Wiring diagram
P Function (priority)
With the priority enabled, the pumps are prioritized. HW pump turns
on rstly and then, after reaching setpoint temperature of the HW
tank - CH pump starts to work. With the priority turned o pumps are
working independently without priority for the HW pump.
To activate priority, press and hold button until the „P” and „L”
letters will appear on the display. Use or buttons to se-
lect„P”and then conrm your selection with button. Use or
buttons to activate (ON) or deactivate (OFF) priority function.
Conrm the selection with button.
Hysteresis and setpoint temperatures for CH and HW pumps can be
changed by pressing button (menu option). On the display will
appear ashing letter„C”,„U”, or„H”and at this point we can change
the desired setpoint temperatures using or buttons. After few
seconds controller will go itself into operating mode and display the
current temperature.
Controller operation
C– activation temperature of the CH pump above the set value
(setting range 5-80°C).
U– maximum reservoir temperature
(deactivates the DHW pump above the set value, setting range 20-80°C).
H- hysteresis of switching on the HW pump ( setting range 5-30°C).
L function (summer mode)
To activate summer mode, press and hold button until the „P”
and „L” letters will appear on the display. Use or buttons to
select „L” and then conrm your selection with button. Use
or buttons to activate (ON) or deactivate (OFF) summer mode.
Conrm the selection with button.
This function deactivates CH pump. Only HW pump is running
and CH pump will turn on only when boiler reaches 90°C temperature
- protecting function will protect boiler against overheating.
230 V AC
Hot Water
T
T
RADIATOR
HEATING
Manual mode
Manual control of the CH and HW pump depends on the operation
mode and safety rules in the central heating phase (overheating).
Holding down the and buttons will enable / disable the
central heating pump for continuous operation. Holding down the
and buttons will enable / disable the hot water pump for
continuous operation. The hot utility water pump turns o always
after reaching the maximum temperature of the reservoir or until the
temperatures are equal.
Histeresis
This is the dierence between setpoint temperature of the pump start
and setpoint temperature of the pump stop. For example:
1. For the central heating system, the controller has a constant 2°C
hysteresis. After setting the temperature in the„C” parameter, eg at
30 °C, the pump will be turned on after exceeding 30 °C, and it will be
turned o when the temperature drops below 28 °C.
2. In the HW system, after setting the temperature in the„U”parame-
ter to 50 °C, the H.W pump will be turned o when the temperature
exceeds 50 °C. However, it will be activated when the temperature
drops below the„U-H”value.
Additional functions
Controller has an„anti-stop”function which protects pump against lime
scale when there is no heating season. Pump is turned on every 14 days
for 15 seconds.
An additional protection is the frost protection function, which runs
pump permanently when temperature on the sensor drops below 5°C.
BOILER
CH
PUMP
HW PUMP
CH
SENSOR
HW
SENSOR
Alarm
The controller is equipped with an acoustic alarm signaling:
- Too high temperature on the boiler 90 ° C.
- Short circuit in the CH sensor
E1 - short circuit in the CH sensor
E2 - broken CH sensor
E3 - short circuit in HW sensor
E4 - broken HW sensor
If the E1 or E2 error is displayed, the CH pump works all the time until
the fault is removed.
Error Code
PLEASE NOTE!
Tank temperature preview is available on pressing the button.
After a few seconds, the controller will return to displaying the boiler
temperature.
Tank temperature preview