EUCHNER CES-A-UBA-01 User manual

EN
Operating instructions
Non-Contact Safety System
CES-A-UBA-01/CES-A-UBA-01B (Multicode)

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
2(Translation of the original operating instructions) 2097097-17-08/20
Contents
1. About this document............................................................................................. 4
1.1. Scope............................................................................................................................................4
1.2. Target group ..................................................................................................................................4
1.3. Key to symbols...............................................................................................................................4
1.4. Supplementary documents ..............................................................................................................4
2. Correct use .......................................................................................................... 5
3. Description of the safety function .......................................................................... 6
4. Exclusion of liability and warranty ......................................................................... 7
5. General safety precautions ................................................................................... 7
6. Function............................................................................................................... 8
6.1. Block diagram CES-A-UBA-… ...........................................................................................................9
7. Mounting............................................................................................................ 10
8. Electrical connection .......................................................................................... 11
8.1. Notes about ..........................................................................................................................11
8.2. Safety in case of faults..................................................................................................................11
8.3. Fusing of the power supply and the safety contacts.........................................................................11
8.4. Correct connection .......................................................................................................................12
8.5. Connection example CES-A-UBA-01B ..............................................................................................13
9. Setup ................................................................................................................. 14
9.1. LED indicators..............................................................................................................................14
9.2. Functional check...........................................................................................................................14
9.2.1. Self-test with test input TST ...........................................................................................14
10. System status table ............................................................................................ 15
11. Technical data .................................................................................................... 16
11.1. Evaluation unit CES-A-UBA-… .........................................................................................................16
11.2. Read head CES-A-LNA-…...............................................................................................................18
11.3. Read head CES-A-LNA-SC ..............................................................................................................20
11.4. Read head CES-A-LCA-… ...............................................................................................................23
11.5. Read head CES-A-LMN-SC..............................................................................................................27
11.6. Actuator CES-A-BBA/CES-A-BCA.....................................................................................................29
11.7. Actuator CES-A-BQA......................................................................................................................30
11.8. Actuator CES-A-BDA-20 .................................................................................................................31
11.9. Actuator CES-A-BMB .....................................................................................................................32

3
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
12. Ordering information and accessories................................................................. 33
13. Inspection and service ........................................................................................ 33
14. Service .............................................................................................................. 33
15. Declaration of conformity ................................................................................... 34

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
4(Translation of the original operating instructions) 2097097-17-08/20
1. About this document
1.1. Scope
This document is valid for
ÌNon-Contact Safety System CES‑A‑UBA‑01, evaluation unit for 1 read head (order no. 096960)
ÌNon-Contact Safety System CES‑A‑UBA‑01B, evaluation unit for 1 read head (order no. 096961)
These operating instructions, the document Safety information and any enclosed data sheet form the complete user infor-
mation for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing
special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Meaning
Printed document
Internet
www Document is available for download at www.euchner.com
DANGER
WARNING
CAUTION
Signal
word:
DANGER
WARNING
CAUTION
Consequence if not observed:
Death or severe injuries
Possibly death or severe injuries
Possibly minor injuries
NOTICE
Important!
Signal
word:
NOTICE
Important!
Malfunction or device damage possible
Important information
Tip Useful information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title
(document number) Contents
Safety information
(2525460) Basic safety information
Operating instructions
(2097097) (this document)
Internet
www
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the
device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc.
no. in the search box.

5
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
2. Correct use
Evaluation units of the series CES-A are used to evaluate safety-related signals from EUCHNER read heads. The system
forms an interlocking device. It meets the requirements according to ENIEC60947-5-3.
The system consists of multicode evaluation unit, read head and actuator. It forms an interlocking device with low coding
level (type4).
In combination with a movable guard and the machine control, this system prevents dangerous machine functions from oc-
curring while the guard is open. A stop command is triggered if the guard is opened during the dangerous machine function.
This means:
ÌStarting commands that cause a dangerous machine function must become active only when the guard is closed.
ÌOpening the guard triggers a stop command.
ÌClosing a guard must not cause automatic starting of a dangerous machine function. A separate start command must
be issued. For exceptions, refer to EN 12100 or relevant C-standards.
Before use, a risk assessment must be performed on the machine, e.g. according to the following standards:
ÌENISO13849-1
ÌENISO12100
ÌIEC62061
Correct use includes observing the relevant requirements for installation and operation, e.g. according to the following
standards:
ÌENISO13849-1
ÌENISO14119
ÌEN60204-1
The following components can be connected to the evaluation unit CES-A-UBA…:
ÌCES read heads
ÌCEM read heads
ÌCET read heads
For further information, refer to the operating instructions of the corresponding component and to Table 1: Possible com‑
binations for CES components on page 6.
Important!
ÌThe user is responsible for the proper integration of the device into a safe overall system. For this
purpose, the overall system must be validated, e.g. in accordance with ENISO13849-2.
ÌCorrect use requires observing the permissible operating parameters (see technical data).
ÌIf a data sheet is included with the product, the information on the data sheet applies.
ÌIt is only allowed to use components that are permissible in accordance with the table below.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
6(Translation of the original operating instructions) 2097097-17-08/20
Table 1: Possible combinations for CES components
Evaluation unit Read head
Actuator
CES-A-BBA
071840
CES-A-BCA
088786
CES-A-BDA-20
084720
CES-A-BMB
077791
CES-A-BQA
098108
CES-A-NBA-...
All items
CES-A-BPA
098775
CEM-A-BE05
094805
CEM-A-BH10
095175
CET-A-BWK-50X
096327
CES-A-UBA-01
096960
CES-A-LNA...
All items
CES-A-LNA-SC
077715
CES-A-LCA...
All items
CES-A-LMN-SC
077790
CES-A-LQA-SC
095650
CES-A-UBA-01B
096961
CES-A-LNA...
All items
CES-A-LNA-SC
077715
CES-A-LCA...
All items
CES-A-LMN-SC
077790
CES-A-LQA-SC
095650
CEM-A-LE05K-S2
094800
CEM-A-LE05R-S2
095792
CEM-A-LH10K-S3
095170
CEM-A-LH10R-S3
095793
CET-AX
Key to symbols
Combination possible
Combination possible, guard locking for process protection
Combination possible, guard locking for personnel protection
Combination not permissible
3. Description of the safety function
Devices from this series feature the following safety functions:
The following applies in combination with read heads without guard locking (CES read heads) and read heads with guard
locking for process protection (CEM/CET read heads):
Monitoring of the position of a guard
(interlocking device according to EN ISO 14119)
ÌSafety function:
- The safety contacts are switched off when the guard is open (see chapter 11. Technical data on page 16).
ÌSafety characteristics: category, Performance Level, PFHD(see Technical data for CES‑A‑UBA‑01B on page 17).

7
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety regulations are not followed,
or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety precautions
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components fulll
a personnel protection function.
ÌSafety components must not be bypassed, turned away, removed or otherwise rendered ineffec-
tive. On this topic pay attention in particular to the measures for reducing the possibility of bypass-
ing according to ENISO14119:2013, section 7.
ÌThe switching operation must be triggered only by actuators designated for this purpose.
ÌMounting, electrical connection and setup only by authorized personnel possessing the following
knowledge:
- specialist knowledge in handling safety components
- knowledge about the applicable EMC regulations
- knowledge about the applicable regulations on operational safety and accident prevention.
ÌThe number of switching operations is saved in the internal memory of the evaluation unit. If neces-
sary, this memory can be read by the manufacturer.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating
instructions are always available during mounting, setup and servicing. For this reason you should
archive a printed copy of the operating instructions. You can download the operating instructions from
www.euchner.com.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
8(Translation of the original operating instructions) 2097097-17-08/20
6. Function
The safety system consists of three components:
ÌCoded actuator
ÌRead head
ÌEvaluation unit
1 read head can be connected to the evaluation unit.
Each delivered actuator possesses a unique electronic coding and so is a unique element in the system used. The code in
an actuator cannot be reprogrammed.
Unlike systems with unique code detection, on multicode devices a specic code is not requested but instead it is only
checked whether the actuator is of a type that can be detected by the system (multicode detection). There is no exact
comparison of the actuator code with the taught-in code in the safety switch (unique code detection). The system possesses
a low coding level.
The read head is fastened to the xed part of the guard and is connected to the evaluation unit via a two-core shielded cable
(terminals H11, H12 and SH1).
The actuator fastened to the movable part of the guard is moved towards the read head by closing the door. When the
switch-on distance is reached, power is supplied to the actuator by the read head by induction and data can be transferred.
If a permissible code is detected, the door monitoring output OUT (semiconductor output) is set to HIGH and the safety
outputs (relay output) are enabled. The OUT LED illuminates.
Due to the combination of dynamic polling of the actuators and the redundant, diverse design of the safety electronics with
redundantly controlled safety outputs, the evaluation unit will enter the safe state with every detectable fault.
When a guard is opened, the safety outputs switch off the safety circuit and the OUT LED goes out. The state of the safety
outputs is monitored internally by positively driven NC contacts (relay output).
Independent of the switching state of the safety circuit, the position of the safety door can be polled via the output OUT.
If an internal fault occurs in the evaluation unit, the safety circuit is switched off, the diagnostic output (ERR) is set HIGH
and the ERROR LED illuminates red.
The safety contacts on the safety switch CES can also switch small currents. This allows the user to connect the device
directly to a safe control system.

9
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
6.1. Block diagram CES-A-UBA-…
24V
TST
TST input not connected:
Operation without external testing
0V
OUT ERR GND
H11
10kΩ
10kΩ
H12
14
13 23 24
SH1
DDSP
CPU-A CPU-B
KA KB
white
brown Screen connection
DDSP:
Double Dynamic
Safety Part with fault
monitoring of the actuator,
read head and the
cable to the read head
CES evaluation unit
Read head
Coded
actuator
Trans-
ponder
Illustration: Actuator not in the operating distance
TST Test input (see 9.2.1. Self‑test with test input TST on page 14)
OUT Door monitoring output (not a safety output)
ERR Diagnostic output
GND 0 V (connected internally to 0 V for the operating voltage)
H11/H12 Read head connection
SH1 Read head shield connection
13/14 Connection for relay contact A, safety relay enable
23/24 Connection for relay contact B, safety relay enable

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
10 (Translation of the original operating instructions) 2097097-17-08/20
7. Mounting
NOTICE
Device damage due to improper installation or unsuitable ambient conditions.
ÌRead heads and actuators must not be used as a mechanical end stop.
ÌObserve EN ISO 14119:2013, sections 5.2 and 5.3, for information about fastening the safety
switch and the actuator.
ÌObserve EN ISO 14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
ÌThe evaluation unit must be mounted in a control cabinet with a minimum degree of protection of
IP54. A snap-in element on the rear of the device is used for fastening to a mounting rail.
ÌIf several evaluation units are mounted side by side in a control cabinet without air circulation (e.g.
fan), a minimum distance of 10mm must be maintained between the evaluation units. This dis-
tance enables the heat from the evaluation unit to dissipate.
Important!
ÌFrom the assured release distance Sar, the safety outputs are safely shut down.
ÌWhen mounting several read heads, observe the stipulated minimum distance to avoid mutual in-
terference.
- For CES-A-LNA/-LCA smin=50mm
- For CES-A-LMN smin=20mm
- For CES-A-LQA smin=80mm
smin
ÌIf the actuator is installed ush, the switching distance changes as a function of the installation
depth and the guard material.
Operating
distance
Actuator
Operating
distance
Actuator
Flush mounting Surface mounting
Note the following points:
ÌActuator and read head must be tted so that
- the front faces are at the minimum assured operating distance 0.8xSao or closer when the guard is closed (see sec-
tion Actuating ranges). To avoid entering the area of possible side lobes, a minimum distance is to be maintained in
case of a side approach direction. See section Typical actuating range for the related actuator.
- a hazard is excluded until the assured release distance (Sar) is reached when the guard is open.
- the actuator is positively mounted on the guard, e.g. by using the safety screws included.
- they cannot be removed or tampered with using simple means.
ÌPay attention to the maximum tightening torque for the read head or safety switch and actuator fastenings of 1Nm. For
read heads/actuators made of PE-HD, the maximum tightening torque is only 0.5Nm.

11
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
8. Electrical connection
WARNING
If there is a mistake, loss of the safety function due to incorrect connection.
ÌMonitoring outputs must not be used as safety outputs.
ÌLay the connecting cables with protection to prevent the risk of short circuits.
NOTICE
Risk of damage to equipment or malfunctions as a result of incorrect connection.
ÌAll the electrical connections must either be isolated from the mains supply by a safety transform-
er according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equiv-
alent isolation measures.
ÌAll electrical outputs must have an adequate protective circuit for inductive loads. The outputs
must be protected with a free-wheeling diode for this purpose. The switch-on current may have to
be limited for capacitive loads.
ÌThe tightening torque for the screws on the connection terminals must be 0.6…0.8Nm.
ÌThe connection cable for the read heads must only be extended using EUCHNER plug connectors,
and adequate consideration must be given to EMC. Intermediate terminals must not be used.
ÌThe shield on the connection cable for the read head must be connected to the appropriate termi-
nal SH on the evaluation unit. The portion of cable from which insulation is stripped should be kept
as short as possible (max. 3cm).
8.1. Notes about
Important!
ÌFor use and operation as per the requirements 1), a power supply with the feature “for use in
Class 2 circuits” must be used.
Alternative solutions must comply with the following requirements:
- Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be
designed for max. 3.3A and should be integrated into the 30VDC voltage section.
1) Note on the scope of the UL approval: The devices have been tested as per the requirements of UL508 and CSA/C22.2 no. 14 (protection against electric shock
and re).
8.2. Safety in case of faults
ÌThe operating voltage UBis reverse polarity protected.
ÌThe connections for the read heads, ERR and OUT are not short circuit-proof.
ÌA short circuit between 13/14 and 23/24 can be detected only by means of external pulsing.
ÌA short circuit in the cable can be excluded by laying the cable with protection.
8.3. Fusing of the power supply and the safety contacts
ÌProvide external contact fuses (6AgG fuse or 6A circuit breaker, characteristic B or C) for relay outputs.
ÌThe power supply must be protected with a max. 8A fuse ahead of terminal UB.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
12 (Translation of the original operating instructions) 2097097-17-08/20
8.4. Correct connection
Important!
ÌTo ensure safety, both safety outputs (13/14 and 23/24) must be evaluated.
ÌTo achieve category3 according to ENISO13849-1, it is necessary to monitor the downstream
contactors.
M
Monitoring output
(no safety function!)
Relay K A
Relay K B
+ 24 V
+ 24 V
To the control system
+ 24 V
0 V
24 V
OUT
14
13
24
23
Application
CES-A-UBA...
WARNING
If there is a mistake, loss of the safety function due to incorrect connection.
ÌTo ensure safety, both safety outputs (13/14 and 23/24) must always be evaluated. Sin-
gle-channel use of the safety outputs leads to a reduction of the category in accordance with
EN ISO 13849-1.
M
Monitoring output
(no safety function!)
Relay K A
Relay K B
+ 24 V
To the control system
0 V
24 V
OUT
14
13
24
23
Application
CES-A-UBA...
+ 24 V

13
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
8.5. Connection example CES-A-UBA-01B
24 VDC
GND
-F1
CES-A-UBA-01B
096961
0V
TST
-F2
24V
OUTERR
-V1
SH1
GND
-K1
Read-
head
H11
Trans-
ponder
23
H12
24
-V2
EUCHNER
13 14
-K2
L1
-K2
13
14
-K1
13
14
M
3~
-M1
L2
23
24
23
24
L3
33
34
33
34
Important!
To achieve category 4 according to EN ISO 13849-1, it is necessary to monitor the downstream
contactors.
This example shows only an excerpt that is relevant for the connection of the CES system. The example
illustrated here does not show complete system planning. The user is responsible for safe integration
into the overall system.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
14 (Translation of the original operating instructions) 2097097-17-08/20
9. Setup
9.1. LED indicators
Designation Color Meaning
STATE green Status indication (multifunction display using ashing modes)
OUT yellow Safety circuit closed
ERROR red
ÌOperating fault or
ÌExternal fault (fault in the feedback loop) or
ÌInternal device fault or
ÌTST input activated (function test active)
9.2. Functional check
After installation and any fault, the safety function must be fully checked. Proceed as follows:
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
ÌBefore carrying out the functional check, make sure that there are no persons in the danger zone.
ÌObserve the valid accident prevention regulations.
1. Switch on operating voltage.
- The safety switch carries out a self-test.
The green STATE LED ashes up to 3 times.
The STATE LED then illuminates continuously.
The OUT and ERROR LEDs do not light up.
2. Close all guards.
- The machine must not start automatically.
- The green STATE LED and the yellow OUT LED light up continuously.
3. Enable operation in the control system.
4. Open the guard.
- The machine must switch off and it must not be possible to start it as long as the guard is open.
- The green STATE LED illuminates continuously; the OUT and ERROR LEDs do not illuminate.
Repeat steps 2…4 separately for each guard.
9.2.1. Self-test with test input TST
On electromechanical safety switches or magnetic switches, the function test can be performed by cyclically opening the
guard.
From category 2 according to ENISO13849-1, EN 60204-1 : 1997 (section 9.4.2.4) requires a function test performed
on the entire safety system on start-up or after dened intervals.
Testing of the internal function of the unit is not necessary because the device monitors itself in real time. Welding of an
output contact (relay output) is detected by the device at the latest the next time the guard is opened. A short circuit in the
output cable is not detected by the device.
In addition, the entire safety circuit can be tested without opening the guard. For this purpose, opening of the guard can be
simulated by applying 24 V DC to the test input TST.
The safety outputs are switched off, enabling testing of the complete safety circuit. The diagnostic output ERR on the eval-
uation unit is also set HIGH as a monitoring function.
When test input TST is reset, the evaluation unit resets the diagnostic output ERR to LOW, the red LED switches off and
normal operation is continued.
Important!
After the self-test, the test input TST must be connected to 0 V again or must be disconnected.

15
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
10. System status table
Operating mode
Actuator/door position
Safety outputs A and B
PLC LED indicator
Output
State
In-
put Output
TST
OUT (status
signal)
ERR
STATE (green)
OUT (yellow)
ERROR
(red)
Normal operation
closed on N 1 0 Normal operation, door closed
open off N 0 0 Normal operation, door open
State indication X off X 0 0 3 x + Self-test after operating voltage is applied
Fault display X off N 0 1 Device-internal component failure or
excessively high external interference (EMC)
Function test X off 1 0 1 Function test active (TST input=24V)
Key to symbols
N 0 Volt or not connected
1 24 Volt
0 0 Volt
LED not illuminated
LED illuminated
3 x + LED ashes three times and then illuminates continuously
X Any state
Important!
If you do not nd the displayed device status in the system status table, this indicates an internal device
fault. In this case, you should contact the manufacturer.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
16 (Translation of the original operating instructions) 2097097-17-08/20
11. Technical data
11.1. Evaluation unit CES-A-UBA-…
ÌHousing for rail mounting, IP20
ÌRelay output
Ì1 read head can be connected
Dimension drawing
CES
STAT E
OUT
ERROR
114
22,5
99
13 14 23 24
GNDERROUTTST
24V 0V
H11 H12 SH1
Suitable for standard 35 mm mounting rail
Switching characteristics
Ì2 safety outputs with one NO contact
each (relay outputs)
Ì1 door monitoring output (semiconductor
output, not a safety output)
Approvals
Guard
closed
(actuator detected)
open
(actuator not in the actuating
range)
Read head Actuator Read head
13 14
23 24
24 VOUT
13 14
23 24
24
VO
UT

17
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
Technical data for CES-A-UBA-01B
Parameter Value Unit
min. typ. max.
Housing material PA6.6 plastic
Dimensions 114x99x22.5 mm
Weight 0.2 kg
Ambient temperature at UB=DC 24 V -20 - +55 °C
Atmospheric humidity, not condensing - - 80 %
Degree of protection IP20
Degree of contamination 2
Mounting Mounting rail 35mm according to EN60715 TH35
Number of read heads 1 read head per evaluation unit
Connection (plug-in screw terminals/coded) 0.25 - 2.5 mm²
Operating voltage UB(regulated, residual ripple < 5%) 21 24 27 V DC
For the approval according to the following applies Operation only with UL class 2 power supply or equivalent measures
Current consumption IB(with relay energized) 1) - 150 - mA
External fuse (operating voltage UB) 0.25 - 8 A
Safety contacts 2 (relays with internally monitored contacts)
Switching current (relay outputs)
mA
- at switching voltage AC/DC 21…60 V 1 - 300
- at switching voltage AC/DC 10…30 V 10 - 6000
Switching load according to Class 2 max. 30 V AC/Class 2 max. 60 V DC
120 V AC 3 A / 240 V AC 1.5 A
External fuse (safety circuit) according to EN60269-1 6 AgG or 6 A circuit breaker (characteristic B or C)
Utilization category according to EN60947-5-1 AC-12 60 V 0.3 A / DC-12 60 V 0.3 A
AC-12 30 V 6 A / DC-12 30 V 6 A
AC-14 30 V 2 A / DC-13 24 V 3 A
Rated insulation voltage Ui63 V
Rated impulse withstand voltage Uimp 1.5 kV
Rated conditional short-circuit current 100 A
Resilience to vibration Acc. to EN60947-5-2
Mechanical operating cycles (relays) 10x106
Switching delay from state change 2) - - 180 ms
Discrepancy time (of the switching points of both relays) - - 120 ms
Ready delay 3) - - 3 s
Dwell time 4) 0.5 - - s
Switching frequency max. 5) - - 1 Hz
Repeat accuracy R acc. to ENIEC60947-5-3 ≤10 %
Monitoring outputs (diagnostics ERR, door monitoring output
OUT, semiconductor output, p-switching) 6)
- Output voltage 0.8xUB- UBV DC
- Max. load - - 20 mA
Test input TST
- Input voltage LOW 0 - 2 V DC
HIGH 15 - UB
- Input current HIGH 5 8 10 mA
EMC protection requirements Acc. to EN60947-5-3
Reliability values acc. to ENISO13849-1
as a function of the switching current at 24 V DC ≤0.1 A ≤1 A ≤3 A
Category 3
Performance Level (PL) e
PFHD4.3x10-8
Mission time 20 years
Number of switching cycles/year 760 000 153 000 34 600
Diagnostic coverage DC 90 %
MTTFD100 years
1) Without taking into account the load currents on the monitoring outputs.
2) Corresponds to the risk time according to EN60947-5-3. This is the maximum OFF time for the safety outputs following removal of the actuator.
3) After the operating voltage is switched on, the relay outputs are switched off and the door monitoring output is set to LOW potential during the ready delay.
4) The dwell time of an actuator inside and outside the actuating range must be at least 0.5s to ensure reliable detection of internal faults in the evaluation unit (self-monitoring).
5) If the current load is >100mA, a switching frequency of 0.1 Hz should not be exceeded as this will affect the mechanical life of the relay contacts.
6) Not short circuit-proof.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
18 (Translation of the original operating instructions) 2097097-17-08/20
11.2. Read head CES-A-LNA-…
ÌCube-shaped design 42x25mm
ÌHard-wired cable
Dimension drawing
CES-A-L XXXXXX
25
∅8
∅4,5
42
32 ±0,1
12
4,6
"l"
2 M4x14 safety screws included
Active face Active face
Typical actuating range
With evaluation unit CES-A-UBA-01 and actuator CES-A-BBA
-8 -4
-6 -2 26
48
0
2
4
6
8
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on
distance
ON
OFF
Hysteresis
Distance sSao
Output stage
Switch-off
distance
OFF
With evaluation unit CES-A-UBA-01B and actuator CES-A-BBA
Side
lobe
N
-10-15 -5 0
Centre offset m [mm]
Distance s [mm]
OFF
ON
Switch-on
distance
ON
OFF
Hysteresis
Distance sSao
Output state
Switch-off
distance
OFF
Hysteresis
-20 5 201510
5
10
15
20
Side
lobe
N
Actuator
Read head
s
m
NOTICE
For a side approach direction for the actuator and read head, a minimum distance of s=3mm must
be maintained so that the actuating range of the side lobes is not entered.
Approvals

19
2097097-17-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
EN
Terminal assignment
Read head with connection cable
H11
H12SH1
BN
WH
Shield Read
head
Evaluation unit
CES-A-UBA-…
Technical data
Parameter Value Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated
Dimensions 42 x 25 x 12 mm
Weight (incl. 10 m cable) 0.3 kg
Ambient temperature -25 - +70 °C
Degree of protection IP67/IP69K
Installation orientation Any
Method of operation Inductive
Power supply Via evaluation unit
In combination with actuator CES-A-BBA on evaluation unit CES-A-UBA-01
Assured release distance Sar - - 23
mm
Actuating range for center offset m = 0 1)
- Switch-on distance - 6 -
- Assured operating distance Sao 5 - -
- Switching hysteresis 0.5 1.5 -
In combination with actuator CES-A-BBA on evaluation unit CES-A-UBA-01B
Assured release distance Sar - - 32
mm
Actuating range for center offset m = 0 2)
- Switch-on distance - 15 -
- Assured operating distance Sao 10 - -
- Switching hysteresis 0.5 2 -
Minimum distance s for side approach direction - 3 -
In combination with actuator CES-A-BDA-20 on evaluation unit CES-A-UBA-01
Assured release distance Sar - - 24
mm
Actuating range for center offset m = 0 3)
- Switch-on distance - 7 -
- Assured operating distance Sao 6 - -
- Switching hysteresis 0.5 1.5 -
Minimum distance s for side approach direction - 1 -
Installation in steel, surface/ush
Assured release distance Sar - - 24
mm
Actuating range for center offset m = 0
- Switch-on distance - 4.4/3.6 -
- Assured operating distance Sao 3.6/3 - -
- Switching hysteresis 0.4/0.3 1.2/1.0 -
Minimum distance s for side approach direction - 1 -
Installation in stainless steel, surface/ush
Assured release distance Sar - - 24
mm
Actuating range for center offset m = 0
- Switch-on distance - 4/3.3 -
- Assured operating distance Sao 3.3/2.7 - -
- Switching hysteresis 0.4/0.3 1.1/0.9 -
Minimum distance s for side approach direction - 1 -
In combination with actuator CES-A-BDA-20 on evaluation unit CES-A-UBA-01B
Assured release distance Sar - - 33
mm
Actuating range for center offset m = 0 3)
- Switch-on distance - 16 -
- Assured operating distance Sao 11 - -
- Switching hysteresis 0.5 2 -
Minimum distance s for side approach direction - 4 -
Connecting cable Hard-wired encapsulated connection cable, with crimped ferrules
PVC, ∅4.6 mm
PUR, ∅4.8 mm, suitable for drag chain
Cable length - - 25 m
1) These values apply to ush installation of the read head and the actuator in aluminum.
2) These values apply to surface installation of the read head and the actuator.
3) These values apply to non-metallic surrounding material. Other materials on request.

Operating instructions
Non-Contact Safety System CES-A-UBA-01/CES-A-UBA-01B
20 (Translation of the original operating instructions) 2097097-17-08/20
11.3. Read head CES-A-LNA-SC
ÌCube-shaped design 42x25mm
ÌM8 plug connector
Dimension drawing
5,5
∅10
6,8
∅8
∅4,5
4,6
12
25
min.38
32 ±0,1
4232,6
A0
CES-A-L 077715
3
4
1
A0
CES-A-L 077715
20 1,
26,5
2 M4x14 safety screws included
Cable outlet with angled
connector
Active face
Active face
Typical actuating range
With evaluation unit CES-A-UBA-01 and actuator CES-A-BBA
-8 -4
-6 -2 26
48
0
2
4
6
8
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on
distance
ON
OFF
Hysteresis
Distance sSao
Output stage
Switch-off
distance
OFF
Approvals
This manual suits for next models
1
Table of contents