GB OPERATING INSTRUCTIONS
PD-C360i/8 DIM… + PD-C360i/24 DIM…
Settings and functions via Mobil-PDi/plus remote control
(Item no. EM10425530)
NOTE: For optimum reception, when programming the settings, point the remote control at the
detector. Please note that if the sun shines directly on the sensor, the standard detection range of
approx. 8 m may be dramatically reduced owing to the sun’s infrared rays.
1. Setting via remote control
The DIP switch 1 on the detector needs to be set as shown in the illustration.
GB00029MAN
ALK 08/2011
ESYLUX GmbH
Postfach 1834, 22908 Ahrensburg/Germany
Internet: www.esylux.com
e-mail: [email protected]
Button Customised setting
Entering programming mode
Blue LED lights up on the detector, indicating “blue mode”
(programming mode). The connected lighting turns on.
Whilst in programming mode, the detector’s movement sensor is disabled.
Channel selection
C1 = lighting (confirmed by blue and red LED flashing alternately)
C2 = HVAC (confirmed by blue and green LED flashing alternately)
Set switch-on light value using the eye button or a fixed light value
By pressing the “DIM” button once, the dimmer begins periodically and
automatically adjusting the light intensity of the lighting gradually between
max. and min. values.
When the desired ambient brightness level has been reached, press the
“eye” button.
The light value will be stored as the new predetermined brightness value.
Preset switch-on values (100 lux - daytime operation)
Confirmed by blue and red LED on the detector flashing alternately.
Adjusting the time setting – first select channel C1 or C2.
Determining a time setting for channel “lighting-C1”:
(channel C1 must be selected first) 1 min. to 15 min.
Confirmed by blue and red LED on the detector flashing alternately.
Determining a time setting for channel “HVAC-C2”:
(channel C2 must be selected first) 5 min. to 15 min. or
short pulse: once the detector has been triggered by movement,
the channel and the green LED will be switched on for 5 seconds
and then off for 5 seconds.
Confirmed by blue and green LED on the detector flashing alternately.
Setting fully and semiautomatic operation modes – first select channel C1 or C2.
Alternating between “fully automatic” and “semiautomatic” operation modes
Semiautomatic mode = press button, the blue LED will turn off for approx. 3 seconds.
Fully automatic mode = press button, the blue LED will flash for approx. 3 seconds.
Activating the orientation light (10 % of luminous efficiency)
So-called “night-light feature”: if the natural light in a room/hallway decreases
and the lighting level falls below the light value set on the detector (e.g.:
400 lux), the lighting is automatically dimmed to approx. 10 % of the
max. luminous efficiency. When movement is sensed, the detector turns
the lighting up to the preset light value. If the presence detector no longer
detects movement, the lights will revert to approx. 10% of their maximum
luminous efficiency once the set time has elapsed.
If the ambient brightness is greater than the preset light value, the presence
detector will automatically switch the orientation lighting off.
Confirmed by blue and red LED on the detector flashing alternately.
Activating the orientation light (10 % of luminous efficiency),
but with fixed switch-on time of 1 min. to 60 min.
Lighting has been switched on, either automatically or by manually pressing
a button. If the presence detector no longer detects movement, the lights will
revert to approx. 10 % of their maximum luminous efficiency once the set
time has elapsed. The selected orientation light switch-on time (e.g. 10 min.)
will now begin. If the detector senses new movement within this period, the
detector turns the lighting up to the preset light value. If, however, no new
movement is sensed within this period, the orientation light is switched off
automatically.
Confirmed by blue and red LED on the detector flashing alternately.
Deactivating the orientation light (10 % of luminous efficiency)
Confirmed by blue and red LED on the detector flashing alternately.
Switching LEDs on/off (red/green LED)
To switch LEDs off = press button, the blue LED will turn off for approx. 3 seconds.
To switch LEDs on = press button, the blue LED will flash for approx. 3 seconds.
Reinstating factory settings
Confirmed by blue and red LED on the detector flashing alternately.
Exiting programming mode
Blue LED goes out; settings are now saved.
The detector will now operate automatically according to the preset values.
NOTE: If the programming mode is not exited by pressing the button, the
detector automatically exits the programming mode 10 minutes after the last
button was pressed.
Additional functions via Mobil-PDi/plus remote control
Checking the range/detection using test mode
Connected lighting turns on – for clear inspection/pacing out of a detector’s
field of detection. Real-time, load-free indication of movement given by
2 flashes of the blue LED.
NOTE: Exit test mode by pressing the “TEST” or “RESET” button.
Temporary dimming to the desired light value (replaces button)
By pressing the “DIM” button once, the dimmer begins periodically and
automatically adjusting the light intensity of the lighting gradually between
max. and min. values. When the desired ambient brightness level has been
reached, press the “eye” button.
This light value will be maintained for as long as persons are present in
the room. Should these persons leave the detection range, the presence
detector will revert to the previous setting mode after the default time setting
has elapsed.
Switching channel “lighting-C1” or “HVAC-C2” on/off manually
(replaces button) – first select the channel.
Interrupting the “TEST”, “light ON/OFF” functions
The detector switches back to the corresponding set operating mode.
• •Mobil-PDi/plus
www.esylux.com
GB
GB OPERATING INSTRUCTIONS
PD-C360i/24 DUOplus
Settings and functions via Mobil-PDi/plus remote control
(Item no. EM10425530)
NOTE: For optimum reception, when programming the settings, point the remote control at the
detector. Please note that if the sun shines directly on the sensor, the standard detection range
of approx. 8 m may be dramatically reduced owing to the sun’s infrared rays.
1. Setting via remote control
The DIP switch 1 on the detector needs to be set as shown in the illustration.
Button Customised setting
Entering programming mode
Blue LED lights up on the detector, indicating “blue mode” (programming mode).
The connected lighting turns on.
Whilst in programming mode, the detector’s movement sensor is disabled.
Channel selection
C1 = lighting (confirmed by blue and red LED flashing alternately)
C2 = lighting (confirmed by blue and green LED flashing alternately)
C3 = HVAC (confirmed by flashing blue LED)
Set the switch-on light value using the eye button for both channels C1 + C2 or select a
fixed light value for channel C1 or C2 individually
Inputting the current ambient light value as switch-on light value: between 5 - 2000 lux
Connected lighting C1 + C2 and the blue LED switch off. Once the input
process has been successfully completed, the lighting turns on and the
blue LED lights up continuously.
Setting a fixed, individual switch-on value for channel C1 or C2:
(channel C1 or C2 must be selected first) 100 lux - daytime operation
Confirmed for C1 by blue and red LED on the detector flashing alternately.
Confirmed for C2 by blue and green LED on the detector flashing alternately.
Determining a common time setting for channel “lighting C1 + C2”:
5 min. to 15 min. or
short pulse: once the detector has been triggered by movement (lighting is
below preset ambient lighting level), the lighting and the red LED will be
switched on for 1 second and then off for 9 seconds.
Confirmed by blue and red LED on the detector flashing alternately.
Determining a time setting for channel “HVAC C3”:
(channel C3 must be selected first) 1 min. to 15 min.
Confirmed by flashing blue LED on the detector.
Setting fully and semiautomatic operation modes – first select channel C1, C2 or C3!
Alternating between “fully automatic” and “semiautomatic” operation modes
Semiautomatic mode = press button, the blue LED will turn off for
approx. 3seconds.
Fully automatic mode = press button, the blue LED will flash for
approx. 3 seconds.
Switching LEDs on/off (red/green LED)
To switch LEDs off = press button, the blue LED will turn off for
approx. 3 seconds.
To switch LEDs on = press button, the blue LED will flash for
approx. 3 seconds.
Reinstating factory settings
Confirmed by blue and red LED on the detector flashing alternately.
Exiting programming mode
Blue LED goes out; settings are now saved.
The detector will now operate automatically according to the preset values.
NOTE: If the programming mode is not exited by pressing the button,
the detector automatically exits the programming mode 10 minutes
after the last button was pressed.
Additional functions via Mobil-PDi/plus remote control
Checking the range/detection using test mode
Connected lighting turns on – for clear inspection/pacing out of a detector’s
field of detection. Real-time, load-free indication of movement given by
2 flashes of the blue LED.
NOTE: Exit test mode by pressing the “TEST” or “RESET” button.
Switching channel “lighting C1 or C2” or “HVAC C3” on/off manually (replaces button) –
first select the channel!
C1 = lighting (confirmed by flashing red LED)
C2 = lighting (confirmed by flashing green LED)
C3 = HVAC (confirmed by flashing blue LED)
Interrupting the “TEST”, “light ON/OFF” functions
The detector switches back to the corresponding set operating mode.
GB00004MAN
ESYLUX GmbH
Postfach 1834, 22908 Ahrensburg/Germany
Internet: www.esylux.com
e-mail: [email protected]
ALK 10/2009

This manual suits for next models

3

Other ESYLUX Remote Control manuals

ESYLUX Mobil-RCi User manual

ESYLUX

ESYLUX Mobil-RCi User manual

ESYLUX Mobil-PDi/MDi Series User manual

ESYLUX

ESYLUX Mobil-PDi/MDi Series User manual

ESYLUX MA00556900 User manual

ESYLUX

ESYLUX MA00556900 User manual

ESYLUX MOBIL-PDi/USER User manual

ESYLUX

ESYLUX MOBIL-PDi/USER User manual

Popular Remote Control manuals by other brands

Sony RM-TP501 operating instructions

Sony

Sony RM-TP501 operating instructions

Tormatic W-433 quick start guide

Tormatic

Tormatic W-433 quick start guide

Giant Alarm System JJ-RC-F8 manual

Giant Alarm System

Giant Alarm System JJ-RC-F8 manual

Fidelity Electronics DTA quick guide

Fidelity Electronics

Fidelity Electronics DTA quick guide

Hyundai Mobis FOB-4F18 user manual

Hyundai Mobis

Hyundai Mobis FOB-4F18 user manual

Scanner SDX7 user guide

Scanner

Scanner SDX7 user guide

Radio Shack 15-1931 owner's manual

Radio Shack

Radio Shack 15-1931 owner's manual

Logitech Harmony One+ user manual

Logitech

Logitech Harmony One+ user manual

THOMSON ROC4301 quick guide

THOMSON

THOMSON ROC4301 quick guide

Solas One-Touch Remote quick start guide

Solas

Solas One-Touch Remote quick start guide

ACS 146R INSTRUCTION MANUAL AND TECHNICAL SPECIFICATIONS

ACS

ACS 146R INSTRUCTION MANUAL AND TECHNICAL SPECIFICATIONS

Charter UR4U-MDVR-CHD2 operating instructions

Charter

Charter UR4U-MDVR-CHD2 operating instructions

Astrea TiVo quick start guide

Astrea

Astrea TiVo quick start guide

Daikin G15 operating manual

Daikin

Daikin G15 operating manual

IKONNIK ET4 user manual

IKONNIK

IKONNIK ET4 user manual

Sea gull lighting 16005-15 manual

Sea gull lighting

Sea gull lighting 16005-15 manual

Akerstroms SESAM 800 CONFIGURABLE operating manual

Akerstroms

Akerstroms SESAM 800 CONFIGURABLE operating manual

ICP DAS USA WP-83 Series quick start guide

ICP DAS USA

ICP DAS USA WP-83 Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.