Fire-Lite Alarms 411UD User manual

Digital Alarm
Communicator/Transmitter
411UD
P/N 50759:C ECN 00-106
C
Document #50759
3/07/00 Rev.
© 2000

LimWarLg.p65 01/10/2000
An automatic fi e ala m system–typically made up of smoke
detectors, heat detectors, ma ual pull statio s, audible war -
i g devices, a d a fire alarm co trol with remote otificatio
capability–ca provide early war i g of a developi g fire.
Such a system, however, does ot assure protectio agai st
property damage or loss of life resulti g from a fire.
The Ma ufacturer recomme ds that smoke a d/or heat detec-
tors be located throughout a protected premise followi g the
recomme datio s of the curre t editio of the Natio al Fire
Protectio Associatio Sta dard 72 (NFPA 72),
ma ufacturer's recomme datio s, State a d local codes, a d
the recomme datio s co tai ed i the Guide for Proper Use
of System Smoke Detectors, which is made available at o
charge to all i stalli g dealers. A study by the Federal Emer-
ge cy Ma ageme t Age cy (a age cy of the U ited States
gover me t) i dicated that smoke detectors may ot go off i
as ma y as 35% of all fires. While fire alarm systems are de-
sig ed to provide early war i g agai st fire, they do ot guar-
a tee war i g or protectio agai st fire. A fire alarm system
may ot provide timely or adequate war i g, or simply may ot
fu ctio , for a variety of reaso s:
Smoke detecto s may ot se se fire where smoke ca ot
reach the detectors such as i chim eys, i or behi d walls, o
roofs, or o the other side of closed doors. Smoke detectors
also may ot se se a fire o a other level or floor of a build-
i g. A seco d-floor detector, for example, may ot se se a
first-floor or baseme t fire.
Pa ticles of combustion o "smoke" from a developi g fire
may ot reach the se si g chambers of smoke detectors be-
cause:
• Barriers such as closed or partially closed doors, walls, or
chim eys may i hibit particle or smoke flow.
• Smoke particles may become "cold," stratify, a d ot reach
the ceili g or upper walls where detectors are located.
• Smoke particles may be blow away from detectors by air
outlets.
• Smoke detectors may be draw i to air retur s before
reachi g the detector.
The amou t of "smoke" prese t may be i sufficie t to alarm
smoke detectors. Smoke detectors are desig ed to alarm at
various levels of smoke de sity. If such de sity levels are ot
created by a developi g fire at the locatio of detectors, the
detectors will ot go i to alarm.
Smoke detectors, eve whe worki g properly, have se si g
limitatio s. Detectors that have photoelectro ic se si g
chambers te d to detect smolderi g fires better tha flami g
fires, which have little visible smoke. Detectors that have io -
izi g-type se si g chambers te d to detect fast-flami g fires
better tha smolderi g fires. Because fires develop i differ-
e t ways a d are ofte u predictable i their growth, either
type of detector is ecessarily best a d a give type of detec-
tor may ot provide adequate war i g of a fire.
Smoke detectors ca ot be expected to provide adequate
war i g of fires caused by arso , childre playi g with
matches (especially i bedrooms), smoki g i bed, a d viole t
explosio s (caused by escapi g gas, improper storage of
flammable materials, etc.).
Heat detectors do ot se se particles of combustio a d
alarm o ly whe heat o their se sors i creases at a prede-
termi ed rate or reaches a predetermi ed level. Rate-of-rise
heat detectors may be subject to reduced se sitivity over time.
For this reaso , the rate-of-rise feature of each detector
should be tested at least o ce per year by a qualified fire pro-
tectio specialist.
Heat detectors are desig ed to protect
property, ot life.
IMPORTANT!
Smoke detecto s must be i stalled i the
same room as the co trol pa el a d i rooms used by the sys-
tem for the co ectio of alarm tra smissio wiri g, commu i-
catio s, sig ali g, a d/or power.
If detectors are ot so lo-
cated, a developi g fire may damage the alarm system, crip-
pli g its ability to report a fire.
Audible wa ning devices such as bells may ot alert people
if these devices are located o the other side of closed or
partly ope doors or are located o a other floor of a buildi g.
A y war i g device may fail to alert people with a disability or
those who have rece tly co sumed drugs, alcohol or medica-
tio . Please ote that:
• Strobes ca , u der certai circumsta ces, cause seizures
i people with co ditio s such as epilepsy.
• Studies have show that certai people, eve whe they
hear a fire alarm sig al, do ot respo d or comprehe d the
mea i g of the sig al. It is the property ow er's respo sibil-
ity to co duct fire drills a d other trai i g exercise to make
people aware of fire alarm sig als a d i struct them o the
proper reactio to alarm sig als.
• I rare i sta ces, the sou di g of a war i g device ca
cause temporary or perma e t heari g loss.
A fi e ala m system will ot operate without a y electrical
power. If AC power fails, the system will operate from sta dby
batteries o ly for a specified time a d o ly if the batteries
have bee properly mai tai ed a d replaced regularly.
Equipment used in the system may ot be tech ically com-
patible with the co trol. It is esse tial to use o ly equipme t
listed for service with your co trol pa el.
Telephone lines eeded to tra smit alarm sig als from a
premise to a ce tral mo itori g statio may be out of service
or temporarily disabled. For added protectio agai st tele-
pho e li e failure, backup radio tra smissio systems are rec-
omme ded.
The most common cause of fire alarm malfu ctio is i ade-
quate mai te a ce. To keep the e tire fire alarm system i
excelle t worki g order, o goi g mai te a ce is required per
the ma ufacturer's recomme datio s, a d UL a d NFPA sta -
dards. At a mi imum, the requireme ts of Chapter 7 of NFPA
72 shall be followed. E viro me ts with large amou ts of
dust, dirt or high air velocity require more freque t mai te-
a ce. A mai te a ce agreeme t should be arra ged
through the local ma ufacturer's represe tative. Mai te a ce
should be scheduled mo thly or as required by Natio al a d/
or local fire codes a d should be performed by authorized pro-
fessio al fire alarm i stallers o ly. Adequate writte records
of all i spectio s should be kept.
While a fire alarm system may lower i sura ce
rates, it is ot a substitute for fire i sura ce!
Fi e Ala m System Limitations

LimWarLg.p65 01/10/2000
WARNING -
Several differe t sources of power ca be co -
ected to the fire alarm co trol pa el.
Disco ect all sources
of power before servici g. Co trol u it a d associated equip-
me t may be damaged by removi g a d/or i serti g cards,
modules, or i terco ecti g cables while the u it is e ergized.
Do ot attempt to i stall, service, or operate this u it u til this
ma ual is read a d u derstood.
CAUTION -
System Reaccepta ce Test after Software
Cha ges.
To e sure proper system operatio , this product
must be tested i accorda ce with NFPA 72 Chapter 7 after
a y programmi g operatio or cha ge i site-specific soft-
ware. Reaccepta ce testi g is required after a y cha ge, ad-
ditio or deletio of system compo e ts, or after a y modifica-
tio , repair or adjustme t to system hardware or wiri g.
All compo e ts, circuits, system operatio s, or software fu c-
tio s k ow to be affected by a cha ge must be 100% tested.
I additio , to e sure that other operatio s are ot i advert-
e tly affected, at least 10% of i itiati g devices that are ot
directly affected by the cha ge, up to a maximum of 50 de-
vices, must also be tested a d proper system operatio veri-
fied.
This system meets NFPA requireme ts for operatio at
0-49° C/32-120° F a d at a relative humidity of 85% RH ( o -
co de si g) at 30° C/86° F. However, the useful life of the
system's sta dby batteries a d the electro ic compo e ts
may be adversely affected by extreme temperature ra ges
a d humidity. Therefore, it is recomme ded that this system
a d all peripherals be i stalled i a e viro me t with a omi-
al room temperature of 15-27° C/60-80° F.
Ve ify that wi e sizes a e adequate for all i itiati g a d
i dicati g device loops. Most devices ca ot tolerate more
tha a 10% I.R. drop from the specified device voltage.
Like all solid state elect onic devices, this system may
operate erratically or ca be damaged whe subjected to light-
i g-i duced tra sie ts. Although o system is completely
immu e from light i g tra sie ts a d i terfere ces, proper
grou di g will reduce susceptibility.
Overhead or outside
aerial wiri g is ot recomme ded, due to a i creased sus-
ceptibility to earby light i g strikes.
Co sult with the Tech i-
cal Services Departme t if a y problems are a ticipated or
e cou tered.
Disconnect AC powe and batte ies prior to removi g or i -
serti g circuit boards. Failure to do so ca damage circuits.
Remove all elect onic assemblies prior to a y drilli g, fili g,
reami g, or pu chi g of the e closure. Whe possible, make
all cable e tries from the sides or rear. Before maki g modifi-
catio s, verify that they will ot i terfere with battery, tra s-
former, a d pri ted circuit board locatio .
Do not tighten sc ew te minals more tha 9 i -lbs.
Over-tighte i g may damage threads, resulti g i reduced
termi al co tact pressure a d difficulty with screw termi al
removal.
Though designed to last many yea s, system compo e ts
ca fail at a y time. This system co tai s static-se sitive
compo e ts. Always grou d yourself with a proper wrist strap
before ha dli g a y circuits so that static charges are re-
moved from the body. Use static-suppressive packagi g
to protect electro ic assemblies removed from the u it.
Follow the inst uctions i the i stallatio , operati g, a d
programmi g ma uals. These i structio s must be followed
to avoid damage to the co trol pa el a d associated
equipme t. FACP operatio a d reliability depe d upo
proper i stallatio by authorized perso el.
Adhere ce to the followi g will aid i problem-free
i stallatio with lo g-term reliability:
WARNING: This equipme t ge erates, uses, a d ca
radiate radio freque cy e ergy a d if ot i stalled a d
used i accorda ce with the i structio ma ual, may
cause i terfere ce to radio commu icatio s. It has
bee tested a d fou d to comply with the limits for class
A computi g device pursua t to Subpart B of Part 15 of
FCC Rules, which is desig ed to provide reaso able
protectio agai st such i terfere ce whe operated i a
commercial e viro me t. Operatio of this equipme t i
a reside tial area is likely to cause i terfere ce, i which
case the user will be required to correct the i terfere ce
at his ow expe se.
Canadian Requi ements
This digital apparatus does ot exceed the Class A
limits for radiatio oise emissio s from digital
apparatus set out i the Radio I terfere ce Regulatio s
of the Ca adia Departme t of Commu icatio s.
Le prese t appareil umerique 'emet pas de bruits
radioelectriques depassa t les limites applicables aux
appareils umeriques de la classe A prescrites da s le
Regleme t sur le brouillage radioelectrique edicte par le
mi istere des Commu icatio s du Ca ada.
FCC Wa ning
Installation P ecautions

4 Document #50759 Rev.C 3/07/00 P/N 50759:C
Notes

Document 50759 Rev. C 3/07/00 P/N: 50759:C 5
CHAPTER 1: P oduct Desc iption .........................................................................................................................8
1.1: Product Features..........................................................................................................................................8
FIGURE 1-1: 411UD Digital Communicator......................................................................................8
1.2: pecifications ..............................................................................................................................................9
1.3: Circuits........................................................................................................................................................10
1.3.1: Power Requirements .........................................................................................................................10
1.3.2: Channels/Inputs.................................................................................................................................10
1.3.3: Primary and econdary Phone Lines................................................................................................10
1.3.4: Earth Ground.....................................................................................................................................10
1.4: Controls and Indicators ...............................................................................................................................11
FIGURE 1-2: 411UD Controls and Indicators ....................................................................................11
1.5: Digital Communicator Operation................................................................................................................12
1.6: Telephone Requirements and Warnings ......................................................................................................12
1.6.1: Telephone Circuitry - PH1 & PH2....................................................................................................12
1.6.2: Digital Communicator: .....................................................................................................................12
1.6.3: Telephone Company Rights and Warnings:......................................................................................13
1.6.4: For Canadian Applications................................................................................................................13
1.7: Operational Modes ......................................................................................................................................14
1.7.1: Normal Mode ....................................................................................................................................14
1.7.2: Real Time Clock Mode.....................................................................................................................14
1.7.3: Program Mode...................................................................................................................................14
1.7.4: Troubleshoot Mode...........................................................................................................................14
1.7.5: Default Mode ....................................................................................................................................14
CHAPTER 2: Installation.........................................................................................................................................15
2.1: Mounting Options .......................................................................................................................................15
FIGURE 2-1: 411UD Enclosure..........................................................................................................15
2.2: Operating Power..........................................................................................................................................15
2.3: Input Channels.............................................................................................................................................15
FIGURE 2-2: Fire•Lite M -9200 Connection to 411UD....................................................................16
FIGURE 2-3: Notifier AFP-200 Connection to 411UD......................................................................16
FIGURE 2-4: tyle B Channel Connections........................................................................................17
2.4: Output Circuits............................................................................................................................................18
FIGURE 2-5: Programmable Relay.....................................................................................................18
2.5: Telephone Circuits.......................................................................................................................................19
FIGURE 2-6: Wiring Phone Jacks.......................................................................................................19
2.6: Optional Programmer..................................................................................................................................20
FIGURE 2-7: Programmer Connection to 411UD ..............................................................................20
2.7: UL Power-limited Wiring Requirements ....................................................................................................21
CHAPTER 3: Modes of Ope ation..........................................................................................................................22
3.1: Normal Mode ..............................................................................................................................................22
3.1.1: Programmer Key Functions ..............................................................................................................23
FIGURE 3-1: Programmer Keypad.....................................................................................................23
3.1.2: Programmer Display.........................................................................................................................24
3.2: Real Time Clock Mode ...............................................................................................................................24
3.3: Program Mode.............................................................................................................................................26
3.3.1: DACT Programming .........................................................................................................................27
TABLE 3-1: Ademco Contact ID Format - Primary ...........................................................................29
TABLE 3-2: 4+2 tandard and 4+2 Express Formats - Primary.........................................................29
TABLE 3-3: All 3+1, 4+1 and 4+2 Expanded Formats - Primary ......................................................30
TABLE 3-4: Ademco Contact ID Format - econdary .......................................................................33
Table of Contents

Table of Contents
6 Document #50759 Rev. C 3/07/00 P/N: 50759:C
TABLE 3-5: 4+2 tandard and 4+2 Express Formats - econdary.....................................................33
TABLE 3-6: All 3+1, 4+1 and 4+2 Expanded Formats - econdary ..................................................34
3.4: Default Mode...............................................................................................................................................39
3.5: Troubleshoot Mode......................................................................................................................................39
FIGURE 3-2: Handset/ peaker Connection ........................................................................................40
CHAPTER 4: Cent al Station Communications....................................................................................................41
TABLE 4-1: Format election Addresses ( 20 and 50) Programming................................................42
TABLE 4-2: Format election Address Explanation...........................................................................43
4.0.1: Transmittal Priorities.........................................................................................................................44
4.0.2: Ademco Contact ID Format Event Code Description.......................................................................45
TABLE 4-3: Compatible UL Listed Receivers....................................................................................46
CHAPTER 5: Remote Site Upload/Download........................................................................................................47
5.1: General ........................................................................................................................................................47
5.1.1: ecurity Features...............................................................................................................................48
5.2: Downloading to the Communicator ............................................................................................................49
5.3: Uploading From the Communicator............................................................................................................49
5.4: imultaneous Data Transfers.......................................................................................................................50
Appendix A: Programming Sheets .......................................................................................................................51
A.1: Digital Communicator Options Program heets .......................................................................................51
A.2: Digital Communicator Options Program heet (Factory Defaults) ..........................................................53
Appendix B: Event Codes/Transmission Format Programming Sheets ..........................................................55
B.1: 4+2 tandard & 4+2 Express Formats Primary Central tation ................................................................55
B.2: 4+2 tandard & 4+2 Express Formats econdary Central tation ............................................................55
B.3: 4+2 tandard & 4+2 Express Formats Primary Central tation ................................................................56
B.4: 4+2 tandard & 4+2 Express Formats econdary Central tation ............................................................56
B.5: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central tation ...............................................57
B.6: All 3+1, All 4+1 and 4+2 Expanded Formats for econdary Central tation ...........................................57
B.7: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central tation (Factory Defaults) ................57
B.8: All 3+1, All 4+1 and 4+2 Expanded Formats for econdary Central tation (Factory Defaults) ...........57
B.9: Ademco Contact ID Format Primary Central tation ................................................................................58
B.10: Ademco Contact ID Format econdary Central tation ..........................................................................58
B.11: Ademco Contact ID Format Primary Central tation (Factory Defaults) ...............................................59
B.12: Ademco Contact ID Format econdary Central tation (Factory Defaults) ...........................................59
Appendix C: Ademco Contact I Format Event Code escription .................................................................60
Appendix : Wire Requirements .........................................................................................................................64
TABLE 5-1: Wire pecifications.........................................................................................................64
Appendix E: Operational Modes ..........................................................................................................................65
TABLE 5-2: Operational Modes..........................................................................................................65

This digital communicator has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories tandard
• NFPA 72 National Fire Alarm Code
• CAN/ULC - 527-M87 tandard for Control Units for Fire Alarm ystems
NFPA Standards
This digital communicator complies with the NFPA 72 National Fire Alarm Code for:
Central tation ignaling ystems Protected Premises Unit (Automatic, Manual and Waterflow)
Local Fire Alarm ystems (Automatic, Manual, Waterflow and prinkler upervisory)
Proprietary Fire Alarm ystems (Protected Premises Unit)
Remote tation Fire Alarm ystems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm ystems
Inspection, Testing and Maintenance for Fire Alarm ystems
Underwriters Laboratories ocuments:
UL 217 moke Detectors, ingle and Multiple tation
UL 268 moke Detectors for Fire Protective ignaling ystems
UL 346 Waterflow Indicators for Fire Protective ignaling ystems
UL 464 Audible ignaling Appliances
UL 521 Heat Detectors for Fire Protective ignaling ystems
UL 864 tandard for Control Units for Fire Protective ignaling ystems
UL 1076 Proprietary Burglar Alarm Units and ystems
UL 1481 Power upplies for Fire Protective ignaling ystems
UL 1635 Digital Alarm Communicator ystem Units
UL 1638 Visual ignaling Appliances
UL 1971 ignaling Devices for Hearing Impaired
CAN/ULC - 524-M91 tandard for Installation of Fire Alarm ystems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective ignaling ystems
Applicable Local and tate Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Befo e p oceeding, the installe should be familia with the following documents.
Document #50759 Rev. C 3/07/00 P/N 50759:C 7

P oduct Desc iption
8 Document #50759 Rev.C 3/07/00 P/N 50759:C
CHAPTER 1 Product Description
The 411UD is a four input/channel, dual line, digital communicator which can be used as a slave communicator with
UL listed fire and nonfire control panels. The four inputs are compatible with normally open relay contacts, require
End-Of-Line (EOL) resistors, are supervised and are fully programmable. The 411UD interfaces with the public
switched telephone network and is compatible with most central station receivers. A total of fifteen popular commu-
nications formats are supported, including Ademco Contact ID. The communicator also contains a unique DACT
option that eliminates 'dialer runaway'. It restricts the transmission of any trouble event to 1 attempts in a 24 hour
period. Power supplied must be 12 or 24 volts, filtered and nonresettable. Accessories include the Fire-Watch 411
eries DACT Programmer (Model PRO-411) as well as the PK-411 Windows® 95 based remote site programming
software. The 411UD comes in a small 6.841" (17.376 cm) X 4.595" (11.671 cm) X 1.00" (2.54 cm) metal enclosure,
providing a variety of mounting options.
1.1 P oduct Featu es
• Four input channels
• Dual telephone lines
• Dual telephone line voltage detect
• Program locations for entering up to 20-digit
central station and service terminal
telephone numbers
• urface mount technology
• Compact in size
• eparate external keypad and display
✓provides means of programming digi-
tal communicator in program mode
✓provides means of testing phone
circuits in troubleshoot mode
• 6.841" (17/376 cm) X 4.595" (11.671 cm) X 1.0" (2.54 cm) metal enclosure facilitates internal and external
control panel mounting
• Communicates vital status of monitored control panel:
✓fire alarm
✓host control panel trouble
✓fire supervisory
✓process monitor
✓AC (mains) power loss (programmable)
✓security alarm
✓other
• Communicates vital status of 411UD digital communicator:
✓digital communicator troubles
✓telephone Line 1 and 2 voltage fault
✓Primary Central tation number communication fault
✓econdary Central tation number communication fault
✓system off-normal (local Program Mode entered)
✓24 Hour normal test
✓24 Hour abnormal test (24 hour test message with previously reported alarm or trouble still active)
FIGURE 1-1:411UD Digital Communicato
411udcvr.cdr

Document #50759 Rev. C 3/07/00 P/N 50759:C 9
Specifications
• Individual LEDs for:
✓Communication Fail (visible with cover on)
✓DACT Trouble (visible with cover on)
✓Channel Active (visible with cover on)
✓Primary Phone Line (PH1) active
✓econdary Phone Line (PH2) active
✓Modem Active
• Piezo sounder
• Local piezo silence switch which silences onboard piezo sounder (accessible without removing cover)
• Real time clock
• Extensive transient protection
• One Form-C relay, fully programmable to activate for the following conditions:
✓fire alarm
✓host control panel trouble
✓fire supervisory
✓process monitor
✓total communication failure
✓AC loss
✓DACT trouble (factory default for relay)
✓security alarm
• PK-411 Remote Upload/Download Kit
• Industry-first, UL recognized 'dialer runaway' feature'
1.2 Specifications
Operating Power
The 411UD may be powered from UL listed control panels that output nonresettable and power-limited 12 or 24
VDC power. The configuration of Jumper J4 determines whether 12 VDC power is to be supplied directly to the
411UD circuit board or 24 VDC power is to be supplied and then internally regulated down internally to 12 VDC.
C Power - TB1 Terminals 4(+) and 5(-), Terminal 6 is Earth Ground
• J4 Jumper removed - Filtered, nonresettable and power-limited 24 VDC (nominal) power must be supplied at
TB1 Terminals 4(+) and 5(-). Operating voltage provided must be within 21.3 to 24.0 VDC (UL tested range:
-15%, +10%). Current requirements are 100 mA in standby and 170 mA1 while communicating.
• J4 Jumper installed - Filtered, nonresettable and power-limited 12 VDC (nominal) power must be supplied at
TB1 Terminals 4(+) and 5(-). Operating voltage provided must be within 11.2 to 12.4 VDC (UL tested range:
-15%, +10%). Current requirements are 100 mA in standby and 170 mA1 while communicating.
Channels/Inputs2 - TB2 Terminals 1 through 8
Programmable Channels 1 through 4
Power-limited circuitry
Fully supervised
Operation: All channels NFPA tyle B (Class B). Requires Normally Open contact to trigger
1. A maximum of 300 mA is possible with all input channels shorted, the 411UD communicating, the Programmer connected and
Lamp Test active.
2. Channels/inputs do not support 2-wire smoke detectors.

Ci cuits
10 Document #50759 Rev.C 3/07/00 P/N 50759:C
Normal Operating Voltage: 12 VDC
Maximum Line Resistance: 100 ohms per channel
Alarm Current: 3.34 mA
End-Of-Line Resistor: 2.2K ohms, ½ watt (P/N 27070)
hort Circuit Current: 3.8 mA per channel/input
One Form-C Relay - TB1 Terminals 1 through 3
Contact rating: 2.0 amps @ 30 VDC (resistive)
1.3 Ci cuits
The 411UD circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual modu-
lar phone line jacks, piezo sounder, piezo silence switch, one programmable relay and two connectors for input, out-
put and power wiring.
1.3.1 Power Requirements
Voltage for the digital communicator may be a power-limited, filtered, nonresettable nominal 12 VDC [11.2 to
12.4 VDC (UL tested range: -15%, +10%)] or nominal 24 VDC [21.3 to 24.0 VDC (UL tested range: -15%,
+10%)]. Jumper J4 is used to select the power source.
1.3.2 Channels/Inputs
Four input channels are provided on the 411UD digital communicator which are used for connection to the control
panel being monitored. Each input can be programmed to monitor the control panel for:
• fire alarm activation
• process monitoring activation
• trouble activation
• fire supervisory activation
• security alarm activation
• AC loss activation
Each input channel is configured as a Class B circuit and must be wired to a Normally Open contact.
1.3.3 Primary and Secondary Phone Lines
Modular jacks are used to interface the primary and secondary phone lines to the public telephone network.
1.3.4 Earth Ground
Connect a separate earth ground wire to TB1 terminal 6 for transient protection.

Document #50759 Rev. C 3/07/00 P/N 50759:C 11
Cont ols and Indicato s
1.4 Cont ols and Indicato s
Front Panel Switch
• ilence witch - press to silence local 411UD piezo sounder
411U Piezo Sounder
• The 411UD piezo sounder is used to locally annunciate DACT troubles. DACT troubles include input channel
open circuit, phone line 1 or 2 voltage fault, phone number 1 or 2 communication fault, total communication
failure and communications disabled.
Front Panel Indicators
• Communication Fail - yellow LED
• DACT Trouble - yellow LED
• Channel Active - red LED
Circuit Board Indicators
• Primary Phone Line 1 (PH1) Active - red LED
• econdary Phone Line 2 (PH2) Active - red LED
• Modem Active - green LED
TB2
TB1
R41
U8
U10
U11
J2
PH1
PH2
J1
J4
FIGURE 1-2:411UD Cont ols and Indicato s
Channel
Active
LED
DACT
T ouble
LED
Comm.
Fail LED Piezo
Silence
Switch
PH1 LED
PH2 LED
Modem
LED
Comm.
Fail LED
DACT
T ouble
LED
Channel
Active
LED
411udbrd.cdr
411udcvr.cdr

Digital Communicato Ope ation
12 Document #50759 Rev.C 3/07/00 P/N 50759:C
1.5 Digital Communicato Ope ation
The 411UD has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control
panels. Numerous formats are also available for communication to a central station. Two modular phone jacks allow
easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and econdary phone
lines. The digital communicator provides the following functions:
• Line eizure- takes control of the phone lines, disconnecting any premises phones using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central tation(s) phone number - default is Touch-Tone®, programmable to rotary
• Discern proper Central tation 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central tation(s)
• Verify data has been accepted by the Central tation(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Refer to Table 4-1, “Format election Addresses ( 20 and 50) Program-
ming,” on page 42).
1.6 Telephone Requi ements and Wa nings
1.6.1 Telephone Circuitry - PH1 & PH2
AC Ringer Equivalence Number (REN) = 0.5B
DC Ringer Equivalence Number (REN) = 1.3
Complies with FCC Part 68
Mates with RJ31X Male Connector
upervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs
on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas,
the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to
the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the
calling area.
1.6.2 igital Communicator:
Before connecting the 411UD to the public switched telephone network, the installation of two RJ31X jacks is neces-
sary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472
Product Model Number: 411UD
FCC Registration Number: OAAU A-25431-AL-E
Ringer Equivalence 0.5B

Document #50759 Rev. C 3/07/00 P/N 50759:C 13
Telephone Requi ements and Wa nings
1.6.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this digital communicator. How-
ever, the telephone company is required to give advance notice of such changes or interruptions. If the digital com-
municator causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private tele-
phone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.6.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment
meets certain telecommunications network protective, operational and safety requirements as prescribed in the appro-
priate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment
will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the sup-
plier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the tele-
communications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative: NOTIFIER, CANADA
24 Viceroy Road
Concord, Ontario L4K2L9
IC Certificate Number: 2132 9028 A
Ringer Equivalence Number (REN): 0.2

Ope ational Modes
14 Document #50759 Rev.C 3/07/00 P/N 50759:C
1.7 Ope ational Modes
1.7.1 Normal Mode
Normal Mode is the standard mode of operation in which the 411UD digital communicator monitors the host control
panel status as well as telephone line voltage and other internal circuits. In addition to locally annunciating system
trouble, active channel and communication fail, the digital communicator transmits system status information to UL
listed central station receivers. Transmitted data includes fire alarm, fire alarm trouble, supervisory alarm, security
alarm, AC loss and process monitoring information. pecific digital communicator troubles are also transmitted.
1.7.2 Real Time Clock Mode
Real Time Clock Mode allows the user to change the digital communicator’s internal 24 hour clock. Connecting an
external Programmer allows access to the various Modes of operation. While the communicator is in Real Time
Clock Mode, it does not monitor channel inputs.
1.7.3 Program Mode
Program Mode is used to change the programmed functions of the 411UD digital communicator. While the commu-
nicator is in Program Mode, it does not monitor channel inputs.
1.7.4 Troubleshoot Mode
Troubleshoot Mode may be used for testing the telephone line interconnect wiring. Connection from the 411UD’s
modular jacks, through the RJ31X jacks and into the telephone network may be easily checked. In this mode, the
Programmer keypad acts similar to a telephone touchpad. While the communicator is in Troubleshoot Mode, it does
not monitor channel inputs.
1.7.5 efault Mode
Default Mode may be used to return all 411UD programming back to the factory default settings.

Document #50759 Rev. C 3/07/00 P/N 50759:C 15
Installation
CHAPTER 2 Installation
2.1 Mounting Options
The 411UD with enclosure may be mounted in the cabinet of the Fire•Lite/Notifier control panel which is being mon-
itored or in any enclosure UL listed for fire protective use. When using with other than Fire•Lite/Notifier control
panels, the 411UD may be mounted in any enclosure UL listed for fire protective use. Mounting tabs are provided
for ease of mounting.
2.2 Ope ating Powe
CAUTION: Disconnect all power before servicing the 411UD. The digital communicator may be damaged by
removing and/or inserting components or interconnecting cables while the unit is energized.
12VDC or 24VDC nominal power connections are made to TB1 on the 411UD circuit board. When jumper J4 is
installed, the 11.2 to 12.4 VDC nominal operating voltage (UL tested range: -15%, +10%) for the digital communica-
tor must be power-limited, filtered, nonresettable. This 12 VDC nominal operating power can be supplied directly to
the 411UD by a UL listed 12 VDC power supply listed for fire protection or by a nonresettable 12 VDC output from
a control panel. Alternatively, removing J4 Jumper on the digital communicator circuit board allows the 411UD to be
supplied by a power-limited, nonresettable 21.3 to 24.0 VDC (UL tested range: -15%, +10%). This 24 VDC nominal
operating power can be supplied by a UL listed 24 VDC power supply, which, in order to comply with UL 864 must
be listed for Fire Protective ignaling ystems or by a nonresettable 24 VDC output from a control panel. This nom-
inal 24 VDC power is then internally regulated by the digital communicator to 12 VDC operating power.
Note that upon power-up, the 411UD will immediately annunciate a DACT trouble since the communicator is factory
defaulted to 'communicator disabled' at program location 64.
2.3 Input Channels
The 411UD digital communicator has four channel inputs. Each channel is supervised for opens (trouble) and shorts
(alarm) by the digital communicator. Each channel is a tyle B (Class B) Initiating Device Circuit designed to accept
any normally-open contact device. ince channels do not latch, a reset switch is not provided by the 411UD. The
communicator transmissions to a central station track the state of the inputs. Refer to Figure 2-4, “ tyle B Channel
Connections,” on page 17 for information on wiring tyle B circuits. Figure 2-2 illustrates the connection of the
411UD to a Fire•Lite M -9200 and Figure 2-3 illustrates connection of the 411UD to a Notifier AFP-200.
1.000“
(
2.54 cm
)
6.841“ (17.376 cm)
1.000“
(2.54 cm)
4.595“
(11.671 cm)
0.187“
(0.475 cm)
0.187“
(0.475 cm)
FIGURE 2-1:411UD Enclosu e
Mou ti g bracket
Mou ti g
bracket
Mou ti g bracket
Mou ti g bracket Bottom
411bkbox.cdr
!

Input Channels
16 Document #50759 Rev.C 3/07/00 P/N 50759:C
TB2
TB1
U8
U10
U11
J1 J2
J4
PH1
R41
PH2
M300
FIGURE 2-2:Fi e•Lite MS-9200 Connection to 411UD
Fi e•Lite MS-9200
411UD
24 VDC o resettable power
+ -
MS-9200
Supervisory Relay
MS-9200
Trouble Relay
MS-9200
Alarm Relay
Cha el 1
Cha el 2
Cha el 3
Cha el 4
2.2K EOLS
P/N 27070
47K EOL
SLC Loop
J4 Not I stalled
Relay Output
(DACT Trouble)
M300 Mo itor
Circuit I put
Note: The M300 monito module
input, which is being used to moni-
to the 411UD Relay Output (p o-
g ammed fo DACT T ouble), must
be p og ammed as 'DACT T ouble'
at the Fi e•Lite MS-9200
2.2K
EOL
9200411u.cdr
TB2
TB1
U8
U10
U11
J1 J2
J4
PH1
R41
PH2
MMX-2
FIGURE 2-3:Notifie AFP-200 Connection to 411UD
Notifie AFP-200
SLC Loop
2.2K
EOLs
P/N 27070
AFP-200
Supervisory Relay
AFP-200
Alarm Relay
AFP-200
Trouble Relay
J4 Not I stalled
24VDC o resettable power
MMX-2
Mo itor
Circuit
I put
Relay Output
(DACT Trouble)
411UD
Cha el 1
Cha el 2
Cha el 3
2.2K
EOL
Note: The MMX-2 monito module
input, which is being used to moni-
to the 411UD Relay Output (p o-
g ammed fo DACT T ouble), must
be p og ammed as 'DACT T ouble'
at the Notifie AFP-200. Cha el 4
afp2411u.cdr

Document #50759 Rev. C 3/07/00 P/N 50759:C 17
Input Channels
Each input channel monitors a normally open device and may be programmed as follows:
• fire alarm
• process monitor
• host control panel trouble
• fire supervisory
•AC Loss
• security alarm
Programming the input channel automatically programs the transmitted event code, however, the event code can be
changed since it is fully programmable. Event code transmissions can be tailored to the specific application and
requirements of the Central tation.
AC Loss Reporting: Channel 4, which is defaulted to AC Loss, will transmit a specific AC loss signal only if the
assigned Normally Open contact provides this function. Some panels provide an option that will automatically delay
the trigger of their system trouble relays upon loss of AC (such as the Fire•Lite Sensiscan 2 , MS-92 and Notifier
AFP-2 and AFP-4 ). If this is provided by the host panel, use Channel 2. Be certain to verify the method
employed by the host panel to be monitored.
Note that Process Monitor refers to circuits which may not specifically tie into elements of a fire system. With the
exception of burglary functions, process monitoring circuits could be used to monitor any nonfire functions such as
water temperature, room temperature, door open/closed, gas leakage, chemical leakage, etc.
The factory default programming for each channel is as follows:
✓Channel 1 - fire alarm
✓Channel 2 - host control panel trouble
✓Channel 3 - fire supervisory
✓Channel 4 - AC Loss
Channel Labels
Note that space is provided for labeling the function of each channel. Write the function that has been programmed
for each channel in the white boxes located to the right of the channel designator.
FIGURE 2-4:Style B Channel Connections
Normally Ope Co tact Device
2.2K EOL Resistor
P/N 27070
Cha el/I put Labels
411udchl.cdr

Output Ci cuits
18 Document #50759 Rev.C 3/07/00 P/N 50759:C
2.4 Output Ci cuits
Relays
The 411UD provides one Form-C relay rated for 2.0 amps @ 30 VDC (resistive). The relay is programmable for
activation on fire alarm, host panel trouble, fire supervisory, process monitoring, total communication failure, AC
loss, DACT trouble and security alarm.
Relay Label
Note that space is provided for labeling the function of the relay. Write the function that has been programmed for
the relay in the white box located below the relay designator.
FIGURE 2-5:P og ammable Relay
Relay Label
O e Form-C Relay
411udcvr.cdr

Document #50759 Rev. C 3/07/00 P/N 50759:C 19
Telephone Ci cuits
2.5 Telephone Ci cuits
Provision to connect two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 ( econdary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. (RJ31X jacks must be ordered separately).
CAUTION: It is critical that the 411UD be located as the first device on the incoming telephone circuit to
properly function.
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
RJ31X
JACK RJ31X
JACK
J2
PH1
PH2
FIGURE 2-6:Wi ing Phone Jacks
To Premises Pho e
Gree Wire
Red Wire
Red Wire
Tip
Ri g
Ri g
Tip
Ri g
Tip
Ri g
Tip
To Premises
Pho e
(Primary Li es)
I comi g Telco
Pho e Li es
(Seco dary Li es)
I comi g Telco
Pho e Li es
Note: Shorti g bars
i side RJ31X Jack
removed duri g
male plug i sertio
7 foot Cable (MCBL-7)
Not supplied - Order
Separately
Modular
Female
Co ector
Seco dary Pho e Li e
PH2
Male Plug Co ectors
Primary Pho e Li e
PH1
411UD
Gree Wire
411jack.cdr

Optional P og amme
20 Document #50759 Rev.C 3/07/00 P/N 50759:C
2.6 Optional P og amme
The optional Fire-Watch 411 eries DACT Programmer (Model PRO-411) is used to:
✓switch between the digital communicator's five Modes of operation
✓set the digital communicator's 24 hour internal clock in Real-Time Clock Mode
✓program the 411UD digital communicator in Program Mode
✓test the telephone lines interconnect in Troubleshoot Mode
✓return all digital communicator programming to the factory default settings in Default Mode
To use the PRO-411 Programmer:
1. Remove all power from the 411UD
2. Remove the two screws holding the 411UD cover in place and remove the cover
3. Connect the Programmer cable to connector J2 located in the upper right corner of the 411UD. Note that the
key on the connector must align with the slot in the J2 connector
4. Reapply power to the 411UD
5. Operate the Programmer by pressing the MO E key. Enter the appropriate four digit code and then press the
[ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the four Channels is programmed
for fire alarm, fire supervisory or security alarm, and is active, that is, in alarm (shorted).
FIGURE 2-7:P og amme Connection to 411UD
Cable attached to Programmer
411UD
Programmer
J2 co ector
411udpro.cdr
Table of contents