can be attached to the wall or recessed into the
wall up to 4 inches (102mm) in depth.
3. The wall in which the furnace is recessed has (0) zero (0mm)
clearance to the furnace sides and top.
4. When using side discharge registers, SOR-1 or SOK-1, the
furnace cannot be recessed into the wall.
5. Clearance to sidewall or combustible material is 4 inches
(102mm).
6. Ceiling clearance is 7-1/2 inches (191mm).
7. Floor and rear wall clearance is (0) zero inches (0mm).
8. Clearance of 18 inches (457mm) is required to adjacent wall or
combustiblematerialwhenushmountedSOR-1,sideoutlet
register is used.
Before Installing Consider The Following Venting
1. A chimney for residential-type or low-heat gas utilization
equipment shall extend at least 3 feet (914mm) above the
highest point where it passes through a roof of a building and
at least 2 feet (610mm) higher than any portion of building
within a horizontal distance of 10 feet (3m).
2. Thisfurnacemustnotbeconnectedtoachimneyueserving
a separate solid-fuel burning appliance.
3. Uninsulated Single-Wall Metal Pipe shall not be used
outdoors in cold climates for venting gas utilization
equipment.
INSTALLATION
4. Attention! This Fan Type Vented Wall Furnace is equipped with
aventsafetyswitch.Intheeventofspillageofueproducts
due to improper venting the vent safety switch will open, which
results in the main burners to “shut off”.
Refer to Figure 1 and page 17 for additional information regarding
U.L. Listed gas vent equipment.
Installing Optional Side Outlets
Side outlet register, SOR-1 may be installed on one or both sides
of the furnace at the required clearances of 18 inches (457mm) to
adjacent wall or combustible material as shown in Figure 2.
1. Locate and cut the 5-1/2” (140mm) square opening inthe cabinet
sideusingthetemplatefromthekit,exposingtheinnerliner
knock-out.
2. Removetheknock-out.
3. Place the register on the 5-1/2” (140mm) opening with the
louversset for the desireddirectionandmarkthe mounting
holes using the register as a template.
4. Drill (2) 1/8” (3mm) diameter holes in cabinet side and fasten
theregisterinplacewith(2)#10x1”(25mm)screwsprovided.
Sideoutletkit,10”(254mm)bootassemblywithregister,SOK-1
for warm air discharge into an adjoining room may be installed on
either side of the furnace at the required clearance of 4 inches to
adjacent wall as shown in Figure 3A.
1. Locate and cut the 5-1/2” (140mm) square opening inthe cabinet
sideusingthetemplatefromthekit,exposingtheinnerliner
knock-out.
2. Removetheknock-out.
3. Usingtheinnerandouterbootsasholetemplates,markand
drill (8) 1/8” (3mm) diameter holes in the inner liner and cabinet
side.
4.
Using Figure 3A locate and cut a 6-3/4” (171mm) square opening
through walls.
5. Attach furnace to wall. (See Attaching Furnace to Wall).
6. Withfurnaceinplace,aftercheckingalignmentofsideoutlet
openinginwallandfurnace,placethe9-3/8”x9-3/8”(238mm
x238mm)sideoutletwallplateoverouterboot,passtheouter
boot through the wall and attach side outlet wall plate to furnace
sideofwallwith(2)#10x1”(25mm)screwsprovided.
7. Fastenouterboottothecabinetsidewith(4)#8x1/4”(6mm)
screws provided.
8. Positionandattachinnerboottoinnerlinerwith(4)#8x1/4”
(6mm) screws provided.
9. Locate the register with its louvers positioned for the desired
airdischargedirectionandmarkthemountingholesusingthe
register as a template.
10. Drill (2) 1/8” (3mm) diameter holes in the wall and fasten the
registerinplacewith(2)#10x1”(25mm)screwsprovided

45053-0-0523 Page 7
INSTALLATION (CONT’D)
VENTCENTERTOCOMBUSTIBLES
MINIMUMCLEARANCE1-9/16”(40mm)
REGISTER KIT #DV-637
REAR OUTLET
3” (76mm) TO CENTER OF
1/2” (13mm) INLET ELBOW
6-5/8” (168mm)
WALL TO VALVE INLET
3-3/4” (95mm) FLOOR TO
CONTROL VALVE INLET
FURNACE CLEARANCE TO
COMBUSTIBLES
4” (102mm) MINIMUM
KIT PART DV-608
SIDE OUTLET
TOPTO COMBUSTIBLES
7-1/2” (191mm)
MINIMUM CLEARANCE
4” (102mm) OVAL TYPE “B”
CONNECTION
VENT CENTER TO
COMBUSTIBLES MINIMUM
CLEARANCE 1-9/16” (40mm)
VENTENCLOSURE
DV-651 OR DV-665
OR DV-666
MINIMUM CLEARANCE
TO COMBUSTIBLES
18” (457mm)
REGISTER PART DV-603
Figure 2
(140mm)
(406mm)
(102mm)
(102mm)
(140mm)
(102mm)
3 1/4” (83mm)
11 ½”(292mm)
Figure 3 Figure 3A
Installing Optional Rear Outlet
Rearoutletkit,10”(254mm)bootassemblywithregister,ROK-1
for warm air discharge into an adjoining room.
Attention: Before furnace is attached to the wall, the wall opening
for the rear outlet must be cut, in addition to removal of the outer
andinnercasingknockoutsonfurnace.
1. The wall opening measurements for the rear outlet are the
following.
A. Fromoortobottomofwallopeningis14-3/4”(375mm).
B. From bottom of wall opening to top of wall opening is 8-1/2”
(216mm) .
C. Wall opening width is 12-1/8” (308mm).
2. Removeoutercasingknockoutfromoutercasingback.
3. Removeinnercasingknockoutfrominnercasing.
4. Attach furnace to wall (see Attaching Furnace to Wall).
5. Alignclearanceholeson8”x12”(203mmx305mm)bootwith
screwholesonoutercasingbackandmarkboottobeush
with wall surface. Remove boot and cut to proper length.
6. Attach8”x12”(203mmx305mm)boottooutercasingback
with(6)#10x1/2”(13mm)screwsprovided.
7. Alignclearanceholeson6”x10”(152mmx254mm)ductwith
screwholesoninnercasingandmarkducttobe2-1/4”(57mm)
shorterthan8”x12”(203mmx305mm)boot.Removeduct
and cut to proper length.
8. Attach6”x10”(152mmx254mm)ducttoinnercasingwith
(6)#10x1/2”(13mm)screwsprovided.
9. Insertrearregisterinto8”x12”(203mmx305mm)boot.Attach
rearregistertowallwith(2)#10x1”(25mm)screwsprovided.
ALL CONNECTIONS MUST BE MECHANICALLY
MADE AND LISTED CLERANCES MAINTAINED
*PARTS LISTED ARE TO BE
PURCHASED
LOCALLY
SPACER STRAP*
BASE PLATE*
MOUNTING HOLE
2
PIECE VENT ENCLOSURE
CUT
TO THE PROPER LENGTH
BASE PLATE
GASKET
Figure 1
SIDE OUTLET
KIT PART SOK-1
VENTCLOSURE
DV651DB, DV665DB,
DV666DB
REGISTER PART SOR-1
REAR OUTLET
REGISTER KIT ROK-1
* 3-1/4" (83mm)
* 11-1/2" (292mm)
* (Add 1-1/2" if using DV648DBD)

45053-0-0523Page 8
Locating Furnace On Wall
The furnace is to be located on a wall. The furnace is 16 inches
(406mm) in width and normal 16 inches (406mm) on center studs
will not allow the furnace to be recessed into the wall unless a stud
is repositioned.
A template is provided in furnace carton for locating gas line
connection. Also, refer to Figure 2 for positioning the furnace on
wall and for locating gas line connection.
Locating Gas Supply
Thegaslinecanenterthefurnaceeitherthroughtheoororwall.
The gas line opening should be made at this time. Location of the
openingwillbedeterminedbythepositionofoorjoistsandthe
valve and union used for servicing.
Locating Electric Supply
A7/8”(22mm)diameterknockoutisprovidedatthebottomofthe
left and right side panels. A three-prong (grounding) plug assembly
is located within the control compartment (bottom) of the furnace.
Pleaseremove7/8”(22mm)knockoutfromappropriatesidepanel
when routing plug assembly to an electrical outlet.
Installation of Three-prong (Grounding) Plug Assembly
1. Disconnect nylon cap on 3’ (914mm) plug assembly from nylon
plug on wiring harness. Remove 3’ (914mm) plug assembly from
control compartment (bottom) of the furnace.
2. Remove7/8”(22mm)knockoutfromappropriatesidepanel.
3. Insert nylon cap on 3’ (914mm) plug assembly into the 7/8”
(22mm) hole in the side panel.
4. Connect nylon cap on 3’ (914mm) plug assembly to nylon plug
on the wiring harness.
5. Place 7/8” (22mm) strain relief bushing around the cord of the 3’
(914mm) plug assembly. Insert 7/8” (22mm) strain relief bushing
into the 7/8” (22mm) hole in the side panel.
Attention! The 7/8” (22mm) strain relief bushing is located within
the same yellow envelope as the Installation Instructions and
Owner’s Manual.
Attaching Furnace to Wall
When attaching furnace to the wall remove that portion of baseboard
and molding on the wall which is behind the furnace. Attach furnace
to wall, at the outer casing top, with (2) toggle bolts provided and
tooor,attheoutercasingbottom,with(2)#10x11/2”(38mm)
screws provided.
Attention! The screw holes on the outer casing bottom are off-set
abovethe oor approximately3/8”(9.5mm).Do not over-tighten
screws and distort the off-set on the outer casing bottom. Distortion
of the outer casing bottom will not allow the lower front panel to be
attached to the furnace.
Gas Supply
Checkalllocalcodesforrequirements,especiallyforthesizeand
typeofgassupplylinerequired. OnNaturalGaslineslessthan
15’ (4.5m) long, use 1/2” (13mm) pipe; on longer runs, use 3/4”
(19mm) iron pipe or equal. On Propane Gas lines please consult
Propane Gas supplier.
Installing a New Main Gas Shut-Off Valve
Each appliance should have its own manual gas shut-off valve.
A manual main gas shut-off valve should be located in the vicinity
oftheunit.Wherenoneexists,orwhereitssizeorlocationisnot
adequate, contact your local authorized installer for installation or
relocation.
Compounds used on threaded joints of gas piping shall be resistant
totheactionofliqueedpetroleumgases.Thegaslinesmustbe
checkedforleaksbytheinstaller.Thisshouldbedonewithasoap
solutionwatchingforbubblesonallexposedconnections,andif
unexposed,apressuretestshouldbemade.
Never use an exposed ame to check for leaks. Appliance
must be disconnected from piping at inlet of control valve and
pipe capped or plugged for pressure test. Never pressure test
with appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required by
theNationalFuelGasCodethatadriplinebeinstallednearthegas
inlet. This should consist of a vertical length of pipe tee connected
into the gas line that is capped on the bottom in which condensation
and foreign particles may collect.
(3mm)
(3mm)
Figure 4
Method of Installing a Tee Fitting Sediment Trap
The use of the following gas connectors is recommended:
— ANSZ21.24ApplianceConnectorsofCorrugatedMetalTubing
and Fittings
— ANSZ21.45AssembledFlexibleApplianceConnectorsofOther
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction.
Pressure Testing of the Gas Supply System
1. Tochecktheinletpressuretothegasvalve,a1/8”(3mm)N.P.T.
plugged tapping, accessible for test gauge connection, must
be placed immediately upstream of the gas supply connection
to the appliance.
2. The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during any
pressuretestingofthatsystemattestpressuresinexcessof
1/2psig(3.5kPa).
3. The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressuresequaltoorlessthan1/2psig(3.5kPa).
Attention! If one of the above procedures results in pressures in
excessof1/2psig(14”w.c.)(3.5kPa)ontheappliancegasvalve,
it will result in a hazardous condition.
INSTALLATION (CONT’D)

45053-0-0523 Page 9
Figure 6
Electrode and pilot must be kept clean. Clean through pilot
access hole with a small brush (toothbrush) and water.
Proper Main Burner Flame
The correct ame will be a short blue inner ame with a much
largerlightblueouter ame.Themainburner(Figure 7) shows
theapproximateheightofeachpartoftheameforeachgas.The
burnerdoesnothaveaprimaryairadjustment.Theamewillbe
correctifthefactory-setpressureandoriceopeningareused.After
thefurnacehasbeenoperating,theburnerportsmaybeblocked
by foreign matter carried in by combustion air. Therefore, cleaning
oftheburnermaybeneededforproperame.
To clean burner port disconnect the gas supply to the valve, and
remove the eightscrews fastening theburner door. After removing the
burner door from the combustion chamber, remove rear burner, pilot
burner and front burner. With front and rear burners removed from
furnace, force water into the ribbon ports and dry with air pressure.
4”
(102mm) NAT
6”
(152mm) LP
1 ½”(38mm) NAT
1/4” (6mm) LP
Figure 7
Replacing Fan and Oiling the Motor
The fan motorshould be cleanedand oiled once eachheating season.
To reach the motor, withdraw the metal shroud surrounding the fan
blade by removing the screws on each side. Oil holes are located
on the top at each end of the motor. Use a few drops of #10 motor
oil. To clean the motor, blow air through its ventilation openings
with a vacuum cleaner or low pressure air source.
Iffanmotorisreplaced,thesiliconerubbergaskets,seepage18,
IndexNo.5,PartNo.M147shouldalsobereplaced.Thegaskets
mustbestretchedtotthemotorboltsintothegasketholesand
thenthemotorandgasketsinstalledonthemotormountingbars.
Checking Manifold Pressure
Both Propane and Natural Gas valves have a built-in pressure
regulatorinthegasvalve.NaturalGasmodelswillhaveamanifold
pressureofapproximately3.5”w.c.(.871kPa)atthevalveoutlet
with the inlet pressure to the valve from a minimum of 5.0” w.c.
(1.24kPa) for the purpose of input adjustment to a maximum of
10.5”w.c.(2.615kPa)Propane Gasmodelswill haveamanifold
pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 11.0” w.c.
(2.739kPa)forthepurposeofinputadjustmenttoamaximumof
13.0”w.c.(3.237kPa).
A 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge
connection, is located on the outlet side of the gas control.
Thebuilt-in regulator comes onat approximately 1/4th pressure
and full on in 10 seconds.
Figure 5
High Altitudes
For altitudes/elevations above 2,000feet (610m), input ratings should
be reduced at the rate of 4 percent for each 1,000 feet (305m) above
sealevel. Canadian High Altitudes for locations havingan elevation
above mean sea level between 2,000 feet (610m) and 4,500 feet
(1370m), the manifold pressure is to be decreased from 3.5” w.c.
(.871kPa)to2.8”w.c.(.697kPa)forNaturalGasandfrom10.0”w.c.
(2.49kPa)to8.0”w.c.(1.992kPa)forPropaneGas.
Proper Pilot Flame
Thepilotame(Figure 6)goingtothesparkmustbelargeenough
tocompletelycoverthesparkingarea.Withtheproperame,only
2or3sparkswilloccur.Moresparksindicateasmallpilotame
andnoignitionwithsparkstoppingafterapproximately90seconds
generallymeansnotenoughame.
Toadjustpilotameremovethepilotcoverscrewonthecontrol
valve (Figure 5),andturntheadjustmentscrewclockwisetoreduce
ame.Replacepilotcoverscrewtoeliminategasleakage.
Thepilotamewillappearlarge.Abluenearlyhorizontalameis
proper.Thesparkgapmustbe1/8”(3mm).Alargergapcanresult
inthesparkoccurringsomeotherplace.Thepilotameandthe
sparkgaparefactorycheckedandtested.
Afteruse,cleaningmayberequiredfortheproperame.
Safety Lockout
S8600H module provides 100 percent shutoff, or safety
lockout. If the pilot fails to light within 90 seconds, the
control system will shut down. The control system must be
reset by turning off the power to the module for one minute.
INSTALLATION (CONT’D)
MANUAL GAS SHUT-OFF KNOB

45053-0-0523Page 10
Vent Safety Shut-Off System
This appliance must be properly connected to a venting system.
This appliance is equipped with a vent safety shutoff system.
Warning: Operation of this wall furnace when not connected
to a properly installed and maintained venting system or
tampering with the vent safety shutoff system can result in
carbon monoxide (CO) poisoning and possible death.
This furnace is equipped with a manual reset vent safety switch.
Themanualresetventsafetyswitchwillcausegasowtothemain
burnersto“shutoff”duetoimproperventingorablockedue.
To reset the manual reset vent safety switch:
1. Remove upper front panel.
2. Depress red manual reset button. The manual reset vent
safety switch is located on the draft diverter.
3. Replace upper front panel.
If the manual reset vent safety switch continues to “shut off” the
gasowtothemainburnersaqualied servicepersonmustbe
contactedtoinspectforimproperventing,blockageintheventpipe
or the manual reset vent safety switch for being defective.
Wiring
The appliance, when installed, must be electrically grounded in
accordance with local codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70 or Canadian Electrical
Code, CSA C22.1,ifanexternalelectricalsourceisutilized.This
appliance is equipped with a three-prong [grounding] plug for
your protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle. Do
not cut or remove the grounding prong from this plug. For an
ungrounded receptacle, an adapter, which has two prongs and a
wire for grounding, can be purchased, plugged into the ungrounded
receptacle and its wire connected to the receptacle mounting screw.
With this wire completing the ground, the appliance cord plug can
be plugged into the adapter and be electrically grounded. A 7/8”
(22mm)holeisprovidedinthejunctionboxforusewithaconduit
connector if local codes require this type of protection.
To Conserve Gas: Turn off pilot when heater is not in use.
Insulated Vent Enclosure
Ventedwallfurnacesinstalledinbuildingswithatroofscanhave
poor venting. The cold vent pipe will have a delay in proper venting
and cause the wall furnace to shut “OFF” by the vent safety switch.
Topreventdelayedventingaswellascondensationofueproducts
an insulated vent enclosure is recommended.
Use type B vent pipe and maintain at least a one inch (25mm)
clearance to combustibles.
Use metal thimble to protect vent pipe as it passes through
combustibles.
Installing the
ON/OFF Device
ToinstallanON/OFF
device (such as a
wall switch, remote,
toggle switch, or
thermostat), remove
the wire nut from the
two wires from the
valve. Run additional
wire from the valve
wirestotheON/
OFF device. Install
theON/OFFdevice
in the same room as
the furnace following
the installation
instructions supplied
with it. In the absence
of instructions, install
theON/OFFdevice
4 to 5 feet above the
ooronaninterior
wall not affected
by another heating
source (i.e. stove or
water heater) or the
temperature of an
adjoining room.
INSTALLATION (CONT’D)
Figure 9 Figure 10
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THIS UNIT MUST BE REPLACED, IT MUST
BE REPLACED WITH 150°C THERMOPLASTIC
4/64 THICK OR ITS EQUIVALENT.
120V. 60Hz. LESS THAN 3 AMPS
S´IL YAUN FIL ORIGINAL FOURNI AVEC
L´APPAREIL QUI DIOT ÊTRE REMPLACÉ. IL DOIT
ÊTRE REMPLACÉ AVEC UN FIL
THERMOPLASTIQUE 150°C.
120V. 60Hz. MOINS DE 3 AMPS.
—————— ———————————————————————————————————————————————
WHITE (BLANC)
LOW VOLTAGE (BAS VOLTAGE)
120 VOLTS
120 VOLTS
SCHEMATIC WIRING DIAGRAM
——————————————————————————————
SCHÉMA ÉINSTALLATION LECTRIQUE
JUNCTION BOX
—— —— ——— —————————————— ——
BOÎTE DE JONCTION
LIMIT CONTROL
——— — ——————————————— —
CONTROL DE
TOLERANCE
AUTO FAN
——— —— ——————————— —
VENTILATE
AUTO
TRANSFORMER
——— —— —————————————————— —
TRANSFORMATEUR
SPT-3 CORDSET
——— —— ——————————————— —
CORDON SPT-3
BLACK (NOIR)
LADDER WIRING DIAGRAM
——————————————————————————
DIAGRAMME À L´ÉCHELLE
D´INSTALLATION ÉLECTRIQUE
YELLOW
——— —————————
JAUNE
WHITE
——— —————————
BLANC
BLACK
——— —————————
NOIR
RED
—
ROUGE
WHT
—
BLANC
TRANSFORMER
——— —— —————————————————— —
TRANSFORMATEUR
24 VOLTS
MOTOR
————— —————
MOTEUR
AUTO FAN
——— —— ——————————— —
VENTILATEUR
AUTO
MOTOR
————— —————
MOTEUR
VENT SAFETY
——— — ——————————————— —
SÛERTÉ DE
L’ÉVENT
BRN/Brun
WHT/Blanc
RED/Rouge
GRN/Vert
MV
MV/PV
PV
GRND
GAS VALV E
——— — ——————————————— —
VALVE DE GAZ
MODULE
VENT SAFETY
——— — ——————————————— —
SÛERTÉ DE
L’ÉVENT
GAS VALV E
——— — ——————————————— —
VALVE DE GAZ
BRN/Brun
MODULE
WHT/Blanc
RED/Rouge
GRN/Vert
MV
MV/PV
PV
MV
MV/PV
PV
GRND
24V
24V
LIMIT CONTROL
——— — ——————————————— —
CONTROL DE
TOLERANCE
ON/OFF DEVICE
——— — ——————————————— —
ON/OFF
PÉRIPHÉRIQUES
WIRE
NUT
————————————— —
FILS
TORSADÉS
WIRE NUT
—————————————---------------- —
FILS TORSADÉS
ON/OFF DEVICE
——— — ——————————————— —
ON/OFF
PÉRIPHÉRIQUES
(3m)
(.6m)
(3m)
More than 10”
Figure 8

45053-0-0523 Page 11
FOR YOUR SAFETY READ BEFORE OPERATING
A. This appliance is equipped with an ignition device which
automatically lights the pilot.
Do not try to light the pilot by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don’t try to repair it; call a qualied service
technician. Force or attempted repair may result in a re
or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
1. STOP! Read the safety information above.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot
by hand.
4. Remove control access panel (lower front panel).
5. Turn gas control knob clockwise to “OFF.”
6. Wait ten (10) minutes to clear out any gas. Then smell
for gas, including near the oor. If you smell gas, STOP!
Follow “B” in the safety information above. If you don’t
smell gas, go to the next step.
7. Turn gas control knob counterclockwise to “ON”.
8. Replace control access panel (lower front panel).
9. Turn on all electric power to the appliance.
10. If the appliance will not operate, follow the instructions
“TO TURN OFF GAS TO APPLIANCE” and call your ser-
vice technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
OPERATING INSTRUCTIONS
1. Turn off all electric power to the appliance if service is to
be performed .
2. Remove control access panel (lower front panel).
3. Turn gas control knob clockwise to “OFF.” Do
not force.
4. Replace control access panel (lower front panel).
LIGHTING INSTRUCTIONS
WARNING
If you do not follow these instructions exactly, a re or explosion may result causing property damage,
personal injury or loss of life.

45053-0-0523Page 12
CALL SERVICEMAN
SERVICE & MAINTENANCE SUGGESTIONS
GENERAL: Allfurnaceshavebeenre-testedtocheckforproper
operation. This includes, main burner ame, pilot ame, fan
operation, fan control, limit control and automatic valve operation.
If the furnace fails to function on initial installation, it is advisable to
re-checkthefollowing:
1. 115 volts to the junction box.
2. Inlet gas pressure.
3. The 24 volt system.
4. Type of gas being used and that shown on the rating label.
The Service Department at Empire Comfort Systems, Inc. may be
contacted to assist in servicing furnace.
Servicing the Pilot and Main Burners, Pilot Orice, and Main
Burner Orices: Disconnect the gas supply at the inlet to the
control valve. Then remove the burner door to which the above
components are attached.
Servicing The Fan Motor: The upper front panel, the shroud
surrounding the fan blade and fan blade must be removed. See
“Oiling the Motor” paragraph on page 7.
S8600H INTERMITTENT IGNITION MODULE SPECIFICATIONS
Lockouttimingis90seconds.Ignitiontimingisuntilpilotlightsor
lockoutoccurs.
Moduleshutsdownandcutspowertogascontrolonamefailure.
Gascontrolclosestoprovide100percentlockoutonamefailure.
Manual reset required.
ELECTRICALRATINGS:
Voltage and frequency: 20.5 to 28.5V (24V nom.) 60 Hz.
Current rating: 0.2 A.
Valve contact ratings (at 24 Vac):
Run Inrush
Pilot 1.0 A 10.0 A
Main 1.0 A 10.0 A
SPARKGENERATOROUTPUT:13kVpeakat25pfload.
ANTICIPATORSETTING:0.2Apluspilotvalveratingplusmain
valve rating.
COMPATIBILITY: Standard models compatible with all open-close
switch type 24 Vac capable of supplying rated voltage and current
to the module.
AMBIENTTEMPERATURE RATING: Minus 40 F to plus 175 F
(minus 40 C to plus 79 C).
RELATIVEHUMIDITYRATING:5to90percentRHat95F.
FLAMEFAILURERESPONSETIME:0.8secondsat1.0uAame
current.
FLAMECURRENT:1uA,min.
CHECKOUT
Checkoutthegascontrolsystem:
1. At initial installation of the appliance.
2. As part of regular maintenance procedures.
3. Astherststepintroubleshooting.
4. Anytimeworkisdoneonthesystem.
STEP 1: Perform Visual Inspection.
A. Withpoweroff,makesureallwiringconnectionsarecleanand
tight.
B. Turn on power to appliance and ignition module.
C. Open manual shut-off valves in the gas line to the appliance.
D. Dogasleaktestaheadofgascontrolifpipinghasbeendisturbed.
GAS LEAK TEST: Paint pipe joints with rich soap and water
solution.Bubblesindicategasleak.Tightenjointstostopleak.
STEP 2: Review Normal Operating Sequence and Module
Specications.
STEP 3: Reset the Module.
A. Turn the control valve to “OFF”.
B. Wait one minute.
As you do Steps 4 and 5, watch for points where operation
deviates from normal. Refer to Troubleshooting Chart to correct
problem.
STEP4:CheckSafetyLockoutOperation.
A. Turn gas supply off.
B. Watchforsparkatpilotburner.
C. Time length of spark operation. Maximum spark time is 90
seconds.
D. Openmanualgasshut-offvalveandmakesurenogasisowing
to pilot or main burner.
E. Set thermostat below room temperature and wait one minute
before continuing.
STEP5:CheckNormalOperation.
A. Turn the control valve to call for heat.
B. Make sure pilot lights smoothly when gas reaches the pilot
burner.
C. Makesuremainburnerlightssmoothlywithoutashback.Make
sureburneroperatessmoothlywithoutoatingorlifting.
D. Ifgaslinehasbeendisturbed,completegasleaktest.
GAS LEAK TEST: Paintgascontrolgasketedgesandallpipe
connections downstream of gas control, including pilot tubing
connections, with rich soap and watersolution. Bubbles indicate
gasleaks.Tightenjointsandscrewsorreplacecomponentto
stopgasleak.
E. Turnthe control valveoff.Make suremain burner and pilot
amesgoout.
OPERATION
Module operation can be conveniently divided into two phases for
S8600H. The phases are trial for ignition and main burner operation.
TRIAL FOR IGNITION
Pilot Ignition
Following call for heat (system start on S8600H), the module
energizestherstmainvalveoperator.Therstmainvalveopens,
whichallowsgastoowtothepilotburner.Atthesametime,the
electronicsparkgeneratorinthemoduleproducesa13,000volt
sparkpulseoutput(at25pfload).Thevoltagegeneratesaspark
at the igniter-sensor that lights the pilot.

45053-0-0523 Page 13
Ifthepilotdoesnotlight,orthepilotamecurrentisnotatleast1.0
uA and steady, the module will not energize the second main valve
and the main burner will not light.
Safety Lockout
S8600H provides 100 percent shutoff, or safety lockout.A timer
startstimingthemomentthetrialforignitionstarts.Ignitionspark
continues only until the timed trial for ignition period ends. Then
the module goes into safety lockout. Lockout de-energizes the
rstmainvalveoperatorandclosestherstmainvalveinthegas
control,stoppingpilotgasow.Thecontrolsystemmustbereset
by turning the valve off for one minute or by turning off power to the
module for one minute.
Main Burner Operation
When the pilot ame is established, a ame rectication circuit
iscompletedbetweenthesensorandburnerground.Theame
sensingcircuitinthemoduledetectstheamecurrent,shutsoff
thesparkgeneratorandenergizesthesecondmainvalveoperator.
Thesecondmainvalveopensandgasowstothemainburner,
whereitisignitedbythepilotburner.Theamecurrentalsoholds
thesafetylockouttimerinthereset(normal)operatingcondition.
When the call for heat ends, both main valve operators are de-
energized, and both main valves in the gas control close.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
SERVICE & MAINTENANCE SUGGESTIONS
Spark Generator Powered
First Valve (Pilot)
Operator Opens
Pilot burner lights.
Module senses flame current.
PILOT BURNER OPERATION
MODULE
S8600H
* Lockout timing is stamped on module.
RESPONSE
After 90 seconds*pilot valve
closes, spark stops.
OR
IF FLAME CURRENT SENSED
Spark generator off
Second valve operator
(Main) opens.
MAIN BURNER OPERATION
Module monitors pilot
flame current.
THERMOSTAT SATISFIED
Valves close. Pilot and
main burners are off.
START
STAGE 1
Trial for Ignition
STAGE 2
Main Burner
Operation
END
S8600H NORMAL OPERATING SEQUENCE
Pilot burner does not light
Thermostat, Wall Switch,
Remote, Etc. Calls for Heat
POWER INTERRUPTION
System shuts off. Restarts when
power is restored.
PILOT FLAME FAILURE
Second main operator closes.
Module starts trial for ignition.
ON/OFFDEVICESATISFIED
Valves close. Pilot and main
burners are off.
Wall Switch, Remote, Etc.
Calls for Heat

45053-0-0523Page 14
Important
1. The following service procedures are provided as a general
guide.
2. Meter readings between gas control and ignition module must
betakenwithinthetrialforignitionperiod.Oncetheignition
modulelocksout,thesystemmustberesetbyturningvalve
off for at least one minute before continuing.
3. Ifanycomponentdoesnotfunctionproperly,makesureitis
correctly installed and wired before replacing it.
4. The ignition module cannot be repaired. If it malfunctions, it
must be replaced.
5. Onlytrained,experiencedservicetechniciansshouldservice
intermittent pilot systems.
Perform the CHECKOUT steps on page 10 as the rst step in
troubleshooting. Then check TROUBLESHOOTING GUIDE to
pinpoint the cause of the problem. If troubleshooting indicates an
ignition problem, see Ignition System Checks below to isolate
and correct the problem.
Following troubleshooting, perform the CHECKOUT procedure
(page 10 ) again to be sure system is operating normally.
Ignition System Checks
Step1:Checkignitioncable.
Makesure:
A. Ignition cable does not touch any metal surfaces.
B. Ignition cable is no more than 36 inches (914mm) long.
C. Connections to the ignition module and to the igniter-sensor
are clean and tight.
D. Ignition cable provides good electrical continuity.
Step2:Checkignitionsystemgrounding.
Nuisance shutdowns are often caused by a poor or erratic
ground.
A. Acommonground,usuallysuppliedbythepilotburnerbracket,
is required for the module and the pilot burner/igniter sensor.
• Check for good metal-to-metal contact between the pilot
burnerbracketandthemainburner.
• CheckthegroundleadfromGND(BURNER)terminalonthe
moduletothepilotburner.Makesureconnectionsareclean
and tight. If the wire is damaged or deteriorated, replace it
with No. 14-18 gauge, moisture-resistant, thermoplastic
insulated wire with 105 C (221 F) minimum rating.
• Ifamerodorbracketarebentoutofposition,restoreto
correct position.
• Replacepilotburner/ignitersensorifinsulatoriscracked.
Step3: Checksparkignitioncircuit.You will need a short jumper
wire made from ignition cable or other heavily insulated
wire.
A. Close the manual gas valve.
B. Disconnect the ignition cable at the SPARK terminal on the
module.
WARNING
When performing the following steps, do not touch stripped
end of jumper or SPARK terminal. The ignition circuit
generates 13,000 volts at 25 pf load and electrical shock
can result.
C.Energize the module and immediately touch one end of the jumper
rmlytotheGNDterminalonthemodule.Movethefreeend
ofthejumperslowlytowardtheSPARKterminaluntilaspark
is established.
D. Pull the jumper slowly away from the terminal and note the
lengthofthegapwhensparkingstops.Checktablebelow.
ARC LENGTH ACTION
Noarcorarclessthan1/8
inch (3mm).
Arc 1/8 inch (3mm) or longer.
Checkexternalfuse,if
provided.
Verify power at module input
terminal.
Replace module if fuse and
powerokay.
Voltageoutputisokay.
Step4: Checkpilotamecurrent.
A. Turn off furnace.
B. Disconnect main valve wire from the TH or MV terminal on the
gas control.
C. Disconnect ground wire from GND (BURNER) terminal at
module.
D. Connect a meter (dc microamp scale) in series with the ground
lead.
• DisconnectgroundleadfromGNDterminalonignitionmodule.
• Connecttheblack(negative)meterleadtotheignitionmodule
GND(BURNER)terminal.
• Connect the red (positive) meter lead to the free end of the
ground lead.
E. Turnvalveontocallforheat.Thesparkwilllightthepilotbut
the main burner will not light because the main valve actuator
is disconnected.
F. Readthemeter.Theamesensorcurrentmustbesteadyand
at least 1.0 uA.
G. If the reading is less than the minimum or unsteady,
• Make sure pilot ame envelopes 3/8 (9.5mm)to 1/2 inch
(13mm)oftheamerod.
• If necessary, adjust pilot flame by turning the pilot
adjustmentscrewonthegascontrolclockwisetodecrease
or counterclockwise to increase pilot ame. Following
adjustment, always replace pilot adjustment cover screw
andtightenrmlytoassurepropergascontroloperation.
• Checkforcrackedceramicinsulator,whichcancauseshort
to ground, and replace igniter-sensor if necessary.
• Makesureelectricalconnectionsarecleanandtight.Replace
damagedwirewithmoisture-resistantNo.18wireratedfor
continuous duty up to 105 C (221 F).
H. Remove meter and reconnect all wires. Return system to
normal operation before leaving job.
TROUBLESHOOTING

45053-0-0523 Page 15
S8600H TROUBLESHOOTING GUIDE
•Checklinevoltagepower,lowvoltagetransformer,limitcontroller,andwriting.
•Also,checkairprovingswitchoncombustionairblowersystem(ifused)andthattheendswitch(ifused)ismade.

GREEN LED STATUS CODES
Green LED
Flash Code
(X + Y)a
Indicates Next System Action Recommended Service Action
OFF No“CallforHeat” Notapplicable None
Flash Fast Startup-Flame sense calibration Notapplicable None
Heart Beat Normaloperation Notapplicable None
3
Recycle
- Flame failed during run
Initiate new trial for ignition. Flash code
will remain through the ignition trial until
ameisproved.
If system fails to light on next trial for
ignition, check gas supply, pilot burner,
ame sense wiring, contamination of
amerod,burnergroundconnection.
4
Flame sensed out of sequence If situation self corrects within 10 sec-
onds, control returns to normal se-
quence. If ame out of sequence re-
mains longer than 10 seconds, control
goes to Flash code 6 + 4 (see below).
Checkforpilotame.Replacegasvalve
if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats, re-
place control.
7
Flamesenseleakagetoground Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.
Check ame sense lead wire for dam-
ageorshorting.Checkthatamerodis
in proper position.
Check ame rod ceramic for cracks,
damageortracking.
8
Low secondary voltage supply -
below 15.5 Vac)
Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.
ChecktransformerandAClineforprop-
er input voltage to the control. Check
with full system load on the transformer.
6 + 2
Failed trial for ignition resulting in
lockout
Remaininlockoutuntil“CallforHeat”is
cycled.
Check gas supply, pilot burner, spark
andame sense wiring, amerodcon-
taminated or out of position, burner
ground connection.
6 + 3
Morethan5amefailuresduring
run on the same “Call for Heat” re-
sultinginlockout
Remaininlockoutuntil“CallforHeat”is
cycled.
Check gas supply, pilot burner, ame
sense wiring, contamination of ame
rod, burner ground connection.
6 + 4
Flame sensed out of sequence -
longer than 10 seconds
Control waits until ame is no longer
sensed and then goes to soft lockout.
Flash code continues. Control auto re-
setsfromsoftlockoutafteronehour.
Checkforpilotame.Replacegasvalve
if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats, re-
place control.
ON Softlockoutduetoerrordetected
duringselfchecksequences
Controlautoresetsfromsoftlockoutaf-
ter one hour.
Reset by cycling “Call for Heat.” If error
repeats, replace the control.
aFlash Code Descriptions:
- FlashFast:Rapidblinking
- Heartbeat: Constant 1/2 second bright 1/2 second dim cycles
- AsingleashcodenumbersigniesthattheLEDashesXtimesat2Hz,remainsofffortwoseconds,andthenrepeatsthe
sequence.
- X+YashcodessignifythattheLEDashesXtimesat2Hz,remainsofffortwoseconds,ashesYtimesat2Hz,remainsoff
for three seconds, and then repeats the sequence.
45053-0-0523Page 16
S8600H TROUBLESHOOTING GUIDE

45053-0-0523 Page 17
ModelNo.FAW-55maybeventedasshown.Theventcapmust
beatleast12feet(3.7m)abovetheoor.Clearancetocombustible
constructionisheldbythexedspacersat1inch(25mm)withB-1
vent pipe. Installation must conform to local codes.
A. 4” (102mm) Round (all parts purchase locally except item 2)
1. Type B-1 round pipe
2. PartNo.DV-648,4”(102mm)oval-to-roundueadapterkit
(see accessories)
3. Single story type B-1 gas vents require a baseplate and one
pair of ceiling plate spacers.
4. Multi-story type B-1 gas vents require a baseplate, one pair
ofceilingplatespacersattherstoorceilingandonepair
ofrestopspacersateachsuccessiveceilinglevel.
B. 4” (102mm) Oval (all parts purchase locally)
1. Type B-1 oval pipe
2. Single story type B-1 gas vents require a baseplate and one
pair of ceiling plate spacers.
3. Multi-story type B-1 gas vents require a baseplate, one pair
ofceilingplatespacersattherstoorceilingandonepair
ofrestopspacersateachsuccessiveceilinglevel.
C. 4” (102mm) Oval In-The-Wall (all parts purchase locally)
1. Type B-1 oval pipe
2. Type B-1 oval elbows
3. Single story type B-1 gas vents require a baseplate and one
pair of ceiling plate spacers.
4. Multi-story type B-1 gas vents require a baseplate, one pair
ofceilingplatespacersattherstoorceilingandonepair
ofrestopspacersateachsuccessiveceilinglevel.
Stud space around gas vents must be free of obstructions and
building paper.
Use U.L. listed gas vent equipment when installing the FAW-55. For
vent pipe running through walls, roof, and within one inch (25mm)
of combustible construction, use B-1 (one inch (25mm) clearance
tocombustibles)ventpipe.TypeB-2x4orTypeB-2x6aretobe
usedinconjunctionwithaListedrestopspacer.
Type BW gas vent pipe is available for single story or multi-story
installations. Type BW gas vent pipe is to be used with the Listed
baseplate,ceilingplatespacersandrestopspacers.
SPACER
BASEPLATE
4" 45 DEG.
OVAL ELBOW
4" B-1 OVAL
4" B-1 OVAL
SPACER
BASEPLATE
4" B-1 Round
ADAPTER
BASEPLATE
BRACKET
VENTING
A
B
C

45053-0-0523Page 18
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
PARTS LIST
Index
No.
Part
No. Description
1 WFA115 BaseplateGasket
2 11763 Outer Casing Top
3 R618 Motor Mount (Four Required)
4 11764 Motor Mounting Bar (Two Required)
5 M147 Gasket(TwoRequired)
6 R619 Motor
7 11787 Fan Blade
8 DV635 Combustion Chamber
9 11766 Fan Housing
10 11759 Side Panel
11 DV627 Upper Front Panel
12 R1619 Bushing
13 DV823 Diverter Assembly
14 R1749 Vent Safety Switch
15 R1587 Vent Safety Wire Assembly
16 R1536 Bushing
17 11765 Switch Compartment Assembly
18 DV832 Switch Compartment Cover
19 R630 Limit Control
20 R1941 Fan Control
21 DV826 Rear Burner
22 R1617 SparkPlugWire
23 R714L PilotBurnerWithOricePropaneGas
23 R714N PilotBurnerWithOriceNaturalGas
24 DV808 Pilot Tubing
25 DV562 Lower Front Panel
26 DV824 Front Burner
27 P8842 MainBurnerOriceNaturalGas(Two
Required)
27 P8853 MainBurnerOricePropaneGas(Two
Required)
28 DV687 Manifold and Plate Assembly
29 M148 ManifoldGasket
30 DV064 Cover Plate For Observation Hole
31 DV847 BurnerDoorNaturalGas
31 DV972 Burner Door Propane Gas
32 45069 SealBracket
33 M147 GasketTubingSeal
34 P112 Manifold Union
35 R2147 Gas Valve VR8204C 1126 Propane Gas
(10.0”)
35 R2149 GasValveVR8204C1001NaturalGas
(3.5”)
36 UH810 TransformerMountingBracket
37 R1995 Transformer
38 UH451 JunctionBoxCover
39 DV974 Outer Casing Bottom
40 R1515 Bushing
41 R690 Cord Set
42 R896 Bushing
43 DV671 Manifold Support
44 DV765 GasketforChamberAirInlet(Top&Bot-
tom) (Two Required)
45 DV764 GasketforChamberAirInlet(Sides)(Two
Required)
46 R721 Wire Harness
47 R1616 Control Module
48 DV692 ControlModuleMountingBracket
49 R1404 Bushing
50 DV684 Inner Lining Assembly
51 DV629 CasingBack
52 11759 Side Panel
N/S R9832 Wiring Assembly Upper
N/S R9833 Wiring Assembly Lower
N/S R1378 PilotOricePropane
N/S R7429 PilotOriceNatural
Index
No.
Part
No. Description

45053-0-0523 Page 19
PARTS VIEW

45053-0-0523Page 20
To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort.
com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the
nature of the problem with the unit.
To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below.
Thislistchangesfromtimetotime.Forthecurrentlist,pleaseclickontheMasterPartsbuttonatwww.empirecomfort.com.
Please note: Master Parts Distributors are independent businesses that stock the most commonly ordered Original
Equipment repair parts for Heaters, Grills, and Fireplaces manufactured by Empire Comfort Systems Inc.
MASTER PARTS DISTRIBUTOR LIST
Parts Not Under Warranty
Parts can be ordered through your Service Person, Dealer, or a Master Parts Distributor. See this page for the Master Parts Distribu-
tors list. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the
service person/dealer.
Warranty Parts
Warranty parts will need a proof of purchase and can be ordered by your Service Person or Dealer. Proof of purchase is required for
warranty parts.
AllpartslistedinthePartsListhaveaPartNumber.Whenorderingparts,rstobtaintheModelNumberandSerialNumberfromthe
nameplateonyourequipment.ThendeterminethePartNumber(nottheIndexNumber)andtheDescriptionofeachpartfromthefol-
lowing illustration and part list. Be sure to give all this information . . .
ApplianceModelNumber Part Description
ApplianceSerialNumber PartNumber
TypeofGas(PropaneorNatural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipmentscontingentuponstrikes,resandallcausesbeyondourcontrol.
HOW TO ORDER REPAIR PARTS
Dey Distributing
1401WillowLakeBoulevard
VadnaisHeights,MN55101
Phone: 651-490-9191
Toll Free: 800-397-1339
Website: www.deydistributing.com
Parts: Heater, Hearth and Grills
F. W. Webb Company
200 Locust Street
Hartford, CT 06114
Phone: 860-722-2433
Toll Free: 800-243-9360
Fax: 860-293-0479
Toll Free Fax: 800-274-2004
Websites: www.fwwebb.com&www.victormfg.com
Parts: Heater, Hearth and Grills
East Coast Energy Products
10 East Route 36
WestLongBranch,NJ07764
Phone: 732-870-8809
Toll Free: 800-755-8809
Fax: 732-870-8811
Website: www.eastcoastenergy.com
Parts: Heater, Hearth and Grills
This manual suits for next models
1
Table of contents
Languages:
Other Empire Wall Furnace manuals

Empire
Empire DVC55IPXLP-2 Quick start guide

Empire
Empire DV-55IP Quick start guide

Empire
Empire DV215SGXLP-2 Quick start guide

Empire
Empire FAW40SPPXLP-1 Quick start guide

Empire
Empire DV-25-2SG Quick start guide

Empire
Empire FAW40IPXLP-1 Quick start guide

Empire
Empire DV-210-7SG Quick start guide

Empire
Empire DV-20E-5 Quick start guide

Empire
Empire DV-210-7SG Quick start guide

Empire
Empire DV-20E-5 Quick start guide