FBII XL-2T User manual

-
XL-2T
Hookup and Installation Instructions
-
—
FBIIz@)
FIRE BURGMRY INSTRUMENTS INC.
Subsida~ of HtWay Cop.
149 Hleen Way, Syoaset, NY 11791
Nw33
Previous Menu

THANK YOU for your purchase of the FBII
XL-2T.
The purpose of the manual is to give you abrief overview of the XL-2T control panel, and provide instructions for installing a
baaic system. FBII is always available to servs YOU. Our SALES and TECHNICAL SUPPORT staff are available to assist
you in anyway possible.
FOR SALES , REPAIRS
OR
TECHNICAL SERVICE ,
CALL TOLL FREE :
(800) 645-5430
(8:OOAM-8:OOPM)Efl.
Before you call Technical Service, be sure you:
+Check the wiring diagram and verify your connections.
+Check all fuses.
,- +Assure that the transformer and backup battery voltagee are supplying the proper voltage Ievele.
oVefify your programming information.
+Read this manual thoroughly.
+Consult the Trouble shooting Section of this Manual.
+Note the roper model number of this product, and the vereion level of known) along with any
!’documen ation that came with the product.
+Have your company name and telephone number ready.
This information will allow us to service you more quickly and effectively. Please, remember to BE PATIENT while
waiting on the telephone; your call will be answered as soon as possible.
FOR YOUR CONVENIENCE, aSystem Planning Worksheet and aProgramming Worksheet is included at the
back of this manual. These can be removed to help you record account information.
XL-2T Hookup& Installation Manual Page 3

TABLE OF CONTENTS
~TRODUCflON . . . . . . . . . . . . . . . . . . . 7
sYsm~GANDHooKuP . . . . . . . . . . ...8
WtiingDia~m . . . . . . . . . . . . . . . . . . . ...8
TertindComections . . . . . . . . . . . . . . . ...9
Au. Device CumentWorkheet 13
W1ringMo.forhnes&KeWads . . . 13
PCBOARD~STW~ON . . . . . 14
Mounting tie PCBoad 14
~YPADMO~~G . . . . . . . . . . . . . . 15
=4600WKe~ad . . . . . . . . . . . 15
=4600SMKeypad 16
6615Ke~ads . . . . . . . . . . . . . . . . . . . 17
~YPADMYOUT . . . . . . . . . . . . . 18
WypadSounder . . . . . . . . . . . . . . . 20
SYS~MOPERAT30NS . . . . . . . . . . . . . . . . . . ...21
Power Up/SNtem Reset . . . . . . . . . . . . . . 21
Mating, . . . . . . . . . . . . . . . . . . . . . . . . . ,21
Smyting . . . . . . . . . . . . . . . . . . . . . ..2l
hs~nthting . . . . . . . . . . . . . . . . . . . ...21
Stiy-hsWt ~ng . . . . . . . . . . . . . . . . . 22
Dieting ., .,, ,, . . . . . . . . . . . . . . . . . .,22
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
BWassbyhndtioup . . . . . . . . . . . . . . . 22
QuickBWmsbyfine/tio.p 23
Auto-Unbypass . . . . . . . . . . . . . . . . . . . . . 23
Mmud Unbypass . . . . . . . . . . . . . . . . . . 23
User Ctie Pro~ting 24
User Deletion . . . . . . . . . . . . . . . . . . . . . 25
KeWad Emergency Conditions 25
Quick Comand Mties ..,.,.,, . . . . . . 25
Quick ~ng . . . . . . . . . . . . . . . . . . . . . . 25
Qui.k Force ma.......,,,,,. 25
Set Ttie 26
Display %ne Dkectoq . . . . . . . . . . . 26
Set Autoh Time . . . . . . . . . . . . ...26
Toggle Chne, ,,, .,, ,, ...,..... 27
Display Time .,, ,, .,, ,, .,,,,.,, .27
Display Autoh Time ,., ,,,, ... 27
Door Skike . . . . . . . . . . . . . . . . . . . . 27
On-ltie Dowdoad . . . . . . . . . . . . . ...27
Instiler Modes . . . . . . . . . . . . . . . . . . . ...28
hstiler Keypad Roguing....,,,,. 28
System Default 28
User Ctie Default . . . . . . . . . . . . . . . 28
Wak Testw/Sounder 28
Wak Testw/So”nder&BeU 29
S~tembg View 29
hstiler Unauended Dow”load ,., 29
On-line Dowdoad . . . . . . . . . . . . . . . 30
SYS~MPROGRAMM~G . . . . . . . . . . 30
PROGRAMM~G Q~STfONS .,... 31
OIPti~TeIephone Number ,...,....31
02 Secon~T elephoneN umber ,,,.,..31
03 CaObwk Telephone Number ., .,,,, 31
04 Telephone heti . . . . . . . . . . . . . . . . . 31
05 Account Nwberl 31
06 Account Nwber2 31
07 CSDider l& System Options 32
08 CSDialer 2& SWtem Options 34
09 MisceUaneous Options 36 w
10 Bell Timeou@ &CSTestktemal . . . . 37
llEnq&tit& CrossTmeouk . . . . . . . . 39
12 Miscellaneous Options 40
13 System Options . . . . . . . . . . . . . . . . . 42
14 Triggers l&2 . . . . . . . . . . . . . . . . . . 43
15 Autoh The . . . . . . . . . . . . . . . . . 44
16 CSTest Tre e. . . . . . . . . . . . . . . . . . . 44
17 fine lType . . . . . . . . . . . . . . . . . . . . . 44
18~ne2T~e . . . . . . . . . . . . . . . . . . . . . 44
19~ne3TWe . . . . . . . . . . . . . . . . . . . . . 44
20~ne4Type 44
21~ne5Type . . . . . . . . . . . . . . . . . . . . 44
22 Bne6T~e . . . . . . . . . . . . . . . . . . . . . 44
23%ne7T&e .,..,,.,,,,,.,,,,,,.. 44
24~nesl &2 CSCdes . . . . . . . . . .. ,41
25%nes3&4CS Codes . . . . . . . . . . ...47
26%nes S&6 CSCties 47
27~nes7CS Col e. . . . . . . . . . . . . 47
28 bbush&ACbss 48
29 Ptic&bw Batted,.. , .,,..,,,,,. 48
300pen& Close . . . . . 48. . . . . . . . . ...48
31 Cancel &CSTest, . . . . . . . . . . . . . . . 49
32 BW~s, Restore, Day& Fke Trouble 49
33 Keypad Fie&Atii~ . . . . . . . . . . . 49
34 Dowtioad &Tmper . . . . . . . . . . . . . . 50
35 Recent Close, Exit Wor&Sw. Shut 50
00 bstiler Code . . . . . . . . . . . . . . . . . . . . 50 u
DATA ENTRY VW~D&~D~YPADS ,., S1
HOWto Enter Prog _gMde,.., ,. 51
Wbat You See Ontie=DKeWad,., ,, 51
Wbat You See Onthe ED Keypad ... 52
Howto Enter Dati . . . . . . . . . . . . . . . ...52
Exit S~tem Rogm Mtie 53
S.m~Of S~@m Roguing . . . . . . 53
tine Descriptor tiogd g. . . . . . . . . 54
SYSTSMDEFA~TS . . . . . . . . . . . . . . . ,.. ,... 55
S~Y OF =YP~ FUNCTfONS ,., ,., 56
User Functions . . . . . . . . . . . . . . . . . . ...56
hstiler Modes . . . . . . . . . . . . . . . . . . 57
APPENDH ACS =PORT. FORMATS 58
APPENDE B-TROUBESHOO~G 63
SYS~M PW~G WORKS~ET ,,., 64
&neMomtion . . . . . . . . . . . . . . . . . ...64
User Cties . . . . . . . . . . . . . . . . . . . . . . . . 65
Kc~ads . . . . . . . . . . . . . . . . . . . . . . 65
SYS~M PROGRAMM~G WORKSHEET, 66
WARNfNG ~A~ONS STATEENT 68
FCC STA~~NT, . . . . . . . . . . . . . . . . . . . . . ...69
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . 70
w
XL-2T Hookup& Installation Manual Page 4

XL-2TTO XL-2COMPARISON
The XL-2T is an enhanced version of the XL-2 control panel. Some new featurea have been added and others
have been modified, The following is aquick comparison,
XL-2T NEW& MOD\FIED FEATURES XL-2 S[M!LAR FEATURES
7Zones: all fully programmable incluting
Key switch (progrsm quests. #1 7-23) 7Zones: 6fully pro rammable +1prog. only
?as Pamc or Key SWI ch
7R%:;!E{?2kj ‘o ‘r ‘c) EOL Loop Type Only
Audible or Silent by Zone (program quests. #1 7-23)
!5User Codes& Door Strike User capability
Unattended Download (Installer Mode 8)
On-line Download (Installer Mode 9)
Additional Formata: FBI Superfaet, Point ID
(program quests. #7& 8)
Dual CS Reporting (program quests. #7 &8)
Built-in Siren Drivar or Conventional
Bell Output (program quest. #12)
Cross Zoning to revent Falae Alarms
!
(program quests, 17-23)
2EntW Timers (program quest.#11 )
Swinger Shutdown -Bell and Dialer Lockout
(program quest. #04)
Call Waiting IPBX Dialin g.ldig” It ent~
(program quest. #01 &#O )
7S Event History (Alarms, Troubles Low Battery
-not cleared by user code (Installer ~ode 4)
2Programmable Output Trig era
8
Terminal P1 (program quest. 14)
CS Test Timer -1 Hour, 1Day, 7Day, 27 Day, 60 Da
—or 90 Day by Time, Event or Both (program quest. #1 d
Recent Close Code (program quest. #35)
End User Chime OWOFF Toggle (Quick Corn. #8)
Exit Error Warning (always enabled)
Quick Exit (program quest. #9)
Arm While Faulted (program quest. #l 2)
Restore Followe Bell or Loop {program quest. #07)
Sstem Stabili=tion on Power Up -to Eliminata
&tion Detector False Alarms
Fact Loop Reaponae 10 maec) Option by Zone
i
(program quests. #17. 3)
AC (50/60 HZ) Baaad System Resl Time Clock
(program quest. #07)
Bell Supewiaion -Naw NFPA 72 Requirement
(program quest. #22)
Stay Mode 40 +ec. ~aler Delay w/Bell &Keypad
g:;z; p::!Yp ‘“ ‘ones
Auto Arming in ~fferent Modes
(program quest. #08)
LED Deplay on Entry Zone (always enabled)
Programmable Dialer Attempts: 1-15
(program quest. #09)
LED Extinguish on Keypsds
(program quest, #12)
Keypad Tamper/Lockout
(program quest. #12)
Audible Only
8User Codee: NO Door Strike User Capabiliw
Standard Download Only
Standard Download Only
NONE
Single CS Repoting
Conventional Bell Output Only
NONE
1Enty ~mer
Bell Lockout
Multiple digits required
Alarm Memo~ (cleared by user code)
NONE
CS Test Tmec 1Day Only by Event
NONE
NONE
NONE
NONE
NONE
Restore Follows Bell Only
NONE
NONE
Software Basad Systam Rming
NONE
Stay Mode Ent Delay w/Key ad Sounder
78
Warning for EXI Enty Zones nly
NONE
Sounder Only
Non-programmable 8Dialer Attempts
NONE
NONE
.-
XL-2T Hookup& Installation Manual Page 5

xl -ZT NFW &MODIFIFO ~F4TURFS Xl .7 ml AR FFA TURFS
Separate Fire Trouble &Day Trouble Codes Same Code for both Hre Trouble &Day Trouble
(program quest. #32)
Temporal Bell (program quest. #12) NONE
ACLOW Batte~ Ke pad Sounder Disable
YNONE
(program quest. #12
Dial-Tone Detect ~aler Dialer will not detect dial-tone
(program quest. #13)
Rre Zone Type without Verification NONE
(program quests. #17-23)
Interior Follower Zone Type without Stay Arming NONE
(program queets. #1 7-23)
Chime Trigger NONE
(program quest. #14)
Alarm Reset Trigger NONE
(programqueet. #14)
w
u
XL-2T Hookup& Installation Manuel
Page 6

1. INTRODUCTION
‘a The XL-2T Secutify System is astate of the art microprocessor-based control/communicator it is ahardwired system.
Programming can be performed through the any of the compatible keypada or the system can be uploaded and downloaded
remotely using the EZ-Mate PC Downloader Software, In addition, remote control ,actions (arming, disarming, bypaesing,
etc.) can be peflormed by tha software. Programming options are stored in non-volatile re-programmable EEPROM memory
and that information which has been programmed will not be lost in the event of acomplete Iosa of power. Other features of
the XL-2T include:
.
.
.
.
.
.
.
.
.
@
.
.
.
.
.
.
.
.
,-. .
.
,
.
.
.
*
.
.
7Zones (all fully programmable including Key switch)
15 User Codes (Ambush, Arm Only& Door Sttike Capability)
Keypad Programming and Remote Programming via PC and Modem
UploadlDownload and remote commands with answering machine override capability
3methods of Uploading/Downloading PC operator initiated, Unattended Downloading& On-line Downloading
Optional Built-in 2-Tone siren driver or Conventional Ball Output
Auto Arming at aspecific time of day with capabilfy to arm in either Away, Stay or Instant Modes
Dual Entry Timers
78 Event History Log (Alsrms, Troubles, Low Battery, Bypasses, CS Test, Openings& Closings)
3Emergency Keypad Conditions (Panic, fire& Auxiliary)
2Programmable Trigger Outputs
Raal ~me Clock (Displays ~me &Date via LCD Keypad) with reminder when clock needs to be set
CS Test Tmer by Event, Time or Both (1 Hour, 1,7,27,60, 90 Days)
Customer Control of Chime Mode
Quick Arming, Quick Bypass and Quick Force Arming
CS Repoting by Zone
False alarm prevention features: Cross Zone, Exit Error, Recent Close, Swinger Shutdown Cancel Code &
System Stabilization during power up
Arming by Key switch in Away or Stay Modes
Keypad Tamper/Lockout with optional CS Repoting
Restore Transmission options: After Loop or After Bell
Hre Zone Reset through keypad
Glass Break Reset through keypad
Bell Test, Low Battery Test, AC Loss and Communications Failure
Fuse less design eliminates unnecessary semice calls
Input Powec 12 VAC, 20 VA 12 VDC, 4-7 AH
Output Powec 12 VDC, 500mA
Bell Output Power 12 VDC, 1A
The XL-2T secuflty system is compatible with the following keypads only
JFD STYIFKFYPADS lCDSTYIF~
XL-4800RM 7005
XL-4600SM 7005L
XK406 XK-7LC
6615 XK-5LC
NOTE: The systemsuppotis either the LED keypads listed or the LCD keypads listed. Do not use both types of keypade
in asingle installation.
-
XL-2T Hookup& Installation Manual INTRODUCTION
Page 7

~. SYSTEM WIRING AND HOOKUP
2.1. SYSTEM WIRING DIAGRAM
CONNEC~ONS FOR HOUSEHOLD FIR~URGLAR ALARM SYSTEM (PER UL STANDARDS UL985 AND UL1023)
D=AIL A
YI1
-
SYSTEM STABILIZATION MODE: Upon power up of the system snd after completion of system programming,
IF THE SYSTEM WAS PREVIOUSLY ARMED, sII of the lights on the LED keypsds will go ON momentarily snd
the LCD keypeds will dlsplsy STAND BY! momentarily. THE KEYPAD DISPLAY WILL R~URN TO NORMAL.
HOWEVER, THE ZONES WILL NOT RESPOND TO ALARM CONDITIONS FOR APPROXIMATELY 2MINUTES.
THIS CAN BE DISABLED BY SIMPLY ENTERING AVALID USER” CODE which tiesrms the system end
reduces the power up reset time to approximately 5SECONDS. The 2minute intervsl is used to allow motion
detectors (Interior zones) to stsbilize on power up in order to prevent felse slsrms.
Upon system power ups, IF THE SYSTEM WAS PREVIOUSLY DISARMED, the power up reset time will ~
approximately 5SECONDS.
NOTE: If the total system power is lost, then upon power restorsl, the system will return to the previous
srming state.
w
_
aYSTEM WIRING AND HOOKUP XL.2T Hookup& Installation Manwl
Pags 8

2.2. TERMINAL CONNECTIONS
TERMINALS DESCRIPTION
1(+)& 2(-) Zone 1(Requires 2.2K EOL resietor) [Default =DELAY]
.- 3(+) &2(-) Zone 2(Requires 2,2K EOL resistor) [Default =INTERIOR]
q+) &5@) Zone 3(Requires 2,2K EOL resistor)
6(+) &5@) [Default =PERIMETER]
Zone 4(Requires 2,2K EOL resistor) [Default =PERIMETER]
7(+) &8&) Zone 5(Requires 2,2K EOL reaiator) [Default =PERIMETER]
~+) &8P) Zone 6(Requires 2,2K EOL resistor) [Default =PERIMETER]
lo(+) &8(-) Zone 7(Requires 2.2K EOL resistor) [Default =N.O. PANIC]
ZONE INFORMATION:
Normally closed devices may be wired in series andlor normally open devices
in parallel with the 2.2k ohm end of hne reaiator on all zones (Refer to the wiring
diagram), The standard loop reaponae time is 280 ms on all zones, Each zone
can be programmed for Faat Response (1Oma) in programming (see questions
#17-23). The factory default values for each zone is listed in the table above,
however any zone can be programmed for the following types: Delay,
Pedmeter, Interior, Fire, 24 Hr. Alarm, or 24 Hr. Trouble, Further explanation of
the zone types can be found in the System Programming section of this manual.
NOTE Loop response is defined as the minimum time required for afault to trip
azone,
8&lo
11
12131415
23 (-)&21 (+)
ZONE 7
Defaulted to Normally Open PANIC circuit (no EOL resistor required). This
hardwired panic is a 24 hour zone wtich can be programmed for silent or audbla
operation, The panic circuit will activate with each violation, therefore alatched
device isnotrecommended. Amomenta~device isrecommendad. Thiszone
is fully programmable (aeequeafion #23, 10cationsl &2).
EARTH GROUND
Connect this grounding Iugtoacold water pipe utilizing #18AWG wire at a
distance of no greater than 15 fl. Uae anon-corrosive metel strap firmly secured
to the pipe to which the lead is electrically connected and secured. If the
premiees pipes terminate in PVC, thie terminal muet be connected to asix(6)
foot grounding rod.
KEYPADS:
Amaximum of 4keypads, either XL-4600RM, XL-4800SM, 6615, XK406, 7005,
7005L, XK7LC or XK5LC may be wired to these terminala, The connections are
as follows 12 (BLACK= negative), 13 (YELLOW= data in),l 4(GREEN =data
out) and 15 (RED= positive power). Each keypad dmwa approximately 30mA,
Maximum keypad length is 500 feet using 22 gauge wire. NOTE: In some
installations, itmaybe neceaaary to uee shielded wire to prevent radio frequency
interference.
REGULATED POWER (1 1.5- 13.1 VDC]
The total regulated output power for motion detectors and other external devices
is 500mA at 11.8 -12.5V for residential applications, or 12.0 -12.5V for
commercial applications, with less than 100 mVPP ripple. The total regulated
output ~pacity of the XL-2T includes the power available from these terminals
(21 &23) aswellas thepower uaedbythe keypads and smoke detectors,
Therefore, to determine the total power available from these terminals subtrect
the power consumed by the keypads and smoke detectors. See Auxiliary Device
Current Drew Worksheet,
,-
XL-2T Hoohp &IMtallation Manual eYSTEM WIRING AND HOOKUP
Page 9

TRIGGER #l OUTPUT:
15(+) 16(-) SMOKE OETECTOR POWER: This system will accept 9.5- 12VDC four(4)
wire smoke detectors only. Approximately 50mA of current ia available at these
terminals for powering all detectors and an E.O.L. relay FBllmodel 620. For UL
installations seewitingdiagram forhookup. NOTE: Ttigger#l must deselected
forsmoke detector power (see program question #14, locational &2) if you
want reset by keypad. w
Pl: VBELL (+) TI (-)
These terminals adhere to the fire verification and reset logic which is explained
in the zone typee section of this manual. Manual reset of smoke detector power
can be accomplished by entering aval!d user code aiter clearing a!arm memory
or using the aaterisk ~) key.
TRIGGER #1 OUTPUT P1-VBELL(+) &P1-T1 (-) or terminals 15& 16 can be
used foratrigger #toutput. Seeprogramming question #14, locational &2 for
valid trigger types. NOTE: In order to connect devices to the triggers, use
connector XL-2GTC (trigger ceble). Unless othemiae specified, the trigger
output is normally floating and actively sinks current on activation (switched
negative).
17181920 TELEPHONE LINE:
Connect themode1366 cord as follew$ 17(GREEN=Telco Tp), 18(RED=
Telco Ring), 19(BROWN= Home Tp), 20(GRAY= Home Rng), Inseti the plug
into an USOCRJ31 Xjack (or aCA31 Ajack for Canadian installations).
The FCC registration number is AE398E-69554 AL-E, and the ringer
equivalence is O.OB.The system should not be connected to party Iinea, or coin
operated phones.
Ifthfs control panel will beusedfor uploading, downloading or remote commsnd supplications, theteiephone
fine connected to the control psnel must not be shsred with afax machine or modem. Furthermore, this device
should not kconnected toa phone Iine which hsscallwaitfng, unle~~thecall wai~n9 interruPt numbers are
21 (+) CONSTANT DC POWER:
This terminal delivers constant regulated 10.O-15.5VDC power for devices ~
requiring aconstant power such as VS279. It is connected to abell fuse (F3).
NOTE: Constant power for these devices can also be obtained by apiicing the
RED (+) batie~ lead with an in-line fuse of 3Amps.
BELL OUTPU~
The total output power available for sounding devices is 1amp at 10.5 -15.5
VDC for residential applications, or 1amp at 12.0 -14,4 VDC for commercial
installations (750 mA for UL installations). These terminals will deliver
CONSTANT output on BURGLARY, AUDIBLE PANIC and BELL TEST. On a
FIRE condition, aPULSED output will be generated. There are separate bell
cutoff times programmable for Burglary and Fire conditions within the
programming sequence, For UL Household Hre Warning System installation,
the speaker is required to be mounted indoors for best audibility. Also, for UL
installations, use onlyone speaker. NOTE: Before connecting sounding devices
olease consult their specifications for orooer current draw. Othemise. the bell
!use (F3) maybe blown. An option exists ~osupewise the bell output terminals
if zone 6ia programmed as a fire zone (see program questions #17-23); refer
to the following notes:
BELL SUPERVISION (Mechanical Bell )-To meet the NFPA 72 requirement
program zone 6 aa a Fire Zone (program question #22, Iocstions 1&2).
The bell is then supewised for an open circuit (not ashoti circuit) across the
bell output terminals; the keypad will indicate that aFire Trouble condition has
occured and Fire Trouble is repofled to the CS if enabled (program question
#32, location 3). If the bell is already tinging, the supewision will not take effect
until after bell cutoff time. See the diagram on the next page
‘-
SYSTEM WIRING AND HOOKUP XL-2T Hookup& Installation Manual
Pags 10

Bell OutP”t Mschanlal Bell
.—
SIREN SUPERVISION (Self Contained SireWSpsaker
72 requirement program zone 6 as s Fire Zone (prl
location 1). The eiren is then supervised for an open cir(
ecross the bell output teminals; the keyped will indica
condition has occured end Fire Trouble is repotied t(
program question #32, location 3). If the siren is a
SUPeWISiOnWillnot take effect until afier bell cutoff time, N
ZR-815C, ZR-815EC or ZR-830EC. See the diagram be
-To meet the NFPA
ram question #22,
it (not ashort circuit)
that aHre Trouble
:he CS if enabled (
?ady sounding, the
rE: Use FBII models
w:
SPEAKER SUPERVISION (VS-299 Siren/Driver) -To supervise aspeaker
connected to the VS-299 Siren Driver connect terminal 1of the VS-299 to the
oositive terminal of anv zone oroorammed as a 24 Hour Trouble zone
{program questions #17”- 23, Iocafifis 1&2). The speaker is then supervised
for an open circuit across the epeaker terminals (4 &5) of the VS-299 and a
code is reDOtied to the CS if enabled iDrooram auestion #24-27, Iocatione 3&
4). Also, the connection between the bell ofitput terminals and the VS-299 Siren
Driver may be supervised by programming zone 8 as a Fire Zone (program
question #22, Iocstlons 1&2) and connecting e10K Ohm, 1/4 Wresistor
acrosa the ball output terminsls to prevent acontinuous supawisoW
oondkion. Sss the diagrsm below
+P=soh
revents Contln ...s Supew,soW Contitio”
Positive (+) @24Hour Trouble Zone
SPEAKER SUPERVISION (879S Sire~river) -To supewise aspeaker
connected to the 679S Siren Diver connect a5.6K Ohm resistor bs~asn
terminal 5of the 679S and terminal 9(+) of zone 6programmed as a Fire
zone (program queafion #22, Iooations 1&2). Replace the 2.2K Ohm EOL
resistor on zone 6with a5.6K Ohm reeistor. The speaker is then supervised for
an open circuit (not ashort circuit) ecroes the speaker terminals (4 &5) of the
679S. Also, the connection between the bell output terminals and the 679S Siren
Driver will be supervised. If asupewisory occurs, the keypad will indicate that
aFire Trouble condition has occured on zone 6and fire Trouble is repofled to
the CS if enabled (program question #32, location 3). If the siran is alraady
—sounding, the supewision will not take effect until after bell cutoff time, See the
,— diagram-on the rieti page:
XL-2T Hookup& Installation Manual eYSTEM WIRING ANO HOOKUP
Pags11

RePk- 2.2K EOL w/5.6K
Zone 6Programmed
a, fire 20”.
-
=(+) @10,3
Bell Ouwti
~c) @
2
24& 25 TRANSFORMER:
Connect the 1240A (12VAC, 20VA) transformer, utilizing 18awg wire at a
distance notto exceed 15 feet from the panel, to an unstitched 120 VAC outlet.
Do not use any other transformer since this may result in improper operation or
damage to the unit.
The AC/LOW BAT LED on the keypad will remain ON while AC power is present.
If an AC loss occurs the AC/LOW BAT LED will turn off immediately. If AC
remains OFF for 15 minutes, the system will pulee the k,eypad buzzer and
transmit to the central station, if programmed. THE KEYPAD BUZER CAN BE
SILENCED by entry of any valid user code. Whan AC restores the AC/LOW
BAT LED will light immediately, and arestore code will be reportad, if
programmed.
BACKUP SATTERY The RED(+) and BLACK(-) flying leads must be connected to a 12 VDC 4-8AH
GELL CELL, to serve as backup power in the event of AC loss.
Abattery test occurs approximately every 4.5 minutes. Low battery condition
occurs at nominal llVDC. The keypad AC/LOW BAT LED and buzzer will .-,
PULSE SLOWLY when alow battery condition is detected. The system reports
this condition to the CS if programmed. Battery restoral will occur WITHIN 4.5
minutes, at the NEXT battery test. THE BUZER MAYBE SILENCED by entry
of any valid user code.
GROUND STARE Ground stafl capability can be added to tha system through addition of the FBI I
Modal 117 module. Coneult the 117 Installation Instructions for hookup
information. With this device some systems can obtain dialtone where it is not
available. At the moment telephone line seizure occurs, the Telco TIP is
momentary connected to earth ground to access dial tone. NOTE The 117
module haa not been tested for use in UL installations,
Pl: VBELL, TI &T2 TRIGGER OUTPUTS (1 &2):
SYSTEM WIRING AND HOOKUP XL-2T Hookup& Installation Manual
Page 12

2.3. AUXILIARY DEVICE CURRENT DRAW WORKSHEET
XL-4600RMKeypad 30mA.
XL.4600SM Keypad 30mA,
XK5LC 65mA.
XK7LC 66mA’
7005 65mAS
7005L I65mA, II
6615 Keypad 60mA.
Dtm I.. I I I
1,,. .
SmokeDetector .. I
GlassBreakDetector ..
Other ., I
,, I
NOTE: ‘Only appliea if device is powered from control terminals 21 (+) &23 (-).
“If using hardwired devices such as PI Rs, smoke detectors, etc., refer io the specifications for that pafiicular
device’s current draw. If the total current draw exceeds 500mA, then use an additional power supply.
2.4. WIRING INFORMATION FOR KEYPADS ~OTHER DEVICES
KEYPADS &OTHER If single or multiple devices are connected to asingle 4-wire or 2-wire run ~daisy
DEVICES chained”) to the control terminals, determine the current drawn by the unit(s)
connected to the single wira run, then refer to the Wiring Run Table below to
determine the maximum wire length that can be safely used for each wire size.
Examples
1
In some cases, the total current drawn may result in avalue not shown in the
table. For example, ifyou plan to usa #22 gauge wire and the total current drawn
is 400 rmA(a value between 300 mA and 500 mA), the maximum wire Ieng!h
you should use ia approximately 65 ft. (a length between 50 and 60 ft.). Other
maximum wire lengths for values of current not shown in the table can be
calculated in asimilar manner.
Maximum wire Iengthe for adevice that is “homerun” to the control can
also ba determined from the table, baaed on the current draw of thet device
alone.
What is the maximum distance for 1XL-4600SM keypad drawing 30 mA using # 20 gauge wire?
Usin the table above, the keypad can hplaced no greater than 750 ft. away from the
7pane.
2. What is the maximum distance for 3keypads (one XL4600SM &two 6615) drawing 150 mA (30mA +60
mA twice) using # 20 gauge wire connected in asingle wire run?
Usin the table above, the farthest keypad can be placed no greater than 300 ft. away
?
from he panel.
3. Whet is the maximum distance for 5smoke detectors drawing 0,25 mA (5 microA each) using # 22 gauge
wire connected in asin Ie wire run?
8
Using the ta /e above, the farfheat smoke detector can be placed no greater than 500 ft.
away from the panel.
XL-2T Hookup& Installation Manual SYSTEM WIRING AND HOOKUP
Page 13

3. PC Board Mounting
3.1. Mounting the XL-2T PC Board
Before mounting the circuit board, be certain that the appropflate metal knockouts have been removed. u
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS ARER THE CIRCUIT BOARD HAS BEEN INSTALLED.
1. Hang the three mounting clips on the raised cabinet tabs. Obaewe propar clip orientation to avoid damage to the clip when
mounting screws are tightened and to avoid problems with inseflion and removal of the PC board.
2. Insefl the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests in the slots as
indicated in tha diagram shown below.
3, Swing the base of the board into the mounting clips. Secure the board into the catinet with the accompanying screws
OFCLIP INSTALLATION: REQUIRED D=AIL S=VIEW
A.CABINW TAB OFCLIPANDBOARD
WITHOUTCLIP INSTALLED
B. CABINETTAa
WITHHANGING
CLIP
NOTE The front face of the enclosure san be completely removed from the enclosure to gain unrestricted
control panel during installation. The front of the enclosure cen be removed es follows:
1) Open the encloeure to ite fully emended position (approx. 90 degrees)
2) Lift the control panel door and remove the door from the enclosure.
tothe
u
PC BoBrd Mounting XL-2T Hookup& Installation Manual
Pa= 14

4. KEYPAD MOUNTING
-4.1. XL4600RM METAL KEYPAD
FLUSH MOUNTING USING DOUBLE GANG BOX
0’
‘. ‘.
... ..,,
‘...., ....
.... .....
... ...
... .....
.... ....
D
a@
::: ❑mmg
.. ... :::. ❑mmQ
..........
...... ;.- ❑ama
...... •mm~
...........
@@
l-Create an opening and mount aatandard double
gang box.
2- Secure keypad to double gang box as ehown in
diagram below. NOTE: Thedouble gang box should
be mounted flush with the wall in order for the keypad
screws to fit,
NOTE For UL installations, mount the XL4600RM to
an earth grounded outlet box.
FLUSH MOUNTING WITH MOUNTING RING (Ueing the XL4600TR)
In. .n?...
h.....
.....
....
...
....
......
-...
... ,m
-““’’’’’’--..=
SURFACE MOUNTING (Using optional XL4600RMBX)
MOUNTING KEYPAD INCONTROLPANEL ENCLOSURE
1. Create the desired opening where keypad is to be
mounted, using the ineide of the mounting ting asa
template, NOTE: This opening should be made
between studs.
2- Secure mounting plate to wall through the four outer
holes using suitable mounting hardware (not
provided),
3- Connect keypad wiring to control panel and secure
the keypad to the mounting ting using the four painted
screws provided.
1- Depending on type of installation run the keypad
wiring out of the rear, top bottom or sides of the
backbox,
2- Attach backbox to wall at desired height
3- Insert XL4600RM keypad into backbox and secure
with the four screws provided.
1- Remove keypad knockout from front of metal box
enclosure as shown.
2- Insert XL4600RM into opening from front of
enclosure.
3- Secure keypad to enclosure using the four painted
metal screws and nuts provided.
XL-2T Hookup& Installation Manual KEYPAD MOUNTING
Page 15

4.2. XL-4600SM KEYPAD
The XL-4600SM Keypad maybe surface mounted in the following ways:
A. Directly to acontrol panel having akeypad cutout on the front of ita enclosure
B. Directly to asingle or double gang electrical junction box.
C. Direct~ to awall or other surface.
[EARPLATE
LALOTFORCOVERSECURINGs EW
‘0’’’0””) J
COVERPRV4FFSWS (2)
VOREMOVECOVER,INSERTSMALL
SCRWDRIVERB~OEANDWIST.)
~agrem 2: eO~OM VIEW OF KEYPAD
Oiagram3REAR MOUNTINGPLA~
1. Remove the keypad cover aasembly from the rear
mounting plate. Insefl asmall screwdriver blede in the
COVER PRY-OFF SLOTS at the lower edge of the
keypad (see I>iagram 2)and twist to pry off the cover
aaaembly.
2, Mount the rear plate (see Diagram 3).
Note: The plate is correctly oriented when its pat
number, molded into the plaatic, is upright.
A. MOUNTING DIRECTLY TO CONTROL PANEL
ENCLOSURE:
If the control panel haaakeypad cutout on the front
face of its enclosure, remove the cutout and mount the
plate to the enclosure’s face via HOLES “A (see
dagram 3) alqd the four screws and nuts provided.
Note: Certain snack-proof enclosures are not provided
with akeypad cutout.
B. MOUNTIIVG DIRECTLY TO AN ELECTRICAL
JUNCTION 130X:
The plate earl be mounted directly to asingle or double
gang electrical junction box. Use the screw holes
provided and HOLES “B” for asingle gang box or
HOLES “A for adoub!e gang box.
C. MOUNTING DIRECTLY TO AWALL OR OTHER
SURFACE
Provide awiring hole in the mounting sutiace. Position ‘u
the plate’s WIRING OPENING over the hole and
mounting plate, using HOLES “A and/or “B” in
conjunction with appropriate mounting hardware (not
provided) for the type of surface.
3. Complete the keypad wiring as required for the
control with which the keypad is to be used.
4. Replace the keypad cover assembly on the rear
plate, Stafiing at the upper edge of the plate, engage
the plate’s two HOLDING HOOKS (see diagram 3) into
the recesses provided for them inside the upper edge
of the cover aaaembly and snap the lower edge of the
cover assembly and snap the lower edge of the cover
onto the two SNAP HOOKS at the lower edge of tha
plate.
Note (Optional) If desired, cover and plate can be
further secured together by inserting ascrew
(provided) into the SLOT at the keypada lower edge.
NOTE When autiace mounting the keypad, and using screws with heads Iarg<?rthan the screws provided with the unit,
place electrical tape over the screws to prevent them from intetiering with the keypad operation. In the future the back plate
of the keypad will provide additional counte~inking for screws with larger heads.
‘-
KEYPAD MOUNmNG XL-2T Hookup& Instslltion Manual
Page 16

4.3. MOUNTING 6615 KEYPADS
Keypad mounting is identical for both the 6615 LED and XK-406 or LCD keypads. NOTE: After mounting an LCD Keypad
at eve level, vou can adjust the display intensity level to suit the user by adjusting the intensity control located behind the
,- keypad door.”
SURFACE MOUNTING
\
‘ . ~b &@
o@
...........-..m..-..m..- ......l
\
RECESSED MOUNTING
~5’3’lc~,
(15 cm) T
(10 cm) 4‘“
1
2i
1. Select amounting location and place the rear plate
of the keypad on the wall. Mark the location of the
cutout for the keypad wiring cable.
2- Create akeypad opening Connect the kaypad
wiring to the control panel w/ 4-wire connector.
3- Place the keypad wiring through the cutout and
secure the back plate to the wall (see diagram).
4- Connect the keypad wiring connector to the keypad
and place the keypad on the mounting plate attached
to the wall.
5- Secure thekeypad to the rear mounting plate by
attaching the 5/8 inch screw provided in the lower hole,
located behind the keypad door,
1- Select amounting location. For recessed mounting
this must be between two stude. The rear mounting
plate is not used for recessed inatallationa.
2- Create an opening in the wall exactly 4inches high
by 513/1 6inches wide.
3- Turn over the keypad and remove the P~llips head
screw (iteml ondiagram) intheupper leff hand side
of thekeypad printed circuit board. Note: This screw
ia located immediately to the left of the keypad
connector.
4- Attach the black metal mounting strap to the rear of
the keypad as follows (see diagram);
-Face the pointed end of the mounting strap facing the
keypad front. This will be used to latch onto the inside
of the wall.
-Place the small white plastic spacer underneath the
mounting strap. Secure the mounting strap using the
5/8 inch Phillips head screw (supplied) and the plastic
spacer to location 1.
-Secure the other end of the strap (location 2on
diagram) to the white plastic opening using the Phillips
head screw removed in step 2.
5-Connect the white plastic tab into the round opening
immediately behind the kaypad door. Place the longer
Phillips head screw flncluded) through the opening
inside the keypad door and bagin to tighten the ecrew.
Tighten the screw and leave the tab in adown poaifion.
6- Run the keypad wiring to the control panel and
attach the wiring to the keypad.
7- Place the keypad into the wall opening with the aide
containing the black metal strap first until it graba the
inside of the wall.
8- After inserting the eide of the keypad with the metal
strap, insert the other side into the opening unfil the
entire keypad ia firmly in the wall.
9- Tighten the screw inserted in step 5.
XL-2T Hookup& Installation Manual KEYPAD MOUNTING
Page 17

5. KEYPAD LAYOUT
3\ 2\
-7
-8
-9
-lo
?.. —.
141151161[COWR I
1711,
UL
xL.l~600sM KEYPAD
~ ~ XL-4600RM KEYPAD
.3,4,5< . . ... . . . . ...\.
—-.
--.-..—. .--— \
5615 KEYPAD S
1) ZONE STATUS LEDS
These LEDS display the current zone status including alarms, bypasses, troubles and faults. Each condition will cause these
LEDS to operate differently aa follows
ALARMS Fast Blink (approx, 150 ms, ON -150 ms. OFF).
TROUBLES Slow Pulse (appmx. 600 ms, ON -600 ms. OFF),
BYPASSES Wnk(100 ms. ON -900 ms, OFF). Zone bypasses are displayed as a very slow wink of the zone
LED light,
FAULiED ZONES Sohd ON. Faulted zones are the lowest priority indication, Faulted burgla~ zones are
displeyed with the LED solldly ON while the system is disarmed.
NORMAL OFF
NOTE: Upon Entry to dissrm the system the keypsd eounder will annunciate to warn the user to disarm it. In
adrfiton, the respective zone LED(s) will kON to indicate zonee which are violeted (ex ent~ door and
motion detector).
KEYPAD LAYOUT XL-2T Hookup& Installation Msnua[
Pags18

2) AR~lSARM LED
This LED indicates whether the system is currently armed (ON) or disarmed (OFF).
Fast Blink Alarm Mode
Slow Wink Fail to Communicate with Central Station
3) STAY LED
This LED displays whether the system has been armed in the STAY mode or the STAY/lNSTANT mode, If the INSTANT
LED is ON and the STAY LED is ON, then the system is in the STAY/lNSTANT mode. If the INSTANT LED ie OFF and the
STAY LED ie ON, then the system IS in the STAY mode only. STAY/lNSTANT is enabled in programming question #12,
location 3. In either mode the STAY LED indicates the following:
ON Interior zones are bypassed
OFF Interior zones are normal
4) INSTANT LED
This LED displays whether the system has been armed in the INSTANT or STAY/lNSTANT mode, meaning that the system
is currently armed, all delay zonas are instant and all interior zones are bypassed. If the STAY LED is OFF and the INSTANT
LED is ON, then the system is in the INSTANT mode. If the STAY LED is ON and the INSTANT LED is ON, then the ayatem
ie in the STAY/l NSTANT mode. NOTE: See programming question #12, location 3.
ON ‘Delay zones are currently instant
OFF Delay zones are normal
5) AC/LOW BA~ERY LED
Thie indicator light displays the current power status of the panel as follows:
ON AC is present
OFF No AC, running on battery backup
Slow Blink Low banew condition detected
6) READY LED
This LED dieplaye whethar the system is ready for arming, The READY light is common to all BURGLARY ZONES with the
following indications:
ON System ready to be armed
OFF System not ready to be armed
Slow Blink Indicates Installer programming mode
Fast Blink Alarm Memory Mode
7) STAY BU~ON
The STAY bunon enables arming the system, excluding zones programmed as interior zones. TMs will provide extarior
protection of the lo~tion while allowing full access throughout the interior.
8) BYPASS BU~ON
The BYPASS button is used to temporarily exclude protection to aspecific zone.
9) INSTANT BU~ON
If enabled, the INSTANT button enablea arming the system in the INSTANT mode and with the STAY bunon it enables arming
the eystem in the STAY/lNSTANT mode. NOTE INSTANT mode is enablad inquaetion#12, location 3.
10) CODE BU~ON
The CODE button is usad to enter the inetailer programming mode and ent~ of user codes.
11) LCD DISPLAY (7005, 7005L, XK7LC, XK5LC KEYPADS ONLY)
Tha LCD display chows the current status in atw- line by sixteerl character format.
12) KEYPAD AUXILIARY KEYS (XL*OOSM KEYPADS ONLY)
Pressing the WO keys (top& boftom) Iabalad “F,” “A,’ror “P at the same time initiates aCS tranemisaion, if programmed, of
PANIC, AUXILIARY or FIRE, annunciates the keypad sounder and turns on the bell output. If not programmed to transmit,
these keys can only reeult in alocal warning as follows (eee question 07, location 3):
Keypad Souder -Steady for PANIC, Pulsing for FIRE and AUXILIARY
Bell Output -Steady for PANIC, Puleing for FIRE
NOTE See the Keypad Emargency Conditions section for alternate auxiha~ keys.
XL-2T Hookp &Installation Manual KEYPAD LAYOUT
Page ie

5.1. KEYPAD SOUNDER
The keypad sounder annunciate differently to indicate the following conditions
CHIRP -Keypad sounds ashort chirp to confirm each keystroke.
STEADY -The keyped will make asteady sound during entry time, and/or during burgla~ alarm.
CHIME -steady 1second tone (SYSTEM DISARMED ONLY). w
ACKNOWLEDGE -Upon successful entry of acetiain commands the system will sound for approximately half
asecond.
PULSING -Auleing sound approximately half asecond ON then OFF) indicates atrouble condition such as
8$
AC loss, Low affery, or Fire one.
NEGATIVE ACKNOWLEDGMENT -Upon entry of an illegal cOmmapd the keYPad will aOund four shOfl beePs.
For example, if affem fing to define anew user and the master user IS not tmtered, four short beeps WIII be
f
made Indlcatmg that he command was unsuccessful.
SOUNDER RING BACK -Several short bee S,to indicate successful cOmmunicatiOn to the Central Station This
$
occurs for all signale, excluding ambush an silent zones.
FAST PULSING SOUNDER- Sound enerated dufl.ng entv time period AFTER an alarm cOn~~On h??
occurred and,the system reached bel?cutoff. Apulamg sounder w!II follow tile bell output on Fire condlbona.
Trouble condlbons also generate apulamg sounder and maybe silenced through entry of avalid user code.
NOTE: The keypad Ie non-operational If none of the LED’e are Ilt and the keylpad does not beep when keys are
pressed. This Is an Indication that sewice is required. Coneult tha troubleahhoting section of this manual.
KEYPAD LAYOUT XL-2T Hookup& Installation Manual
Page 20

6. SYSTEM OPERATIONS
6.1. POWER UP/SYSTEM RESET
SYSTEM STABILIZATION MODE: Upon power up of the system and after completion of system programming,
IF THE SYSTEM WAS PREVIOUSLY ARMED, sII of the Iighte on the LED keypsde will go ON momentarily and
the LCD keypada will display STAND BY! momentarily. THE KEYPAD DISPLAY WILL RETURN TO NORMAL.
HOWEVER, THE ZONES WILL NOT RESPOND TO ALARM CONDITIONS FOR APPROXIMATELY 2MINUTES.
THIS CAN BE DISABLED BY SIMPLY ENTERING AVALID USER CODE which diearms the ayatem and
reduces the power up reset time to approximately 5SECONDS. The 2minute interval ia uaad to allow motion
detectors (interior zones) to atabifize on power up in order to prevent false %Iarma.
Upon system power ups, IF THE SYSTEM WAS PREVIOUSLY DISARMED, the power up reset time will be
approximately 5SECONDS.
NOTE: If the total ayatem power la Ioat, then upon power restoral, the eyatem will return to the previous
arming afste.
6.2. ARMING THE SYSTEM
The system can be armed only if all burglay zonee are good (not faulted) and the READY LED is on, LCD keypads will
contain the SYSTEM READY indication,
~~ ARM: Enter any programmed kdigit user code, NOTE: The factoy default for user # 1 is 1234,
The ARMED LED will light and the user may axit through an exitienty zone for the time paried programmed as the exit delay.
The LCD keypad displaya “ON: AWAY on the first line for the duration of the exit delay displaying. The system can be armed
without the backup battey being connectad, howevar the AC/LB light will flash,
LCD keypada will dsplay
~
6.3. STAY ARMING
To ARM: Press the STAY key followed by a4-digit user code.
This will arm the system with all programmed interior zones and related points excluded.
KFYPAD RFSPOw
LED KEYPADS STAY =ON; ARM= ON; RDY =Slow Pulse
LCD KEYPADS
~
6.4. INSTANT ARMING
TO ARM: press the INSTANT key and a~digit user code.
The INSTANT mode will arm the system with all programmed exitientry zones as instant,
KFYPAD RFSPO~
LED KEYPADS INSTANT =ON: ARM =ON; RDY =Fast Blink
LCD KEYPADS
m
NOTE: The INSTANT mode can ba enabled through programming question#12, location 3
XL-2T Hookup &Installation Manual SYSTEM OPERATIONS
Page 21
Other manuals for XL-2T
4
Other FBII Control Panel manuals
Popular Control Panel manuals by other brands

Balboa Water Group
Balboa Water Group TP500 user guide

Zonefirst
Zonefirst BPE Installation and operating instructions

Siemens
Siemens SINUMERIK 802D sl Programming and operating manual

Extron electronics
Extron electronics SCP 100P user manual

Biamp
Biamp Apprimo Touch 8i Installation and operation guide

Honeywell
Honeywell W-MMF Installation and maintenance instructions