TECHNICAL ADVISORY BULLETIN
Recommended Grounding for SE41 Remote Power Node Enclosure
Date: 4/21/2020
Model #: SE41 Remote Power Node Enclosure
Issue
•As there are three different configurations of the SE41 RPN enclosure, additional information on
grounding is required beyond what is provided in the installation manual.
Corrective Action
•Provide grounding instructions with diagrams for the three different configurations of the SE41 RPN
enclosure.
•The grounding specifications and diagrams depicted in this TAB are based on recommended
industry best practices. However, site grounding design and construction shall always adhere to
local electrical codes and the internal standards of the company that is responsible for ownership
and operation of equipment.
Warning
•Only qualified personal should install and connect the power components within the Alpha
system.
•An enclosure that is not properly grounded presents an electrical hazard and will likely result in
premature equipment failure.
•A proper grounding system (i.e. ground electrode system) that meets or exceeds the
specifications of the equipment must be designed and installed prior to or in conjunction with
the installation. The ground system must be bonded to the enclosure to ensure a “common” or
“single-point” ground.

For more information visit www.alpha.com Page 2 of 6
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 0470453-TAB Rev A (04/2020)
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice. F-MKT-04 Rev 1.4
Configuration 1: Recommended grounding of SE41 RPN with combination meter and load center
1. Install a #2AWG tinned solid copper site ground wire (grounding electrode conductor)
originating at the closest driven ground electrode and connect it to the Load Center AC
Equipment Ground (ACEG) bus (refer to Figure 1).
Note: It is recommended that all buried grounding connectors are 12” below finished grade
line or below the frost line. For below grade connections, crimp or mechanical connectors may
be used instead of an exothermic weld provided they are listed for direct burial applications.
2. Route a length of #2AWG tinned solid copper conductor from a junction point on the
grounding electrode conductor (GEC)and connect to the Enclosure Master Ground Bar (MGB)
using an appropriate compression two-hole lug (Refer to Figure 1).
Note: Avoid tight radius bends and route the conductor such that it intersects with the GEC at
a downward orientation as illustrated in Figure 1.
3. Connect the other end of the conductor to the GEC via an irreversible compression
connector or exothermic weld.
Figure 1 –SE41 RPN combo meter & load center grounding diagram

For more information visit www.alpha.com Page 3 of 6
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 0470453-TAB Rev A (04/2020)
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice. F-MKT-04 Rev 1.4
Configuration 2: Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located
within four feet of the SE41 cabinet
Objective:
Install a continuous length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote
service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB).
Steps:
1. Connect the #2AWG tinned solid copper conductor to the ACEG bus in the remote service
disconnect enclosure and then to the ground rod nearest to the Enclosure MGB.
2. Terminate this Grounding Electrode Conductor (GEC) to the Enclosure MGB using an
appropriate two-hole compression lug (refer to Figure 2).
Note: Avoid tight radius bends. It is recommended that all buried grounding connectors are 12”
below finished grade line or below the frost line. For below grade connections, crimp or
mechanical connectors may be used instead of an exothermic weld provided they are listed
for direct burial applications.
Figure 2 –SE41 RPN with remote disconnect (<4') grounding diagram

For more information visit www.alpha.com Page 4 of 6
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 0470453-TAB Rev A (04/2020)
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice. F-MKT-04 Rev 1.4
Configuration 3: Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located
greater than four feet away from the SE41 cabinet
Objective:
Install a continuous length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote
service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB).
Steps:
1. Connect the #2AWG tinned solid copper conductor to the ACEG bus in the remote service disconnect
enclosure and then to the ground rod nearest to the AC service disconnect enclosure and continue
this GEC to the driven ground rod of the SE41 system.
2. Connect the GEC to the SE41 driven ground rod nearest to the Enclosure MGB and have it terminated
to the Enclosure MGB using an appropriate two-hole compression lug. (refer to Figure 3).
Note: Avoid tight radius bends. It is recommended that all buried grounding connectors are 12”
below finished grade line or below the frost line. For below grade connections, crimp or
mechanical connectors may be used instead of an exothermic weld provided they are listed
for direct burial applications.
Figure 3 –SE41 RPN with remote disconnect (>4') grounding diagram

For more information visit www.alpha.com Page 5 of 6
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 0470453-TAB Rev A (04/2020)
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice. F-MKT-04 Rev 1.4
Internal Wiring configurations of Enclosure Master Ground Bar
Confirguation 1: Typical internal wiring of the SE41 RPN Enclosure Master Ground Bar
Configuration 2: Typical internal wiring of previous versions of the SE41 Enclosure Master Ground Bar
Figure 4 –Newer versions of the SE41 RPN Enclosure Master Ground Bar Typical Wiring
Figure 5 –Previous versions of the SE41RPN Enclosure Master Ground Bar Wiring

For more information visit www.alpha.com Page 6 of 6
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 0470453-TAB Rev A (04/2020)
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice. F-MKT-04 Rev 1.4
For additional assistance or if you have any questions regarding this notification, please contact
Alpha Technical Support at 1-888-462-7487 or www.alpha.ca/report-a-problem.
Sincerely,
Satheesh Hariharan David Veraguth
Sr. Product Manager, Outside Plant Solutions Sr. Technical Support Representative