
SECTION II
OPERATING INSTRUCTIONS
Care should be taken to ensure that the input selector on the
rear of the unit is set to match the mains supply from which the
supply is to be operated.
The mains lead is wired as follows :
—
BROWN Mains Line.
BLUE Mains Neutral.
GREEN/YELLOW Earth.
NORMAL CONSTANT VOLTAGE OPERATION
Before connection to the mains supply is made, the output
"ON/OFF" switches, should be set to "OFF". The link on the
bottom of the unit should be in the "CV" position.
With the mains supply connected, the mains "ON/OFF" switch
is set to "ON" and the mains indicator lamp should light.
With the meter switch set to "VOLTS", the required output
voltage is selected by adjusting the "COARSE" and "FINE"
voltage controls on the front panel and the current limit control
set to maximum' (fully clockwise). Unless use of the current
limiting is to be made, the load is now connected and the output
"ON/OFF" switch set to "ON". Output current can he monitored
by setting the meter switch to "CURRENT".
CURRENT LIMIT SETTING
If acertain maximum current must not be exceeded or a
roughly constant current is required, use may he made of the
current limiting facility, maximum current being set by the front
panel control marked "CURRENT LIMIT".
(1) APPROXIMATE CONSTANT CURRENT OPERATION
With the mains supply connected to the unit, mains and output
switches set to "ON", the meter switch set to "CURRENT" and
the output voltage controls set to maximum, the positive output
terminal is linked to the negative output terminal and the current
limit control set to give the required current. On removal of the
link and connection to the load, the unit will give aroughly
constant current over avoltage range from zero to the maximum
specified output voltage depending on the bad resistance.
(2) CURRENT CEILING OPERATION
If acertain maximum current is not to be exceeded then the
setting up procedure is as follows :—
With the mains supply connected to the unit, mains and output
switches to "ON", the meter switch set to "CURRENT" and the
voltage controls set to the required value, avariable load is
connected to the unit and is set to give the required maximum
current. The current limit control is then adjusted until the
current just starts to fall. The unit will now prevent more current
than this value being drawn from it. It is advised that this
current "ceiling" is set to approximately 10% in excess of the
expected maximum to prevent any modification to the voltage
regulation characteristic. The variable load is now disconnected
and the unit is ready for use.
ACCURATE CONSTANT CURRENT OPERATION
(See Fig. 1}
If afixed resistor Rs is connected between the positive output
terminal and the "I const" or "—F/B" terminal, the link on the
bottom of the unit set to CI, and the load Rl between the "I const"
or "—F/B" terminal and the "O/P -ve" terminal, then the unit
will keep the voltage across Rs constant. Thus aconstant current
will flow in Rs. Since Rl is in series with Rs, the same current
will flow in Kt..
The value of Rs is given by :— See Errata and
VAddenda -Page 15
Rs =Rl max.
Iout
Where Vis the maximum specified output voltage of the unit.
Rs must have apower rating well in excess of the power it
dissipates in order that the change in resistance due to self heating
is minimised.
The power dissipated in Rs is given by :
—
P(Rs) =Iout- Rs.
Rs is then connected between the "0/P +"and "I const"
terminals. The "I const" or "—F/B" terminal is shorted to the
"O/P—" terminal and the "VOLTAGE ADJUST' controls set
until the meter reads the required output current. The "short"
is then removed and the load connected in its place. The output
current will be constant with the same specification as the constant
voltage specification with the load varying from zero to Rl max.
note i
—
The front panel "CURRENT LIMIT" control should be set
to maximum for this mode of operation.
3