Fire Pro FP-08917 User manual

Local Application Fire System
FP-08917
Rev 3.1
Page | 1
CONTENTS
1General Operations ..................................................................................................................2
2Components ...............................................................................................................................3
3Specifications .............................................................................................................................3
4Installation....................................................................................................................................4
5Servicing & Maintenance.........................................................................................................5
6Operation -Activation ...............................................................................................................5
7Installation of FirePro Generators .........................................................................................6
8Connection of Multiple FirePro Generators ....................................................................... 7
9Safety Data Sheet (SDS) ..........................................................................................................8

Local Application Fire System
FP-08917
Rev 3.1
Page | 2
1General Operations
The FirePro local application system is suitable for cabinet protection and other small risk areas. The
system can be connected to a range of available power supplies OR a separate battery may be
connected. The system will draw no current when not activating, so no draw on available power.
This is system can be configured for AUTOMATIC or MANUAL activation.
1.1 The FP-08917 assembly is a non-monitored single detection zone. It designed to operate with
FirePro Condensed aerosol generators.
1.2 Can be configured to operate:
a. Automatic, using Linear Heat Detection Cable which will activate the system.
b. Manual –using a manual activation switch - FP-14053 switch.
c. Combination –which will allow automatic via the LHD or manual from the switch.
1.3 Power Supply –designed to operate on 6 to 30vDC supply. Number of FirePro units will depend
on incoming power supply.
1.4 A thermal Fuse –FP-08825 may be connected to give a signal that system has operated.
1.5 When a fire is detected by the LHD cable (if Installed), the system will operate immediately.
Pressing the manaul switch (if installed) will also operate the system immediately.
How Does it Work
All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound.
Upon activation, the solid compound is transformed into a rapidly expanding, highly efficient gas,
based on Potassium salts. It does not deplete oxygen levels. Its built-in fail-safe activation system
ensures operation of the generators when required, even if everything else fails. The FirePro Aerosol
Generators have a certified life of 15 years, with minimal maintenance required.
Ozone Depletion Potential (O.D.P.) = 0
Atmospheric Life Time (A.L.T.) = 0
Global Warming Potential (G.W.P.) = 0
Non-corrosive & Non-toxic

Local Application Fire System
FP-08917
Rev 3.1
Page | 3
2Components
FP-08917
Local Application system
1 x FP-08917 Y Connector
2x DP-3000 Deutsch Plug 3 Pin M/F, c/w heatshrink
2x DP-2000 Deutsch Plug 2 Pin M/F, c/w heatshrink
1 x End-of-line Plug
Installation & Operators Manual
Agent Release Circuit
FP-8919
Splitter Cable for installaion of multiple
FirePro generators.
FP-08825
Thermal Fuse –used to provide
signal that system has operated.
FirePro Condensed Aerosol Generators
FirePro Aerosol Generator
20g –500g Unit.
Constructed from S Steel. Complete with
Deutsch Plug for easy install.
FP-6200
Heavy Duty Bracket 316 SS.
Suits FP-100, 200, 500 FirePro Aerosol
Generators.
FirePro Aerosol Generator
1200g –5700g Unit.
Constructed from S Steel. Complete with
Deutsch Plug for easy install.
FP-6100
Heavy Duty Bracket 316 SS.
Suits FP-1200, 2000, 3000 5700
FirePro Aerosol Generators.
Detection Circuit
FP-9510
Linear Heat Detection Cable 182° C
Supplied in Cut Lengths with Deutsch
Plugs for easy install.
Lengths: 1,2,4,6 & 8m
FP-14053
Heavy Duty Switch
including 316 SS Bracket.
Installation Components
Service Components
FP-9500
2 Hour Fire Rated Shielded Cable.
FP-8800
System Test Module –this unit
simulates a FirePro generator.
Signage
FP-8960
Marine Signage for the System. A sheet
of different size labels.
FP-8962
Cabinet Signage for the System. A
sheet of different size labels.
3Specifications
Max Number of FirePro Units
6v - 1 FP Unit
12v - 2 FP Units
24v - 4 FP Units
Activation Current for FirePro Units
Max 0.25A
Max 0.50A
Max 1.00A
Quiessant Current
0 A –No current drawn from supply
Power Supply
6-30vDC
Fuse for Power Supply
5A
Max Length of Linear Heat Detection
50m
Max Number of FP-14053 Switches
6 switches over 50m

Local Application Fire System
FP-08917
Rev 3.1
Page | 4
4Installation
4.1 FirePro Aerosol Genrators must be selected in accordance with approved FirePro design
calculations and guidelines. FirePro Brackets must be installed using Bolts –Tec Screws will
vibrate loose in vehicle/marine installations.
4.2 FirePro units have a self-activation temperature of 300⁰C. Placement of units should be carefully
selected.
4.3 All cabling in the FirePro Installation MUST be Installed using min 0.75mm shielded Fire Rated
Cable
4.4 Power MUST be connected directly power supply OR Battery to ensure operation of the system.
6 –30v DC. 5A fuse or circuit breaker to be installed on power supply.
4.5 Manual Actuator(s) where installed, placement is to be carefully considered –ensure that it is
easily accessible in case of emergency. Follow instructios for the installation of the FP-14053
switch.
4.6 Linear Heat Detection where installed, the system will activate automatically. Follow instructions
as per FP-09510 product manual.
Incorrect installation may cause activation.
4.7 Cable Requirements - All cabling in the FirePro
Installation MUST be done using 0.75mm shielded
Fire Rated Cable. Care taken to ensure that all
cables are isolated, and that RF shielding on cable is
stripped back to ensure that there is not accidental grounding. Cables are colour coded for easy
identification.
4.8 Extension Leads - Deutsch Plugs must be used to
ensure water-proof connections are made
throughout the installation.
Colour
Circuit
Red
Power
Yellow
Activation
Green
Detection / Manual Switch

Local Application Fire System
FP-08917
Rev 3.1
Page | 5
5Servicing & Maintenance
The FirePro Suppression system should be serviced at least every 6 months in accordance with AS
1851, more often in aggressive environments. Periodic visual inspections of the installed system must
also be conducted by the operators to ensure all installed parts are free from debris, rust, or electrical
faults. Six Monthly servicing must only be undertaken by accredited service technicians.
NO PERSONNEL SHOULD BE IN THE RISK AREA DURING TESTING
UNTIL THE FIREPRO UNITS ARE DISCONNECTED AND TEST MODULES IN PLACE
Servicing and Maintenance Procedure
5.1 Disconnect the FirePro activation circuit (Yellow) at the panel, and connect
the FirePro simulator.
5.2 Visually inspect all installed FirePro Generators, cable, connections,
detection devices and siren/strobes. Look for any signs of damage or wear
and replace as necessary.
5.3 Activate the system –after ensuring the FirePro Simulator is connected.
Note: the FirePro Simulator stay illuminated until the reset button on the
simulator is pressed.
5.4 Reconnect the FirePro activation circuit.
System Logbook
A logbook must be kept, recording all the relevant events concerning the installation. The logbook
contains the items required that give a picture and provide for the recording of various things during
the life of the installation. In the logbook you will find the following:
Content of logbook:
•General details
•Devices used
•Schematic diagrams
•Photos of the Original FirePro Installation
•Inspection reports
6Operation -Activation
Should the system be activated :
6.1 Keep the FirePro suppression gas within the risk until the fire is extinguished and not re-ignite.
6.2 In case of emergency, ensure all occupants have left the risk area and where possible alert
emergency services.
6.3 DO NOT open any doors/hatches to the risk area for at least 20 minutes, to prevent re-ignition.
6.4 After 20 minutes, the Aerosol will fall to the ground as dust. Check risk area that is safe and
commence clean-up with warm, soapy water.
6.5 The FirePro Aerosol generators are single use items, so will need to be replaced.

Local Application Fire System
FP-08917
Rev 3.1
Page | 6
7Installation of FirePro Generators
7.1 FirePro Condensed Aerosol Fire Extinguishing System Arrangement.
FirePro units and system components installed to allow inspection and maintenance.
Locate FirePro units where they are not exposed to mechanical damage, exposed to
chemicals, or weather conditions, that may render them inoperative. Protective provisions
shall be adopted, if necessary.
Firepro units shall be securely installed. Use heavy duty brackets where necessary.
Brackets should be capable of handling the risk evironment, including vibration.
7.2 Firepro units must be installed at NOT less than the minimum safe distances as specified in the
design calcuations.
7.3 Means for prompt rescue of any trapped personnel shall be provided, including:
Adequate aisle ways/routes of exit.
Alarms –audible and visual, that operate immediately on detection of the fire.
Signs in accordance with relevent standards for the installation.
7.4 System components shall be positioned to the minimum clearances from energized electrical
parts as per:AS 4487 and AS 3000.
7.5 Handling and Storage - when handling theCondensed Aerosol Generators do not:
•Disassemble the unit
•Carry out any welding work in the vicinity of
the fire extinguishing system components.
•Exert force or impact which creates
physical or mechanical damage to the
casing.
STORAGE and OPERATIONAL CONDITIONS
•Temperature: –54 and +54°C
•Humidity: maximum 98% RH
•Service life: 15 years (date of manufacture appears on each generator)
7.6 Positioning
CORRECT
FP Units directing the aerosol stream away from opening
INCORRECT
FP units are directing the stream towards the opening.

Local Application Fire System
FP-08917
Rev 3.1
Page | 7
FP Unit 1
FP Unit 2
FP Unit 1
FP Unit 4
Activation
Cable
Splitter
Lead
Extension Lead
FP Unit 2
Activation
Cable
Extension Lead
Splitter Lead
FP Unit 3
8Connection of Multiple FirePro Generators
Where multiple FirePro Generators are installed, they must be connected
using the FP-08919 Splitter Lead. The Splitter Lead enables the activation
current to pass to all FirePro generators and for monitoring of the circuit.
Splitter Leads can be installed at any point on the activation circuit and do
not need to be installed adjacent to the fire control panel. For ease of install, servicing and more efficient
field wiring, Splitter Leads should be installed in areas easy to access and minimise extension leads.
Installation
8.1 FirePro generators must remain disconnected until system is completed and fire control panel is
no longer in a fault or alarm condition. The FirePro Universal Test Module (P/N FP-08800) can be
used to take the panel out of a fault condition.
8.2 The supply voltage of any system will determine the wiring which can be used
6vDC Max = 1 FP Units
12vDC Max = 2 FP Units
24vDC Max = 4 FP Units
8.3 Where additional units are required in the system a discharge delay module may be required.
Need to check the system manual for specifications.
8.4 Connection of units
Connection of 2 FirePro Units
Connection of 4 FirePro Units

Local Application Fire System
FP-08917
Rev 3.1
Page | 8
9Safety Data Sheet (SDS)
This is an EXTRACT ONLY from the full SDS. The SDS is prepared by Chemwatch - to view the full
SDS go to
www.chemwatch.com.au
.
PRODUCT NAME CELANOVA FIREPRO
PRODUCT USE Fire extinguishing
agent.
HAZARDOUS SUBSTANCE. DANGEROUS GOODS.
According to NOHSC Criteria, and ADG Code.
POISONS SCHEDULE - None
RISK
SAFETY
•Contact with combustible material may cause fire.
•Harmful if swallowed
•Irritating to eyes and skin.
•May cause SENSITISATION by skin contact.
•Harmful to aquatic organisms may cause long-
adverse effects in the aquatic environment.
•Cumulative effects may result following exposure
•May produce discomfort of the respiratory. system*
•Possible respiratory sensitiser*.
•May possibly affect fertility* (limited evidence).
•Keep away from combustible material
•Avoid exposure - obtain special instructions before use.
•To clean the floor and all objects contaminated by this
material use water and detergent.
•Keep away from food drink and animal feeding stuffs.
•In case of contact with eyes rinse with plenty term of water
and contact Doctor or Poisons Information Centre.
•If swallowed IMMEDIATELY contact Doctor or. Poisons
Information Centre (show this container or label).
•This material and its container must be disposed of as
hazardous waste.
FIRST AID MEASURES
SWALLOWED
•If swallowed do NOT induce vomiting.
•If vomiting occurs, lean patient forward or place on left side (head-down position, if possible) to
maintain open airway and prevent aspiration. Observe the patient carefully.
•Never give liquid to a person showing signs of being sleepy or with reduced awareness.
•Give water to rinse out mouth, then provide liquid slowly and as much as casualty can comfortably
drink.
•Seek medical advice.
EYE
•If this product comes in contact with the eyes:
•Wash out immediately with fresh running water.
•Ensure complete irrigation of the eye.
•Seek medical attention without delay; if pain persists or recurs seek medical attention.
•Removal of contact lenses after an eye injury should only be undertaken by skilled personnel.
SKIN
•If skin contact occurs:
•Immediately remove all contaminated clothing, including footwear.
•Flush skin and hair with running water (and soap if available).
•Seek medical attention in event of irritation.
INHALED
•If dust is inhaled, remove from contaminated area.
•Encourage patient to blow nose to ensure clear passage of breathing.
•If irritation or discomfort persists, seek medical attention.
Table of contents
Other Fire Pro Portable Generator manuals
Popular Portable Generator manuals by other brands

NEO TOOLS
NEO TOOLS 04-730 user manual

Generac Power Systems
Generac Power Systems 7117 owner's manual

Generac Power Systems
Generac Power Systems iQ2000 owner's manual

APE
APE 700VM Operation & maintenance manual

Westinghouse
Westinghouse WGen12000DFc user manual

DUROMAX
DUROMAX DUAL FUEL HYBRID ELITE XP8500EH user manual