Feelsafe OMNI 3000 Installation manual

0
tructions
SEPT '86.
F&Safe, Inc., 50 Engineers Road, Houppauge. New York 11788
(516) 5826161 (803) 6455430
Copyright @ ‘85 FeelSafe. Inc. Printed in U S.A.’

; r; ’ 4’
..
..’ Many of-the panels functions including zone types and operations, audible or silent outputs.,
etc. are prom programmable. Therefore, it is imperative that these instructions are read
and followed very carefully. Many of the options available will require programming in
several different locations of different fields. It is advisable to utilize the BLANK
PROGRAMMING SHEET MARKED WITH-LOCATIONS (Ll, L2, etc.) to write out the entire
program before attempting to actually program. The first and MOST IMPORTANT decision
which must be made prior to programming is what each of the 12 general purpose zones are
planned to be. There are several options such as 24 HR ALARM ZONES, 24 HR TROUBLE
ZONES, or CONTROLLED ZONES (Delay, Instant, Interior).
110 Programmer Switch Setting:
.‘MODE SWITCH QUADRANT SW. 8
North South
North South
North North
North North
,
QUADRANT SW. 7
South
North
South
North
QUADRANT
SELECTED
1
2
3
4
I
R96 Quad Selection Jumper Setting 1
2 Quad Program 4 Quad Program
Quad 1 h 2 Connected Connected
Quad 3 & 4 cut
,
It will be necessary to program on at LEAST (2) quadrants of the prom chip for
operation of this system. Either quadrants one and two or quadrants three and
four may be used. The condition of resistor R96 in the OMNI 3000 system dictates
which two quadrants of the prom will be used. It may be necessary to do a four
(4) quadrant program on installations which require advanced communicator features. .
The charts above explain the appropriate 1210switch settings versus the correct condi-
tion of the .R96 resistor in the system.
THE INSTRUCTION MANUAL IS DESIGNED TO ACCOMPLISH WRITING OUT THE
OMNI 3000 PROM PROGRAMMING SHEET 12260 ON PAGE 16. CONTROL PANEL HOOKUP
AND WIRING INFORMATION CAN BE FOUND IN INSTALLATION INSTRUCTION 12258.
STEP 1: QUADRANT 1, OP FIELD
This OP FIELD locations Ll-Lll can be used to program a common
telephone number prefix. (example: 9, 1,800 etc.) All digits pro-
grammed here will be dialed prior to any and all receiver telephone
. . numbers programmed. .
STEP 2: L! FIELD
‘LOCATIONS Ll-Lll in this field must be used to program the telephone
number of the first receiver- As many as eleven (11) digits can be programmed.
I

, STEP 3: 2P FIELD
. LOCATIONS Ll-Lll can be used to program the telephone number of the
second receiver. As many as eleven (11) digits can be programmed. If
there is no second receiver, leave this field blank on
the
program sheet.
STEP 4: 3P FIELD
LOCATIONS Ll-Lll can be used to program the telephone number of
receiver three. As many as eleven (11) digits
can be programmed.
If
there is no third receiver, leave this field blank on the program sheet.
STEP 5: AF FIELD
THE FIRST LOCATION of this AF field marked Ll is used to program the
number of attempts the
OMNI 3000
system should make in the event
the receiver or receivers are busy. Select a digit from the following chart
as desired.
.
// OF ATTEMPTS DIGIT // OF ATTEMPTS DIGIT # OF ATTEMPTS DIGIT
1 1 7 7 13 D
2 2 8 8 14 E
3
3 9 9
15 A
4 4 10 0
* 1 Unlimited F
5 5
I1 B 1
6 6 12 C
THE SECOND LOCATION of this AF field marked L2 is used to deter-
mine two (2) things concerning the receiver format. The first thing is
whether the
OMNI 3000 system should transmit all its data to just the first
receiver (ANY ONE RECEIVER) or will it be necessary to transmit to
ALL RECEIVERS assuming there is more than one telephone number
programmed. The second thing which must be determined in this location
is whether all transmissions io the receivers should be PRIORITY REPORT,
STANDARD FORMAT, OR EXTENDED FORMAT. Priority report means
that if more than one circuit is tripped within the same phone call to the
central office, ONLY THE HIGHEST PRIORITY circuit will be reported
(example: Fire and Burglary trip, only Fire is transmitted). Priority report
should be programmed for receivers which can not handle multiple codes
within the same
phone
call. STANDARD FORMAT means all circuits which
are tripped within the same phone call will be reported to the central office.
EXTENDED FORMAT is similar to the standard format in that all circuits
tripped.will be transmitted to the central office, however, extended format
involves an advanced form of dialer communication.
EXTENDED FORMAT is explained.in the
OMNI 3000 ADVANCED
COMMUNICATION MANUAL. Do not select this format without a full
underz&nding.
2

QUAD 1 ,AF FIELD CON’T.
SELECT A DIGIT FROM THE FOLLOWING CHART FOR THE OPTIONS
DESIRED IN THIS L2 LOCATION.
. DIGIT
0
1
b 2
4
5
1 6
f
FUNCTIONS
any one receiver, priority report
any one receiver, extended format
any one receiver, standard format
all receivers , priority report
all receivers, extended format
all receivers , standard format ,
STEP 6: FF FIELD
Select a digit from the following chart for each of the receiver types for
each telephone number programmed. Ll location of this field corresponds
to the receiver at phone number one (1). L2 and L3 correspond to the re-
ceivers at phone numbers (2) and (3) respectively. If only one receiver is
being used,, leave locations L2 and L3 blank.
NOTE: ALL RECEIVERS MUST HAVE A KISSOFF TONE.
DIGIT
RECEIVER TYPE
0 FBI, Radionics 2300hz, 2Opps w/parity
1 FBI, Franklin, Sescoa, DCI, Radionics 2300hz 2Opps, Osborne Hof.Quika
2 FBI, Radionics 1400hz 2Opps w/parity
3 FBI, Adcor CDRSO, Radionics 1400hz, 20~~s..
5 FBI, Ademco
7
FBI,- Silent Knight (slow)
8 FBI, Radionics 2300hz 4Opps w/parity
.STEP 7:
C’
AC FIELD
LOCATIONS Ll-L4 must be used to program a three (3) or four (4) digit
SUBSCRIBER ACCOUNT CODE. A Four digit account code can be used
ONLY if the receiver is capable of handling it.
J I
-.
3

STEP 8: AL FIELD
This AL field locations Ll-Lll must be used to program the DESIRED ALARM
CODES for all zones listed from the chart below in all the respective locations.
Zones one (1) through five (5) can all be. programmed to report separate alarm
codes. Zones six (6) through twelve (12) will ALL REPORT THE SAME ALARM
CODE. Program an (F) in the locations of all zones which are NOT desired to
transmit to the central office. Program an (F) in the respective locations of all
zones which will be programmed as 24 HR. TROUBLE ZONES. Program location
Lll, (F) until reading the ADVANCED COMMUNICATION MANUAL.
LOCATION DESCRIPTION CODE
_-..._
Ll Keypad AMBUSH o-9
L2 Keypad PANIC o-9
L3 Keypad Medical o-9
L4 Fire Zone Alarm Code o-9
LS Zone 1 Alarm Code o-9
L6 Zone 2 Alarm Code o-9
L7 Zone 3 Alarm Code o-9
L8 Zone 4 Alarm Code o-9
L9 Zone 5 Alarm Code o-9
110 Zone 6- 12 Alarm Code o-9
Lll Always F Always F
QUADRANT ONE HAS BEEN SUCCESSFULLY FILLED OUT AT THIS POINT.
Step 9: QUADRANT 2, OP FIELD
This OP Field Quadrant two (2) can be used to program several of the
communicator codes including CLOSING/OPENING, ZONE BY PASS/TROUBLE,
and THE COMMON TROUBLE CODE. The closing/opening codes which are
programmed here will be reported when ANY of the eight (8) Users of this
system ARM/DISARM. The Zone Bypass/Trouble codes which are programmed.
in locations L4-L8 for zones one (1) through five (5) can actually be two dif-
ferent things depending on the zone types. If any of zones one (1) through five. _
(5) -are programmed to be burglary zones, (delay, instant, interior) these codes
will be reported to the central office as BYPASS CODES. If any of zones
ttio (2) through four (4) have been programmed as 24 HR. TROUBLE ZONES,
these codes will represent the actual ALARM CODES for those zones. Program’
an (F) in the L9 location of this field because zones six (6) through twelve (12)
cannot transmit a bypass code. Program a code in the LlO location that will be
transmitted whenever the COMMON TROUBLE ZONE senses a violation. The

common trouble code will be transmitted on FIRE TROUBLE, LOW BATTERY,
OR AC LOSS (FOR 90 SECONDS).
SELECT THE DESIRED CODES FOR ALL ZONES FROM THE FOLLOWING CHART
IN ALL THE CORRESPONDING LOCATIONS.
QUAD 2, OP FIELD
For English Language Printout of Codes Use:
A _-______ - ________________________
Trouble
B ___-------------------------------- Opening
C --- ___-- ___________ - _____-
Closing
I
STEP 10: QUADRANT 2,1 P FIELD
In this field select the RESTORE CODES for all the zones in the event a
restore on abort or standard restores are desired. The ABORT CODE and
24 HOUR AUTOMATIC TEST CODE is programmed in this field if these
ootions are desired. SONALERT RINGBACK, and AUTO UNBYPASS zones l-5
are the final options which .are selected in the LlO location of this field. Select
one code per location Ll-L9 (as desired). If any of locations Ll-L9 are not de-
sired, program an (E). Then complete LlO and Ll 1 locations.
_ . .

’ SELECT THE DESIRED CODES FOR ALL LOCATIONS FROM THE FOLLOWING
. CHART
QUAD 2, .lP FIELD
For English Language Printout’ use: E ------ Restore
D --- Abort
STEP 11: THE TENTH LOCATION in this 1P field marked LlO determines several
of the following options: (A) SONALERT RINGBACK: Sever’al pulsing tones from
the Keypad Sonalert whenever the Central Office receives a successful dialer trans-
mission. ALL transmissions will have ringback unless otherwise specified. (B) AUTO
UNBYPASS: If any controlled zones one through five are bypassed at the OMNI
3000R Keypad, they will automatically be unbypassed UPON DISARM, if there had
NOT been an alarm condition on any other zone while the system was armed. Other-
wise manual unbypassing must be done after disarming. Select a digit from the follow-
ing chart for this LlO location.
DIGIT Sonalert Ringback Automatic
. Unbvpass
A NO NO
B YES NO
E
NO
YES
F YES YES ..,
THE ELEVENTH LOCATION marked Lll MUST be programmed “F”.

STEP 12: QUADRANT 2,ZP FIELD
THE FIRST LOCATION in this 2P field marked LI will determine what the FIRE ZONE
will do in the event that it IS aborted. An abort on this zone is accomolished bv de-
pressing the keypad
q
.button BEFORE THE FIRE ALARM CODE reiches the’cen-
B tral Off ice. Select one of the following Digits for the Ll location. If this Fire Zone
is not used program a D in this location.
1 DIGITS 1 FIRE ZONE OPERATION
ON
ABORT
I
C No abort
D Stop dialinn on abort
E Restore code on abort
1 F Abort Code on abort
?HE SECOND THRU SIXTH LOCATIONS in this 2P field marked LZ-L6 correspond to zones
l-5 respectively. One digit from the following chart MUST be
programmed for each of these
zones in their specific locations. These locations determine two things for each of the zones;
(A) Zone TYPE and (B) What reaction should take place in the event the subscriber
violates a zone and immediately thereafter attempts to abort the dialer transmission
(eg. because the initial trip was accidental.) There are several different zone types
as-follows: (1) CONTROLLED DELAY OR INSTANT which are standard Burglary
Delay or Instant. (2) INTERIOR which. is a special burglary zone whose operation is
.fully explained in the OMNI 3000 Hook-up and Installation Manual. (3) 24 HR ALARM ZONES
which will transmit whenever violated independent of arm/disarm, and can be prc+
grammed to sound the Burglary Siren output. (4) 24 HR TROUBLE ZONE which will
also transmit whenever violated independent of arm/disarm, and can sound the Keypad
NOTE: AUDIBLE 24 HR ALARM ZONES, can be aborted by momentarily depressing
the Keypad [#I BUTTON. 24 HR TROUBLE ZONES, SILENT 24 HR ALARM
ZONES, can be aborted by not maintaining the violation on their terminals.
Controlled zones can be aborted by disarming the system. Abort action
MUST take place prior to the ALARM CODES transmission of these zones
reaching the Central Office.
NOTE: If any of these zones are not used, program a 5 in their location.
NOTE: Zone 1 and zone 5 cannot be programmed as a 24Hr. Toubie Zone, or 24Hr. alarm zone.
QUAD 2, 2P FIELD

: *
0,. -.
THE SEVENTH LOCATION of this 2P field marked L7 on. the program sheet
MUST be programmed digit FOUR (4). This is where we inform the OMNI 3000
‘.- . that zones six (6) through twelve (12) will be INSTANT ZONES.
THE EIGHTH LOCATION of this 2P field marked L8 on the program sheet
MUST be programmed digit NINE (9). This is where we inform the OMNI 3000
system that the common trouble zone is in fact a 24 hour TROUBLE zone.
THE NINTH LOCATION in this 2P field marked L9 determines the loop response time in milli-
seconds for the Fire Zone, Zones 1, 2 and 3. Select one digit desired from the following
chart for this location.
6 750 msec. 50 msec. 50 rnsec. 750 msec-
7 50 msec. 50 msec. 50 msec. 750 msec
,
I
8 ! 750 msec. ! 750 msec. ! 750
msec. !
50 msec.
9 50 msec. 750
msec.
750
msec.
50 msec.
A
750
msec.
50 msec. 750
msec.
50 rrksec.
1 6 50 tnsec. 50 rmec. 750
msec.
50 msec.
I
C 750
msec.
750
msec.
50 rnsec. 50 rnsec.
D
50 msec. 750
msec.
50 met. 50 rnsec.
L E 750
msec.
50 n-6ec. 50 msec. 50 msec.
F
50 msec. 50 msec. 50 msec. 50 mse.c.
THE TENTH LOCATION in this field marked LlO determines the loop response time in milli-
seconds for
ZONES
4, 5, and the
COMMON
TROUBLE ZONE. Zones six (6) through twelve
(12) are dedicated to respond to a SIXTY (60) MILLISECOND violation on any of their term-
inals. Select
one
digit desired from the following chart for this location.
THE .ELEVENTH LbCATION marked Lll in this field MUST be
programmed “Fft.

__.-_. -..-w-. -~. ? “. ‘- ‘.. . .J ‘. :.z. !
.- 6
..
.
l
Step
13: QUAD 2 , 3P FIELD
.
The FIRST LOCATION of this 3P field must be programmed Digit (2) for
the Fire Zone Dry Contact to operate correctly.
THE SECOND THROUGH SlXTH LOCATIONS of this 3P field
represent zones one
(i)
through five (5) respectively. A digit
MUST be programmed for each one of these locations from one
of the following CHARTS. If these zones were programmed in -
the 2P field as DELAY OR INSTANT zones then a digit MUST
be selected from CHART (A) for all the! ootions desired. If these
zones have been programmed in the 2P field as INTERIOR ,ZONES
then a digit MUST be selected from CHART (B). If these zones
were programmed in the 2P field as 24 HR. ALARM ZONES then
a digit MUST be selected from CHART (C). 24 HR. TROUBLE
ZONES MUST be selected from CHART CD).
NOTE: BYPASS CODES UPON ARMING CAN BE PROGRAMMED
ONLY ON INSTALLATIONS WHICH ALSO INCLUDE CLOSING CODES.
NOTE: ZONES WHICH ARE PROGRAMMED AS DAY ZONES WILL SOUND
THE OMNI 3000 R KEYPAD SONALERT STEADILY, AS LONG AS THOSE
ZONES ARE VIOLATED, WHILE THE SYSTEM IS IN THE DISARMED
CONDTTION-
CHART A *
DIGIT !DELAY AND INSTANT ZONES
2 I
Delay Zone,Bypass--Code upon arming if bypassed,.Day Zone I
3
.Delay Zone,Bypass Code upon arming if bypassed
4
‘Delay 2one;Bypass Code w,hen bypassed, Day Zone
5 Delay Zone, Bypass Code when bypassed
6
Delay Zone,Day Zone
7
.Delay Zone
A
instant Zone ‘, Bypass Code upon arming if bypassed, Day. Zone
0 I
lnstant Zone,Bypass Code upon arming if bypassed I
C
Instant Z.onef Bypass Code when bypassed, Day Zone, I
D I- lnstant Zone,Bypa.ss Code when bypassed I
E
F
Instant Zone, Day Zone
Instant .Zone
9
.-._
-._---
-_._
,
. .__ _ _._. ..__,_~...... --__ _ _ _ __-. _- ..^-._- --_- - --.-... - -. . __ _ ._.

:
’ .’
B
I’
. CHART B
l ,
DIGIT INTERIOR ZONES
A Interior Zone,Bypass Code upon arming if bypassed, Day Zone
B Interior Zone,Bypass Code upon arming if bypassed
C Interior Zone, Bypass Code .when bypassed! Day Zone
D Interior Zone, Bypass Code when bypassed
E Interior Zone, Day Zone
F Interior Zone .
CHART C NOTE: This Chart does not apply to Zones 1 or zones 5-12
’ DIGIT 24 HR. ALARM ZONES
4 Pulsing Burglary Bell
5 Steady Burglary Bell
6 Silent (NO RING BACK)
7 Silent (WITH RING BACK)
CHART D
NOTE: This chart does not apply to Zone 1 or Zones 5 -12
THE SEVENTH LOCATION of ‘this 3P field marked 17 MUST be programmed
(F). This is where we tell the OMNI 3000 system that zones six (6) through
twelve (12) will be standard INSTANT ZONES with no other options. If this
location is programmed (El, then all of zones six (6) through twelve (12) will
be INSTANT/DAY ZONES.
THE EIGHTH LOCATION of this 3P field marked 18 will determine the type
of AUDIBLE SONALERT OUTPUT that will occur on the OMNI 3000R Keypad
when the COMMON TROUBLE ZONE IS VIOLATED.
SELECT A DIGIT FROM THE CHART BELOW AS DESIRED.
r DIGIT
0
1
2
COMMON TROUBLE ZONE OUTPUT t
Pulse Sonalert
Steady Sonaiert
Silent (WITH RING BACK) .
THE NINTH THRU ELEVENTH LOCATIONS marked L9-Lll. MUST.be programmed an
“F”.
10

.’
Step 14: QUAD 2, AF FIELD
THE FIRST LOCATION -of this AF field marked Ll can be programmed for several
control panel options which are actually unrelated to each other, however, they all
share this location. Option one is TOUCHTONE or ROTARY (PULSE). DIALING.
The second option is called BELL TEST. The BURGLARY Siren and dry contacts will trip
momentarily when This system Is armed. The third option is called 24 HR AUTOMATIC TEST
CODE. If this option is selected the OMNI 3000 will automatically transmit A TEST SIGNAL
every 24 HOURS. The timer will be RESET every time there is ANY transmission to
the central office from this system. The last option in this location is called QUAD
SWTCHING. This option is necessary ONLY when the OMNI 3000 is being programmed
to.do a FOUR QUADRANT program (example: open/close by user). DO NOT PROGRAM
THIS OPTION UNTIL READING AND UNDERSTANDING THE ADVANCED COMMUNICATION
MANUAL.
SELECT A DIGIT FROM THE FOLLOWING CHART THAT REPRESENTS ALL
THE OPTIONS DESIRED IN THIS Ll LOCATION.
. 1
DIGIT FUNCTIONS
0 Touchtone dialing, quad switching, Bell test, 24 Hr. auto test -
1 Touchtone dialing, quad switching, Bell test
2 Touchtone, quad switching, 24 hr. automatic test
3 Touchtone, quad switching
4 Touchtone, Bell Test, 24 Hr. auto test
5 Touchtone, Bell Test
6 Touchtone; 24 Hr. auto test
7 Touchtone dialing
8 Rotary dialing, quad switching, Bell test, 24 Hr. auto test
9 Rotary, quad switching, Bell test
A Rotary, quad switching, 24 ‘Hr. auto test
B Rotary, quad switching
c Rotary, Bell test, 24 Hr. auto test
D. Rotary, Bell test
E Rotary, 24 Hr. Auto lest
F Rotary Dialing 4
-THE. SECOND LOCATION of this AF field marked L2 can be programmed for
several system options, which are unrelated to each other. The only relationsKip
between the several options is that they are all programmed in this location.
The first.op;ion in this location regards OMNI 3000 KEYPAD PANIC which can
be programmed either audible or silent. The second option is called OPENING
CODE AFTER ALARM ONLY. ‘This feature was designed into this system to
he us@d on residential systems.. The purpose of this option is to allow the
OMNI. 3000 to report a RESTORE CODE to the central office when this system
is disarmed AFTER A BURGLARY ALARM has occurred. (The actual
RESTORE CODE which will be reported must be programmed in QUAD
2, OP’ FIELD, L2 LOCATION, -called OPENING CODE).
11

The last option in this location is called EXTENDED FORMAT OPEN/CLOSE.
;This option will be selected when the OMNI 3000 system is going to report
opening and closing reports by user in EXTENDED FORMAT ONLY.
THIS OPTION MUST NOT BE PROGRAMMED IF STANDARD OPEN/CLOSE
I (NOT BY USER) 0~ OPEN/CLOSE BY USER,~+~ FORMAT IS DESIRED.
SELECT A DIGIT FROM THE FOLLOWING CHART THAT REPRESENTS
ALL THE DESIRED OPTIONS IN THIS L2 LOCATION.
1DIGIT- FUNCTlONS
AUDIBLE Panic
9 . AUDIBLE Panic, Extended Format Open-/
Closes
‘A AUDIBLE Panic, opening code after alarm ONLY
AUDIBLE Panic, opening code after alarm ONLY, Extended Format Open/Closes
SILENT Panic
1 D I
SILENT Panic, Extended Format Open/Closes
t E !
I SILENT Panic ooenine code after alarm ONLY
I
F I SILENT Panic, opening code after alarm ONLY, Extended Format Open/Closes
STEP 15: FF FIELD . _
_ -_ -
There are three (3) locations in this field marked Ll, L2, L3. The first
location is the STARTUP EXIT TIME. L2 is the STARTUP ENTRANCE TIME
and L3 is the BURGLARY SIREN AND DRY CONTACTS CUTOFF TIME.
Select a digit from the following chart for EACH of these locations that rep-
resents the desired times.
The exit/entrance times may be reprogrammed at the keypad if desired,
permanently voiding out these times unless a total system RESTART is done.

STEP 16: AC FIELD
LOCATIONS Ll-L4 of this AC field MUST be programmed with a FOUR
digit USER ONE STARTUP CODE. Only the digits O-8 may be used. Number
9 can not be used in this code.
This four dinit code is the USER ONE STARTUP ARM/DISARM, AND SYSTEM
PROGRAMMING CODE all in one,when the’OMN1 3000 system is initally powered
up
The USER ONE code can be reprogrammed at the keypad if desired, voiding out
this code unless a .total system RESTART is done.
STEP 17: AL FIELD
THE FIRST LOCATION of this field marked L 1 MUST be programmed (F).
THE SECOND THROUGH SIXTH LOCATIONS of this field marked L2-L6
represent zones one (1) through five (5) respectively.. Several options can
be programmed in these locations if these zones are BURGLARY ZONES
(delay, instant, interior). The first option is called ZONE LOCKOUT. If
this feature is selected for a zone the BURGLARY SIREN will trip
ONLY ONE (1) TIME (the first time) regardless of how many times THAT
zone is actually violated. The second option in this field is called GLOBAL
LOCKOUT. If this feature is selected for a tone,the BURGLARY SIREN will
trip ONLY ONE (1) TIME (the first time) THAT ZONE is violated, HOWEVER
THE SIRENOUTPUT WILL NOT TRIP AGAIN REGARDLESS IF ANY ZONE IS
VIOLATED FROM THEN ON.
The final option in this field is called RESTORE FOLLOWS LOOP. If this
option is selected for a zone the RESTORE CODE for that zone will be
reported to the central station as soon as the violated zone returns to its
normal or unviolated condition. If RESTORE FOLLOWS LOOP is NOT
selected, zones wh:ch are violated will report their RESTORE CODES upon.
SIREN CUTOFF assuming those zones have returned to the normal or un-
violated -condition at that time.
NOTE: If -ZONE LOCKOUT, GLOBAL LOCKOUT, or RESTORE.FOL .LOWS
LOOP is programmed for any of these zones 1-5, it is recommended
that those same zones also be programmed for NO ABORT OPER-
ATION in the 2P field of this quadrant to insure that dialer operation.
is NOT locked out on the RETRIGGER of these zones.
.
NOTE: If none of these features are desired on zones one through five,
program an (F) in their respective locations.

SELECT A DIGIT FROM THE FOLLOWING CHART FOR EACH OF
LOCATIONS L2-L6.
QUAD 2, AL FIELD
1
DIGIT FUNCTIONS
3 .Zone lockout
5 Global- lockout
7 Restore Follows Looo
6 -
D
F
Restore Follows Loop, .Zone. lockout
Restore Follows Loop, Global
lockout
None of the
above.
THE SEVENTH (7) THROUGH ELEVENTH (II) LOCATIONS of this field
marked L7-Lll MUST
be programmed (F).
STEP 18: The OMNI 3000 PROGRAMMING SHEET has been successfully filled
out at ’
this point.
EXTENDED FORMAT OPEN/CLOSE BY USER AND 4+2 FORMAT can all
be
found in the ADVANCED COMMUNICATIONS MANUAL I-2259.
Continue
on
the following page called PROPER PROM PROGRAMMING
PROCEDURE for a step by
step
explanation to actually BURN the data
entered on the OMNI 3000
program sheet
into the prom chip with the
llO/llOC
programmer.
AFTER THE PROM CHIP HAS BEEN SUCCESSFULLY PROGRAMMED, IT
MUST BE INSERTED INTO THE OMNI 3000 SYSTEM BLUE DOT RIGHT.
.

PROPER PROM PROGRAMMING PROCEDURE
STEP A Power up 110 or I IOC. The Prom MUST NOT be in the Programmer at this time.
Insertion of the Prom will be the last stepprior to depressing the Program Button.
STEP B Select the desired Quadrant to program. The 110 and 1lOC will program one quad-
rant (ori of the chip) at a time.
STEP C Depress [ENTER] momentarily, then [O] while the programmer socket is empty.
Depressing [ENTER and 0] loads the present contents of the socket into memory.
In the case of an empty socket, memory is loaded with Blanks or [F’s]. A Blank
and an [F] are the same thing. The only time the [F] Button must actually be de-
pressed is if one specific location in a Field must be jumped over to get to another
location to enter a number. Trailing [F’s] at the end of a field need not be depressed
as long as their locations are Blank.
STEP D Punch in desired information for OP field through AL field in this Quadrant. Move-
ment from OP to the next field and so on, can be accomplished by depressing [ENTER]
then [VI. At the bottom left corner of the programmer resides a chart which repre-
sents the field names, ‘descriptions and most important, the field numbers. Jumps can
be accomplished from one field to another by depressing [ENTER], then the respective
field number desired. Example: To jump from OP field to AC field, depress [ENTER]
then [7]. This variable jumping will become useful for duplicating master chips.
After completing data entry into all desired fields, the Prom may be inserted into
the programmer socket. The Blue Painted dot must be situated down. The Prom
must be pushed all the way in. The programmer does not care what field you are
in when you program. Depress the [Program] Buttonmomentarily, [Finish] should
be disolaved.
STEP F The present quadrant has been successfully programmed. To program addi-
tional quadrants, the Prom must be removed, select the desired quadrant and .
repeat steps C-F.
Summary:
[F]: The [Fl Button does not display anything when depressed, however it jumps
from one location to the next. The only time the [F] Button must actually be
depressed is when a jump must be made over one location to get to another loca-
tion where a number must be entered.
as their iocations are blank. Trailing F’s need not be depressed as long
[Enter], then [O] with socket empty: Loads F’s in selected quadrant.
[Enter], then [O] with Prom in socket: Loads memory Smith present data that re-
sides in the quadrant selected.
[Enter] then [VI: Increments fields from OP to AL back to OP again.
[Enter] then field number:
- Jumps from one field to another as designated by re-
spective field number.
15

. .
. ’
..
OMNI 3000
c * PROGRAMMINGSHEET
(JumwJT2
Corn mon Phone Prefix
[OlPl 1 I I I I I I I I I 1
Ll
LZ
L3 L4 LS 16 L7 LB LSLIOLll
1st Phone
jllpl I 1 I I 1 I I I I I 1
L1 L2 L)
L4 L5
16 L7 La L9LlOLll
2nd Phone
[ZIPI I I I I
I I I I I I I
LI L2 L3 L4 L5 ~6 L7 LB L9LlOLll
3rd Phone
[31PI 1 I I 1 1 I I I
I I 1
LJ L2 L1 Llr L5 Lb L7 LB L9L101.11
Receiver 2
Type
Receiver I Type
Account Number
[AlCl 1 1 1 1
LlI2 13 Lb
*c-r = ConHoN 1ROUBLE
i
R = 1.oop R
esponse
Ll l-2
L3
User
1 Startup Code
IAlCl 1 1 1 ]
Ll L2 L3 LO
*” c” c” c” r” 2
-7 2 Ip 2 0 2
IW-l I I I -1. I ~FIFI’FJFI-
Ll L2 L3 L4 LSL6 L7 L8 L9LI0L
16
jolpl 1 IFI 1 I 1 1 IFI IFI
LJ L2
L3 14
L5 Lb L7 L8 t9LlOLll
Dlalrng lypt. 2A Hr Test, Be11 Teat Ouad Switch
Keypad Psmc Sllent/Aud.
Ll L2
Startup Exit Time
Startup Entrance
Time
Bell Cut Off
lime /

. .
. l
.I ‘.
c .
-3
OMNI
3000
PROGRAMMING SHEET
-4
[olpl 1 I I 1 I I 1 I I
IF1
L1 LZ LJ L4LS L6 L7 L8 L9LlOLIJ
[lIPI 1 1 1 1 1 1 1 1 1 1 ]
Ll LZ L3 L4 LSL6 L7 LB L9LJOLLl
I J L2 L> L4 L5 Lb L7 18 L9LlOLl1
IPl I 1 1 I I 1 1 1 1 1 ]
L1 L2 L) L4 L5 L6 L7 LB 19LlOLlJ
Cl LZ
JrElIul Ll Lt LJ
CLOSING ACCOUNT #
U
niversel Closing C ode
Ll LZ LJ L4L5 L6 L7 L8 L9LlUL11
Universal. Opening Code
l-T-T..,/
I2lpI I I I I I I I lwFI
Ll LZ LJ L4 L5 Lb L7 LB L9LlOLll
User Codes
/
O-r%.?W*rbc\
Ll L2 L) L4 L5 L6 L7 LB L9LlOLlJ
OPENING ACCOUNTB
[AlCl 1.-I 1 ]
LJ 12 LJ Lo

OMNI
3000
. . SAMPLE COMMERCIAL
Corn mar, Phone Prefix
[O]PIl~8~0]0~ 1 1 1 1 1 1 ]
Cl
L2 LI L4LS Lb L7 LB L9LlOLll
1st Phone
[ljPj5]812]611 1611 1 1 1 1 1
Ll LZ L3 LB LS L6 I.7
lb
L9LlOLlI
2nd Phone
\21P12]31418]218[21 1 1 1 ]
Cl
L2 L3 L4 LS L6 L7 LB L9LlOLll
3rd Phone
[31PI 1 I 1 I 1 I 1 I 1 I ]
Cl
Lt
11
L4 L5 L6 L7 L8 L9LlOL11
/,/I
Receiver 1
Type
Receiver 2 Type
Receiver 3
Type
Account Number
[~/~I415161 ]
Cl
LZ L3 L4
L1 L2 L3 L4 L5L6 L7 LB L$LlOLIl
- r: ‘I ::
r:OnBUN :ROUBLE
i R =Loop Response
PROGRAM QUKRNT
~O~P~~~O~F~F~~I~IFI;IF(~~FI
Cl ~2 L3 L4 LS L6 L7 LtJJ9LlOLll
lllPIF19191919191919lFlFl
Ll L2 L3 L4 L5 L6 L7 LB L9L10
Ll LZ L3
User 1 Startup Code
[AlCll
[.2]3],4]
-- _
Ll L2 L3
14
,- c c; c &- c
5 2 2 IL” 0
\. 2
~~~L~F(FIFIFIFIFIFJFIFIFJF]
Ll
L2 L3 L4 L5 L6 L7 LB L9L~OLll

. OMNI 3000
.c SAMPLE RESIDENTIAL PROGRAM
tom mon Phone Prefix
[O/PI 1 I I 1 1 I I I 1 I 1
Ll.L2 LJ l-4 L> 16 L7 LB 191.10l.11
Ll L2 L) Ilr I> L6 L7 LE L9! lOLlI
2nd Phone
[2]PI I I 1 I I
I I I I I ]
Ll L2 I.> LO I5 L6 17 LR 19 I. IOL II
3rd Phone *
Account N u m ber
[~ICI41516I 1
Ll 12 L3 LO
L1 L2 L3 Llr LSL6 L7 LB L9L10L11
0
__c ‘CT = COMMON TROUBLE
* LR = Loop Response
~o(P(FIFIFIF~F[F1FIF~F~7lF]
Ll L2 L3 L4 L5L6 L7 L8&9Ll0L11
c 2. c” c” c” 0 e,
- 2;
p c c” c c 4
co %” 2p 2 2 2p c .L
\3(P12 I71F[FlF[ FlFlOlFlF (F .
Ll 12 I) L4 L5 L6 L7 LB L9L10L1:
r
[q-fy-1 :
FF333~.
LlL2L3
User 1 Startup Code
[AICII 1213141
L1 I<2 L3 L4
Ll L2 L3 La LSL6 L7 L8 L9LlOLll
-19
Other manuals for OMNI 3000
1