Empire DV-25-2SG Quick start guide

R-2070 Page 1
DIRECT VENT
WALL FURNACE
MODELS
DV-25-2SG
DV-35-2SG
EFFECTIVE DATE
NOVEMBER, 2000
INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
WARNING: If the information in
this manual is not followed exactly, a
fire or explosion may result causing
property damage, personal injury or
loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinityofthisoranyotherappliance.
— WHATTODOIFYOUSMELLGAS
•Do not try to light any appliance.
•Donottouchanyelectricalswitch;
do not use any phone in your
building.
•Immediatelycallyourgassupplier
from a neighbor's phone. Follow
the gas supplier's instructions.
•If you cannot reach your gas
supplier, call the fire department.
— Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
WARNING:Ifnotinstalled,operatedand
maintained in accordance with the
manufacturer'sinstructions,thisproduct
could expose you to substances in fuel or
from fuel combustion which can cause
death or serious illness.
This appliance may be installed in an
aftermarketpermanentlylocated,manu-
factured (mobile) home, where not pro-
hibited by state or local codes.
This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases, unless a certified kit is
used.

R-2070Page 2
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so
that all burners and burner ignition devices are located not less than 18"
(457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject to
physical damage by a moving vehicle.
Specifications
Model DV-25 DV-35
Input BTU/HR (KW/H) 25,000 (7.3) 35,000 (10.3)
Height 27 3/4" (705mm) 27 3/4" (705mm)
Width 37" (940mm) 37" (940mm)
Depth 11 1/2" (292mm) 11 1/2" (292mm)
Gas Inlet (Pipe) 1/2" (13mm) 1/2" (13mm)
Accessories For Above Furnaces
Blower Package DRB-1
Vinyl Siding Vent Kit DV-822
Qualified Installing Agency
Installationandreplacementofgaspiping,gasutilizationequipment
or accessories and repair and servicing of equipment shall be
performed only by a qualified agency. The term "qualified agency"
means any individual, firm, corporation or company which either in
person or through a representative is engaged in and is responsible
for (a) the installation or replacement of gas piping or (b) the
connection, installation, repair or servicing of equipment, who is
experienced in such work, familiar with all precautions required and
has complied with all the requirements of the authority having
jurisdiction.
The installation must conform with local codes or, in the
absenceof localcodes, withthe NationalFuel GasCode ANSI
Z223.1*/Canadian Installation Code, CAN/CGA B149.
*AvailablefromtheAmericanNationalStandardsInstitute,Inc.,11West42ndSt.,
New York, NY 10036.
Introduction
Always consult your local Building Department regarding regulations,
codes or ordinances which apply to the installation of a direct vent wall
furnace.
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner fill out and mail warranty card
supplied with furnace.
3. Installer should show owner how to start and operate furnace
and thermostat.
Warning:
Any change to this furnace or its control can be dangerous.
This is a heating appliance and any panel, door or guard
removed for servicing an appliance must be replaced prior
to operating the appliance.
General Information
ThisfurnaceisdesigncertifiedinaccordancewithAmericanNational
Standard/CSA Standard Z21.86b-1998 and CSA 2.32b-M98 by the
American Gas Association and Canadian Gas Association, as a
Gravity Direct Vent Wall Furnace to be installed on an outside wall
according to these instructions.
Any alteration of the original design, installed other than as
shownintheseinstructionsorusewithatypeofgasnotshownon
the rating plate is the responsibility of the person and company
making the change.
Important
All correspondence should refer to complete Model No., Serial No.
and type of gas.
Notice: During initial firing of this unit, its paint will bake out and
smoke will occur. To prevent triggering of smoke alarms, ventilate
the room in which the unit is installed.
•Due to high temperatures the appliance should be
located out of traffic and away from furniture and
draperies.
• Children and adults should be alerted to the hazards
ofhigh surfacetemperaturesand shouldstay awayto
avoid burns or clothing ignition.
• Young children should be carefully supervised when
they are in the same room as the appliance.
• Clothing or other flammable material should not be
placed on or near the appliance.
• Any safety screen or guard removed for servicing an
appliance must be replaced prior to operating the
appliance.
• Keep burner and control compartment clean.
• Vent cap hot while furnace is in operation.
• Installation and repair should be done by a QUALI-
FIED SERVICE PERSON. The appliance should be
inspected before use and at least annually by a
qualified service person. More frequent cleaning
mayberequired due toexcessivelint fromcarpeting,
bedding materials, etc. It is imperative that control
compartments, burners and circulating air passage-
ways of the appliance be kept clean.
• DO NOT put anything around the furnace that will
obstruct the flow of combustion and ventilation air.
• DO keep the appliance area clear and free from
combustible material, gasoline and other flammable
vapors and liquids.
• DO examine venting system periodically and replace
damaged parts.
• DO make a periodic visual check of pilot and burner.
Clean and replace damaged parts.
• CAUTION: Pilot hole cover must be kept tightly
closed during operation.
• DO NOT use this heater if any part has been under
water. Immediately call a qualified service techni-
cian to inspect the heater and to replace any part of
thecontrolsystemandanygascontrolwhichhasbeen
under water.
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.

R-2070 Page 3
Some people cannot smell well. Some people cannot smell
the odor of the chemical stench put into the gas. You must
findoutifyoucansmelltheodorantinpropane. Smokingcan
decrease your ability to smell. Being around an odor for a time
can affect your sensitivity or ability to detect that odor. Some-
times other odors in the area mask the gas odor. People may not
smell the gas odor or their minds are on something else. Think-
ing about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under
some circumstances. For example, if there is an underground
leak,themovementofthegas through soilcanfiltertheodorant.
Odorants in LP-Gas also are subject to oxidation. This fading
by point with the members of your household. Someday
whentheremaynotbeaminutetolose,everyone'ssafetywill
depend on knowing exactly what to do. If, after reading the
followinginformation,you feelyoustill needmoreinforma-
tion, please contact your gas supplier.
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. Youmaynotknowallthefollowingsafetyprecau-
tions which can protect both you and your family from an
accident. Read them carefully now, then review them point
can occur if there is rust inside the storage tank or in iron gas
pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That
will take some of the odorant out of the gas, reducing its odor
intensity.
LP-Gasmaystratifyinaclosedarea,andtheodorintensitycould
varyat different levels. Sinceit isheavier thanair, there maybe
more odor at lower levels. Always be sensitive to the slightest
gas odor. If you detect any odor, treat it as a serious leak.
Immediately go into action as instructed earlier.
•LearntorecognizetheodorofLP-gas. YourlocalLP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it
to find out what the propane odor smells like. If you suspect
thatyourLP-Gas hasaweakor abnormalodor,call your LP-
Gas Dealer.
• If you are not qualified, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. Ifyouarequalified,consciouslythinkabouttheodor
ofLP-Gas priorto andwhile lightingpilot lightsor perform-
ing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people
should be particularly alert and careful when new tanks or
cylinders are placed in service. Odor fade can occur in new
tanks, or reinstalled old tanks, if they are filled and allowed
to set too long before refilling. Cylinders and tanks which
have been out of service for a time may develop internal rust
whichwill cause odorfade. If suchconditions aresuspected
to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas
dealer. Aperiodic snifftestof theLP-gas isagood safety
measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the
sameimmediateactionrecommendedabovefortheoccasion
when you do detect the odorized LP-Gas.
• If you experience a complete "gas out," (the container is
under no vapor pressure), turn the tank valve off immedi-
ately. Ifthecontainervalveislefton,thecontainermaydraw
in some air through openings such as pilot light orifices. If
this occurs, some new internal rusting could occur. If the
valve is left open, then treat the container as a new tank.
Always be sure your container is under vapor pressure by
turningitoffatthecontainerbeforeitgoescompletelyempty
or having it refilled before it is completely empty.
SAFETY INFORMATION FOR USERS OF LP-GAS
• Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
• Geteveryoneoutofthebuilding,vehicle,trailer,orarea. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
firefighters declare them to be safe.
• Useyourneighbor'sphoneandcallatrainedLP-Gasservice
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
•Finally, let the service man and firefighters check for
escaped gas. Have them air out the area before you return.
Properly trained LP-Gas service people should repair the
leak, then check and relight the gas appliance for you.
SOME POINTS TO REMEMBER
NO ODOR DETECTED - ODOR FADE
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!

R-2070Page 4
Location of Furnace
Pickalocationon anoutsidewallwitha clear spaceof28"(711mm) high
by 49" (124cm) wide in the room.
Clearances
1. In selecting a location for installation, it is necessary to provide
adequateaccessibilityclearancesforservicingandproperinstallation.
2. Unit is supported by a wall bracket secured to the wall.
3. The minimum clearances from casing to combustible construction is
48" (121cm) on top, 6" (152mm) on each side and 4" (102mm) from
the floor or from the top surface of carpeting, tile or other floor
covering and 0" (0mm) to rear wall.
4. The minimum distance from the center of the vent cap to the nearest
outside corner or obstruction is 24" (610mm).
5. TheDV-25andDV-35minimumwalldepth is41/2"(114mm)
(and the maximum is 13" (330mm). The use of tubes not
supplied by the manufacturer results in unsatisfactory
performance.
The vent terminal of a direct vent appliance, with an input of 50,000
(14.6KW)BTUperhourorlessshallbelocatedatleast9"(229mm)from
any opening through which flue gases could enter a building. The
bottomof theventterminalandtheairintake shallbelocatedatleast12"
(305mm) above grade.
WARNING: The nearest point of the vent cap should be a
minimum horizontal distant of six (6) (1.83m) feet from any
pressureregulator. Incaseofregulatormalfunction,thesix(6)
(1.83m) feet distance will reduce the chance of gas entering the
vent cap.
Locating Wall Opening
The furnace is to be located on an outside wall. Locate wall studs so that
wall opening will be located between wall studs. The wall studs can be
usedforattachmentofwallmountingbracket. Thewallopeningrequired
as shown in Figure 1 is a diameter of 7 1/2 inches (191mm).
A template is provided in furnace carton for positioning furnace on the
wall. Also, refer to Figure 1 for positioning the furnace on wall and for
locating gas line connection.
Figure 1 will position the furnace four inches (102mm) off the floor. If
it is desired to position the furnace higher on the wall, add the difference
to the "A," "B" and "C" dimensions. Note: the vent opening is not in
the center of the furnace.
Figure 1
Locating Gas Supply
Thegaslinecanentertheuniteitherthroughthefloororoutsidewall. The
gaslineopeningshouldbemadeatthistime. Locationoftheopeningwill
bedeterminedbythe position of floor joists and the valve and union used
for servicing.
Figure 2
Installing Wall Mounting Bracket
Locateandcutwallopening. Ifthereisinsulationabovethe wallopening
(air inlet tube) a barrier should be installed above the wall opening (air
inlet tube) to prevent insulation from coming in contact with the air inlet
tube. The barrier must not penetrate into the 7 1/2" (191mm) diameter
wall opening. Place the flat surface of the wall mounting bracket toward
thewall. Inserthalf round flangeofwallmounting bracket intoandatthe
top of the wall opening. The half round flange of the wall mounting
bracketmustbeincontactwiththesheetrockorwoodatthetopofthewall
opening. Level the wall mounting bracket in the wall opening.
On solid wall, when using wall studs for attachment of wall mounting
bracket, fasten wall mounting bracket to wall studs with (2) #10 x 1 1/2"
(38mm) screws provided and fasten (2) additional #10 x 1 1/2" (38mm)
screws provided through the wall mounting bracket and into the solid
wall.
On sheet rock, when using wall studs for attachment of wall mounting
bracket, fasten wall mounting bracket to wall studs with (2) #10 x 1 1/2"
(38mm) screws provided and by using wall opening for access, fasten 2
additional #10 x 1 1/2" (38mm) screws and (2) Tinnerman nuts provided
through the wall mounting bracket and into the sheet rock.
Attaching Furnace To Wall Mounting Bracket
Hang furnace on wall mounting bracket by aligning (2) tabs on wall
mounting bracket with (2) slots located on inner casing top.
The inner casing bottom is to be fastened to the wall. On solid wall,
fasten inner casing bottom with (2) #10 x 1 1/2" (38mm) screws
provided. On sheet rock wall, fasten inner casing bottom with (2)
toggle bolts provided.
Cutting Vent Tubes
This is the most important part of the installation. With the furnace
installed on wall the 6" (152mm) diameter air inlet tube and the 4"
(102mm) diameter flue outlet tube are to be marked and cut using the
following procedure.
37
(940)
C
19 3/4
(502)
WALL MOUNTING
BRACKET
A
28
(711) B
27 3/16
(691)
7 1/2 (191) DIA.
WALL OPENING
GAS INLET
TO VALVE OUTER CASING
OF UNIT
15 1/2
(394)
11
(279)
14
(356) 2 x 4 ((51 x 102) STUDS
16 (406) ON CENTER
21 1/2
(546)
17 3/4
(451)
4 1/2 (114) MIN. WALL DV-25, DV-35
13 (330) MAX. WALL DV-25, DV-35
INCHES (mm)
(DV-25-2 SHOWN)
UNIT IS SUPPORTED
BY WALL BRACKET
4 (102) MIN.
4 (102) MIN.
INCHES (mm)
MOUNTING PLATE
(CAULK UNDER FLANGE)
VENT CAP
FLUE OUTLET TUBE EXTENDS
2 1/2 (64) BEYOND WALL
AIR INLET TUBE EXTENDS
1/2 (13) BEYOND WALL
OUTSIDE WALL
UNIT FASTENED TO WALL
WITH (2) SCREWS
4
(102) GAS INLET TO REAR OF CASING

R-2070 Page 5
1. Attach 6" (152mm) diameter air inlet tube onto the collar of air drop
assembly. Besure6" (152mm) diameter air inlet tube is placed as far
as possible onto the collar of the air drop assembly. Mark the 6"
(152mm)diameterairinlettube1/2"(13mm)beyondtheoutsidewall.
Remove 6" (152mm) diameter air inlet tube from collar of air drop
assembly.
2. Attach4" (102mm)diameterflueoutlettube ontoflueoutletcollaron
combustion chamber. Be sure 4" (102mm) diameter flue outlet tube
is placed as far as possible onto the collar of flue outlet. Mark the 4"
(102mm)diameterflueoutlettube21/2"(64mm) beyond the outside
wall. Remove 4" (102mm) diameter flue outlet tube from collar of
flue outlet on combustion chamber.
3. Mark or wrap tape completely around the tubes at the marked points
to help in making a true cut. Do not crimp or enlarge tubes.
Installing Vent Assembly
1. Place provided caulking beneath the edge of the outside mounting
plate. Useadditionalcaulking tocorrectunevenwall surface,suchas
clapboard.
2. Attach 6" (152mm) diameter air inlet tube onto the collar of air
drop assembly. Attach caulked, outside mounting plate into the
6"(152mm)diameterairinlettube. Positiontheoutsidemounting
plate so that 6" (152mm) diameter air inlet tube has a slight
downwardslopetotheoutside. Thedownwardslopeisnecessary
to prevent the entry of rainwater. Attach outside mounting
plate to exterior wall with (4) #10 x 1 1/2" (38mm)screws
provided.
3. Apply furnace cement to 4" (102mm) diameter flue outlet collar
on combustion chamber and to 4" (102mm) diameter collar on
vent cap. Attach 4" (102mm) diameter flue outlet tube onto flue
outlet collar on combustion chamber. Attach vent cap into the
4"(102mm) diameter flue outlet tube. Attach vent cap to outside
mounting plate with (3) #10 x 1/2" (13mm) screws provided.
4. Installation is completed.
Reassembly And Resealing Vent-Air Intake System
When vent-air intake system is removed for servicing the furnace,
the following steps will assure proper reassembly and resealing of
the vent-air intake assembly.
1. Remove old furnace cement from flue outlet collar on combustion
chamber and collar of vent cap. Remove old furnace cement from
both ends of 4" (102mm) diameter flue outlet tube.
2. Remove old caulking beneath the edge of the outside mounting
plate. Apply new caulking beneath the edge of the outside
mounting plate. Use additional caulking to correct uneven wall
surface, such as clapboard.
3. Attach 6" (152mm) diameter air inlet tube onto the collar of air
drop assembly. Attach caulked, outside mounting plate into the
6"(152mm)diameterairinlettube. Positiontheoutsidemounting
plate so that 6" (152mm) diameter air inlet tube has a slight
downwardslopetotheoutside. Thedownwardslopeisnecessary
to prevent the entry of rainwater. Attach outside mounting
plate to exterior wall with (4) #10 x 1 1/2" (38mm) screws
provided.
4. Apply furnace cement to 4" (102mm) diameter flue outlet collar
on combustion chamber and to 4" (102mm) diameter collar on
vent cap. Attach 4" (102mm) diameter flue outlet tube onto flue
outlet collar on combustion chamber. Attach vent cap into the 4"
(102mm) diameter flue outlet tube. Attach vent cap to outside
mounting plate with (3) #10 x 1/2" (13mm) screws provided.
5. Reassembly and resealing vent-air intake system is completed.
Installing a Vent Near a Window Ledge,
Other Type of Projection or on Vinyl Siding
Direct vent furnaces are designed to be installed on a uniform outside
wall. When the wind comes from any angle (up, down or from either
side), it must hit the vent cap equally over both the air inlet and the flue
outlet portions of the vent. Any wall projection, such as a door or
window casing, which disturbs the wind on one side of the air inlet
section will result in back pressure on the flue section smothering the
flame and eventual pilot outage.
When the vent cap is to be installed on vinyl siding or it appears that
a projection within 6" (152mm) of any side of the air inlet section
could shield the air inlet section, the entire vent should be supported
away fromthe wallat least thedistance of theprojection. 2" x 4" (51mm
x 102mm) framing whose outside dimensions match the overall
dimensions of the mounting plate is recommended. The 2" x 4"
(51mmx102mm)framingprotectsvinylsidingfrompossiblewarpage
or discoloration. All joints can then be sealed and painted. The wall
depth plus the additional depth of the 2" x 4" (51mm x 102mm)
framing should not exceed a total depth of 13" (330mm) for DV-25 and
DV-35. (See Figure 3)
Vinyl siding vent kit, DV-822, is available from Empire Comfort
Systems, Inc. The depth is 3" (76mm), which enables the vent cap
tobeextended awayfromvinylsidingor projections. Thewalldepth
plus the additional 3" (76mm) depth of the vinyl siding vent cap
extension should not exceed a total depth of 13" (330mm) for DV-25
and DV-35. (See Figure 3a)
Warning: Whenvinyl sidingventkit,DV-822or2"x4" (51mm
x 102mm) framing is added to an existing installation (furnace
is installed) do not attempt to add sections of pipe to the flue
outlettubeorairinlettube. Anairtightsealisrequiredforboth
tubes. Refer to Parts List, page 9 to order tubes.
Figure 3a
OUTSIDE MOUNTING PLATE
APPLY CAULKING
2 x 4 (51 x 102) FRAMING
Figure 3
APPLY CAULKING
OUTSIDE MOUNTING PLATE
VENT CAP EXTENSION INCHES (mm)

R-2070Page 6
Gas Supply
Check all local codes for requirements, especially for the size and type
of gas supply line required. On Natural gas lines less than 15' (4.58m)
long, use 1/2" (13mm) pipe; on longer runs, use 3/4" (19mm) iron pipe
or equal. On LP gas lines please consult LP gas supplier.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate, contact
your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the
action of liquefied petroleum gases. The gas lines must be checked for
leaks by the installer. This should be done with a soap solution watching
for bubbles on all exposed connections, and if unexposed, a pressure test
should be made.
Never use an exposed flame to check for leaks. Appliance must be
disconnectedfrompipingatinletofcontrolvalve andpipecappedor
plugged for pressure test. Never pressure test with appliance
connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line
upstream of the gas control to aid in servicing. It is required by the
NationalFuelGasCodethatadriplinebeinstallednearthegasinlet. This
should consist of a vertical length of pipe tee connected into the gas line
that is capped on the bottom in which condensation and foreign particles
may collect.
Figure 4
Method of Installing a Tee Fitting Sediment Trap
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority having
jurisdiction.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
pluggedtapping,accessiblefortestgaugeconnection, mustbeplaced
immediately upstream of the gas supply connection to the appliance.
2. The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testingofthegassupplypipingsystemattestpressuresequaltoorless
than 1/2 psig (3.5 kPa).
Attention! If one of the procedures results in pressures in excess of 1/2
psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a
hazardous condition.
Checking Manifold Pressure
BothPropaneandNaturalgasvalveshaveabuilt-inpressureregulatorin
the gas valve. Natural gas models will have a manifold pressure of
approximately 4.0" w.c. (.996kPa) at the valve outlet with the inlet
pressure to the valve from a minimum of 6.0" w.c. (1.494kPa) for the
purpose of input adjustment to a maximum of 7.0" w.c. (1.743kPa)
Propane gas models will have a manifold pressure approximately 10.0"
w.c.(2.49kPa)atthevalveoutletwiththeinletpressuretothevalvefrom
a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment
to a maximum of 13.0" w.c. (3.237kPa).
A1/8"(3mm)N.P.T.pluggedtapping,accessiblefortestgaugeconnection,
is located on the outlet side of the gas control.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), input ratings should
be reduced at the rate of 4 percent for each 1,000 (305m) feet above sea
level. Canadian High Altitudes for locations having an elevation
abovemeansealevelbetween2,000feet(610m)and4,500feet(1370m),
themanifold pressureistobedecreasedfrom4.0"w.c.(.996kPa)to3.2"
w.c. (.796kPa) for Natural Gas and from 10.0" w.c. (2.49kPa) to 8.0"
w.c. (1.992kPa) for Propane Gas.
Piezo Pilot Ignitor Instructions
Depressingtheredbuttoncompletelycausesasparktooccuratthepilot.
This is a substitute for a match which requires opening the pilot hole
cover.
To light the pilot, it is important that the electrode be 1/8" (3mm) from
the thermopile. The spark must occur at the point the burner flame hits
thethermopile. Theendoftheelectrodewillberedhotwiththepiloton.
On a new installation with air in the gas line, it is suggested that a match
be used. The match will light the pilot faster than the piezo under this
condition.
Primary Air Adjustment (Figure 5)
An air adjustment bolt is located on the chamber support bottom. The
four inch (102mm) clearance between the furnace and the floor allows
access to the air adjustment bolt. The air adjustment bolt is above the
rectangular opening on the inner casing bottom.
On Propane gas, if a whistling noise (resonation) occurs, screw air
adjustment bolt into the chamber support in order to reduce the amount
of primary air. If the whistling noise (resonation) is not eliminated
when the air adjustment bolt is screwed into the chamber support this
mayindicate theairadjustmentboltismisaligned. Graspairadjustment
bolt and pivot (push) air adjustment bolt away from yourself. Observe
themainburnerflameasyoupushairadjustmentboltandwhenthemain
burnerflamebeginstodevelop a yellowflame,youshouldstoppushing
ontheairadjustmentbolt. Screwairadjustmentbolt out of the chamber
support until the yellow flame on the main burner is eliminated. The air
adjustment bolt should now be properly aligned. The reduction in
primary air will soften the main burner flame and will eliminate the
whistling noise (resonation).
On Propane or Natural gas, if a yellow flame occurs, screw air
adjustment bolt out of the chamber support but do not completely
removeairadjustmentbolt from chamber support. Therepositioningof
the air adjustment bolt will increase the amount of primary air. The
increase in primary air will sharpen the main burner flame and will
eliminate the yellow flame.
Figure 5
4" (102mm)
FLOOR
AIR BOLT
GAS SUPPLY PIPNG GAS
VALVE
GROUND JOINT UNION
3" (76mm) MIN.
1/8" (3mm) NPT
PLUGGED HOLE
FOR TEST GAGE
GAS SUPPLY
INLET
MANUAL SHUT-OFF VALVE
1/8" (3mm) NPT
PLUGGED HOLE
FOR TEST GAGE

R-2070 Page 7
Figure 7
Thermostat Location
Millivoltwallthermostatsarespeciallydesignedforuseonself-generating
systems. Theyshouldneverbeusedonline or low voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside wall
away from the furnace but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of millivolts.
Proper operation depends on a good pilot flame. The flame must cover
thetop of the thermopile. Cleaning of the pilot orifice and burnermaybe
required due to spiders.
System Check (Figure 8)
A millivolt meter is required to check the system. Millivolt readings
should be:
• Across the thermopile terminals, 400-450 millivolts with thermostat
OFF.
• Across the thermopile terminals, 150-250 millivolts with thermostat
ON.
• Across the thermostat wires at the valve, less than 30 millivolts with
thermostat ON.
• Across the thermostat wires at the thermostat, less than 5 millivolts
with thermostat ON. (Strong winds, dirty pilot and low pressure will
reduce readings.)
Figure 8
Removing Main Burner
1. Disconnect the thermopile and pilot supply line at the pilot burner.
2. Remove the burner compartment cover.
3. Remove orifice shield.
4. Remove bolt on each side of burner and lift out.
Cleaning Main Burner
The main burner may be cleaned by forcing water into the ports and the
throat of the burner. The main burner should be blown dry or heated to
remove water from main burner.
Removing Main Burner Orifice
1. Open the brass union located after the gas valve.
2. Loosen valve bracket.
3. Remove the 3/8" (10mm)manifold pipe that is attached to the union
elbow until the manifold pipe is free.
4. The main burner orifice is at the end of the manifold pipe.
Removing Pilot Orifice
1. Disconnect the pilot supply line at the pilot burner.
2. Remove pilot orifice from pilot burner. It may be necessary to tap on
pilot burner in order to remove the pilot orifice.
Cleaning Pilot Orifice
After use, cleaning of the pilot burner may be required for the proper
flame. Also, cleaning of the pilot burner may be required due to spiders
(spider webs). The pilot orifice can be cleaned with high pressure air or
by placing under running water. Pilot orifice must be dry before
replacement. Use a pipe cleaner to clean inside the pilot after the pilot
orifice has been removed.
Cleaning Combustion Chamber
When the main burner and vent cap are removed, all internal areas of the
combustion chamber are accessible for cleaning with a vacuum hose.
Proper Pilot Flame (Figure 6)
Thecorrect flame will be almost horizontal,blueandwill extend past the
thermopile 1/4" (6mm). The flame will surround the thermopile just
below the tip.
Onpropane(LP-gas) slightyellowmightoccur wherethepilotflame and
burner flame meet.
Natural gas pilots require adjusting when the inlet pressure is above 5"
w.c. (1.25kPa) Turn adjustment screw clockwise to reduce flame.
Propane (LP-gas) will not require adjusting.
Figure 6
Proper Main Burner Flame (Figure 7)
There will be a short blue inner flame with a much larger lighter blue
secondaryflame. Theburnerflamemayhave a yellow tip when hot. See
the burner drawing showing the approximate heights of each part of the
flame. Dustinthecombustionairwillproduceanorangeorredflame. Do
not mistake the orange or red flame for an improper yellow flame. After
use, cleaning may be required for the proper flame.
BURNER FLAME
PRIMARY FLAME 1/4" (6mm) TO 1/2" (13mm)
SECONDARY FLAME 4" (102mm) TO 6" (152mm)

R-2070Page 8
4. Push in gas control knob slightly and turn clock-
wise to "OFF." Do not force.
5. Replace casing front assembly.
8. Find pilot - follow metal tube
from gas control. The pilot is
behind the pilot access cover.
9. Turn knob on gas control counterclockwise
to "PILOT."
10. Push in control knob all the way and hold in. Imme-
diately light the pilot with the Piezo Pilot Ignitor or a
match. Continuetoholdthecontrolknobinforabout
one(1)minuteafterthepilotislit. Releaseknob, and
it will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 10.
• Ifknobdoesnotpopupwhenreleased,stop
and immediately call your service techni-
cian or gas supplier.
• Ifthepilotwillnotstaylitafterseveraltries,
turnthegascontrolknobto"OFF"andcall
your service technician or gas supplier.
11. Replace pilot access cover.
12. Turn gas control knob counterclockwise to
"ON."
13. Replace casing front assembly.
14. Turn on all electric power to the appliance (if appli-
cable).
15. Set thermostat to desired setting.
16. CAUTION: Pilot access cover must be kept tightly
closed during operation.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance (if appli-
cable).
4. Remove casing front assembly.
5. Push in gas control knob slightly and turn clockwise
to "OFF".
NOTE: Knob cannot be turned from "PILOT" to
"OFF" unless knob is pushed in slightly. Do not force.
6. Wait ten (10) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas,
STOP! Follow "B" in the safety information above. If
you don't smell gas, go to the next step.
7. Remove the pilot access cover located on the combus-
tion chamber.
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. Whenlighting thepilot, followthese instructions
exactly.
B. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neigh-
bor'sphone. Followthegassupplier'sinstructions.
• Ifyoucannotreachyourgassupplier,callthefire
department.
C. Useonlyyourhandtopushinorturnthegascontrol
knob. Never use tools. If the knob will not push in
or turn by hand, don't try to repair it; call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service techni-
cianto inspectthe applianceand toreplace anypart
of the control system and any gas control which has
been under water.
LIGHTING INSTRUCTIONS
1. Set the thermostat to lowest setting.
2. Turnoffallelectricpowertoapplianceifserviceistobe
performed (if applicable).
3. Remove casing front assembly.

R-2070 Page 9
SERVICE AND MAINTENANCE SUGGESTIONS
CALL SERVICEMAN
SYMPTOMS -POSSIBLE CAUSES AND CORRECTIONS
1. Lit match goes out as it enters lighter port.
a. Certain wind conditions will blow out match. Ignite match,
and as it flares, thrust match through opening.
b. Open nearby door or window and relight pilot.
2. Pilot flames but goes out when knob is released.
a. See Lighting Instructions. Relight Pilot.
b. Relight the pilot and hold knob down longer and harder. Close
lighterholecoverjustafterigniting. Checkforagoodpilotflame.
c. Defective thermopile or defective magnet in safety section of
valve. Replace.
3. Yellow pilot flame
a. Obstruction at pilot orifice.
b. Clean pilot orifice.
4. Pilot and main burner go out during normal operation.
a. Check millivolts.
b. Check for proper size of pilot flame.
c. Check for defective or weak thermopile.
d. Check input, reduce as needed.
e. Cover on pilot lighter hole must be air tight.
f. Check for tight fit of air and flue tubes at both ends of vent
assembly. No obstruction around vent that would prevent the
wind from hitting all of the vent equally.
5. Thermostat does not turn the main burner on.
a. Check wiring.
b. Check all millivolt readings.
c. Check for spider in main burner orifice.
6. Yellow main burner flame soot on the vent cap.
a. See Page 6, "Primary Air Adjustment".
b. Removemain burnertocheckforobstructionsinthroatandports.
c. Install new main burner orifice and pilot orifice. Refer to Parts
List, page 9.
7. On Propane gas, if a whistling noise (resonation) occurs.
a. See Page 6, "Primary Air Adjustment".
b. Reduce manifold pressure.
c. Size main burner orifice with a drill bit. For DV-25 use #54 drill
bit. For DV-35 use #50 drill bit.
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
Index Part
No. Number Description
USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
1 DV-769 Vent Cap
2 DV-131 Outside Mounting Plate
3 DV-548 Air Inlet Tube
4 DV-524 Flue Outlet Tube
5 DV-757 Vent Kit
6 DV-899 Wall Mounting Bracket
7 DV-900 Inlet Air Drop Chute
8 DV-762 Gasket - Air Drop Chute
& DV-763 (2 Each Required)
9 DV-895 Casing Top
10 DV-901 Heat Shield
11 DV-902 Inner Casing
12 RH-705 Casing Side (2 Required)
13 712036 Gasket - Flue Outlet Support
14 DV-903 Combustion Chamber (DV-25)
14 DV-904 Combustion Chamber (DV-35)
15 712098 Gasket - Lighting Hole
16 DV-781 Lighting Hole Cover Assembly
with Clear Mica
17 DV-064 Cover Plate
18 DV-988 Burner (DV-25)
18 DV-990 Burner (DV-35)
19 672063 Thermopile
20 DV-1004 Pilot Tubing w/Ferrells
21 RH-238 Burner Door
22 DV-778 Gasket - Burner Door
23 712051 Gasket - Pilot Burner
24 DV-994 Pilot Shield
25 R-2224 Pilot Burner with Orifice (Nat)
25 R-2223 Pilot Burner with Orifice (LP)
26 DV-772-G Electrode and Wire
27 DV-913 Casing Front
28 742155 Burner Orifice, (DV-25 Nat)
28 742238 Burner Orifice, (DV-25 LP)
28 P-86-38N Burner Orifice, (DV-35 Nat)
28 742233 Burner Orifice, (DV-35 LP)
29 P-190 Manifold
30 R-191 Manifold Union Assembly
31 R-5600 Gas Valve (Nat) 7000 MVRLC
31 R-5601 Gas Valve (LP) 7000 MVRLC
32 DV-1003 Valve Bracket
33 DV-764 Gasket - Chamber Support
& DV-765 (2 Each Required)
34 DV-908 Valve Shield
35 R-2313 Piezo Ignitor
Not Shown 742158 Pilot Orifice (Nat)
Not Shown 742266 Pilot Orifice (LP)
Not Shown 662021 Wall Thermostat - Millivolt
Not Shown DV-885 Hardware Package
Not Shown 922113 Operator Section - Nat
Not Shown 922217 Operator Section - LP
Not Shown 652121 Regulator - Nat
Not Shown 652211 Regulator - LP
Not Shown DV-1001 Thermostat Bracket
Index Part
No. Number Description

R-2070Page 10
How To Order Repair Parts...
Partscanbeorderedonlythroughyourservicepersonordealer. Forbestresults,theservicepersonordealershouldorderpartsthroughthe distributor.
Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then
determine the Part Number (not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give
all this information . . .
Furnace Model Number Part Description
Furnace Serial Number Kind of Gas (Propane or Natural)
Part Number
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.

R-2070 Page 11
OPTIONAL BLOWER DRB-1
Vented Room Heaters RH-25-(1, 2, 4) and RH-35-(1, 2, 4)
Direct Vent Wall Furnaces DV-25-(1, 2)SG and DV-35-(1, 2)SG
Installing Optional DRB-1 Blower
1. For RH-25-(1, 2, 4) and RH-35-(1, 2, 4), remove casing front.
1. For DV-25-(1, 2)SG and DV-35-(1, 2)SG, remove casing front
and heat shield.
2. When facing appliance, insert blower assembly into the left
section of the casing (adjacent to the combustion chamber).
3. For RH-25-(1, 2, 4) and RH-35-(1, 2, 4), route cord set through
opening in casing back. The opening in casing back is located
adjacent to gas control.
3. ForDV-25-(1,2)SGandDV-35-(1,2)SG,routecordsetthrough
opening in casing bottom. The opening in casing bottom is
located beneath gas control.
4. Alignthe(2) screw holesontheinner sidepanelandthe (2) screw
holes on casing back with the (4) clearance holes on the blower
assembly. Attach blower assembly to the casing back and inner
side panel with (4) #10 x 1/2" (13mm) (13mm)screws provided.
The blower assembly must be attached first to the casing back
and then to the casing side panel.
5. For RH-25-(1, 2, 4) and RH-35-(1, 2, 4), replace casing front.
5. For DV-25-(1, 2)SG and DV-35-(1, 2)SG, replace heat shield
and casing front.
Attention: Wiring harness on blower is factory assembled and
installed. If wiring harness becomes disassembled use the following
steps to reassemble the wiring harness.
1. Attach (1) pin terminal from black (hot) wire, smooth insulation
on cord set to (1) socket terminal on fan control assembly.
2. Attach(1)pinterminalfromblack(neutral)wire,ribbedinsulation
on cord set to (1) socket terminal from white (neutral) wire on
motor.
3. Attach (1) pin terminal on fan control assembly to (1) socket
terminal from black (hot) wire on motor.
4. Attach green ground wire beneath one of the #10 x 1/2" (13mm)
screws on the blower housing.
Fan Control
The automatic fan control is located in the switch box. The switch
box is attached to the front of the blower assembly. The switch box
is adjacent to the combustion chamber. The fan control is a non-
adjustable automatic type. The fan control will require between 5
and 10 minutes of main burner operation before the fan control
"closes" and activates the blower. The blower will continue to run
between 5 and 10 minutes after the main burner shuts off, before the
fan control "opens" and deactivates the blower.
Wiring
Theappliance,wheninstalled,mustbeelectricallygroundedinaccordance
with local codes or, in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA
C22.1, if an external electrical source is utilized. This appliance is
equippedwithathree-prong[grounding]plugforyourprotection
against shock hazard and should be plugged directly into a
properlygroundedthree-prongreceptacle. Donotcutorremove
thegroundingprongfromthisplug. Foranungroundedreceptacle,
an adapter, which has two prongs and a wire for grounding, can be
purchased, plugged into the ungrounded receptacle and its wire
connected to the receptacle mounting screws. With this wire
completing the ground, the appliance cord plug can be plugged into
the adapter and be electrically grounded.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiringerrorscancauseimproperanddangerousoperation.
Verify proper operation after servicing.
WARNING:
Unpluggingofbloweraccessorywillnotstoptheheaterfrom
cycling. To shut heater off: Turn temperature dial or
thermostat to lowest setting. Turn knob on gas control to
"OFF", depressing slightly. Do not force.

R-2070Page 12
Cleaning
The blower wheel will collect lint and could require cleaning once a
year. Iftheair outputdecreasesorthenoiselevelincreases, it indicates
a dirty wheel. Complete removal of the wheel and scrubbing it with a
brush under flowing water is recommended.
Oiling
The blower motor has an oil hole located on each end of the motor. Use
#20 motor oil only. It is best to oil the motor several times during the
heating season using 2 or 3 drops each time. If the motor fails to start
and hums, it could be a tight bearing due to lack of oil. This may be
corrected by pouring kerosene in the oil holes, allowing to stand for a
few hours and then oiling properly.
PARTS LIST
Index Part
No. No. Description
1 R-2090 Motor
2 632016 Motor Cushion
3 RH-036 Motor Support
4 642030 Blower Wheel
5 RH-710 Blower Housing Assembly
6 9120106 Fan Control Switch
7 872087 Heyco Bushing
8 DV-806 Switch Box
9 DV-807 Switch Box Cover
10 R-2091 Wire Assembly 19" (483mm)
11 8720161 Heyco Bushing
12 R-2099 Cord Set 72" (1.83m)
This manual suits for next models
1
Table of contents
Other Empire Wall Furnace manuals

Empire
Empire DVC55IPXLP-2 Quick start guide

Empire
Empire DV-20E-5 Quick start guide

Empire
Empire DV-20E-5 Quick start guide

Empire
Empire DV-55IP Quick start guide

Empire
Empire DV-210-7SG Quick start guide

Empire
Empire FAW40IPXLP-1 Quick start guide

Empire
Empire DV-210-7SG Quick start guide

Empire
Empire DV-210-10SG Quick start guide

Empire
Empire FAW40SPPXLP-1 Quick start guide

Empire
Empire FAW55IPXLP-2 Quick start guide