
More often than not, a keypad that will not power up is due to a defective controller -or no power
or ground to the controller. If there is power and ground to the controller (measure with a digital
volt meter at the red and black wires feeding to the controller from the pump), then the controller
is most likely at fault. There will be no way for a tech in the field to determine this for sure (other
than replacement) so both a controller and a keypad should be ordered, if the wiring is found to
be correct.
Keypad powers up then shuts down when other buttons are pressed
This is known as a power reset. This is caused by the voltage to the controller dropping very
rapidly to below where the processor can operate. When the keypad is powered back up, the
jacks down status LED’s will be on. Press All Retract to clear it after the voltage issue is
resolved. Check the battery and the connections from the battery to the pump assembly. Both the
positive and/or the ground connections could be at fault. Check the power and ground wires (and
their connectors) feeding the controller from the pump assembly.
Keypad powers up, seems to operate, but pump does not come on to extend jacks
First verify that no disables are on (Key switch or park brake in wrong position). Locate the blue
wire at the motor solenoid. Using a digital volt meter, measure for voltage at the blue wire when
extend is attempted. There should be at least 10.5 VDC +. If there is no voltage check the blue
wire back thru the harness to the controller. If there is no issue with the blue wire then the
controller is defective. If there is voltage on the blue wire then the solenoid or the motor may be
defective.
Keypad powers up, seems to operate, but pump does not come on to retract jacks
On Bi-Rotational pumps locate the green wire at the motor solenoid or contactor. Measure for
voltage at the green wire when retract is attempted. There should be at least 10.5 VDC+. If there
is no voltage check the green wire back through the harness to the controller. If there is no issue
with the green wire then the controller is defective. If there is voltage at the green wire then the
solenoid or motor may be defective. On Uni-Directional units the blue wire (at the motor
solenoid) is connected to the green inside of the pump harness through a diode. Check for
voltage at the green and blue wires. There should be at least 10.5 VDC +. If there is no voltage,
check the green wire back through the harness. If there is no issue with the green wire and there
is no voltage on the green wire during an attempt to retract, then the controller is defective.
Keypad powers up, seems to operate, and pump motor runs -But one or more jack
legs do not extend or retract
Locate the manifold valve(s) and coil(s). There is one for each function (jack leg). Locate the
proper valve/coil(s) for the leg(s) that do not operate. Each coil will have different colored wires
feeding them. Measure voltage across the coil terminals when trying to operate the jack(s) that
do not operate. There should be at least 10.5 VDC+. If there is no voltage check the wire(s) back
thru the harness to the controller and the coil ground wire(s). If the wire(s) is good then the
controller is defective. If there is voltage across the two terminals at the coil and the jack(s) do
not operate then there is an issue with the coil or valve or other hydraulic control issue.
*NOTE* All electrical testing of the Auto-Level control circuit must be done using a digital
multi-meter. The use of “test lights” is not recommended- as they can not provide a true voltage
reading and could cause damage to the keypad or controller.