6.4 GS PRODUCT Setting_CO2 Self-Correcting Algorithm ADC
1. NDIR is a fast, accuracy & precious technology to detect CO2 concentration. It uses two physical
characteristics, to detect the concentration of specified gas,
a. The gas absorbs the wavelength of Infrared Rays.
b. The gas concentration and absorbed quantity is Direct Proportion.
2. The strength of Infrared Rays have attenuation phenomenon after long time, Then the accuracy &
precious of measurement must be influenced. Thus the technology of CO2 Self-Correcting Algorithm
provides improvement for this defection.
3. In the general environment, the CO2 concentration usually measured as 400ppm. The environments as
From Room/ Office with the condition as midnight period & nobody status, the CO2 concentration
usually measured as 400ppm. Thus GS use the average statistics values for 7 days to implement
Self-Correcting feature.
4. This feature is not adaptive to use in special environment as Factory/ Plant Greenroom where the CO2
concentration may keep on high value & keep for long period.
6.5 GM/GS PRODUCT Setting_Port No. & Transmission Rate
1. RS-485 serial communication interface merged with Modbus Protocol, these 2 features co-works to
construct the digital communication format.
2. Usable Port No. Range : 1~247.
3. On the same wiring, the Port No. must to be different.
4. The maximum devices quantity which connected to RS-485 interface restricted on 31 devices.
5. Three selectable Transmission Rate (Baud Rate): 9600 / 19200 / 38400 / 57600 / 115200 bps.