DIN rail three
p
hase four wire ener
gy
meter
User manual
1.1 Safety instruction
1.2 Foreword
1.3 Performance criteria
1.4 Specifications
1.5 Basic errors
1.6 Description
1.7 Dimensions
1.8 Installation
1.9 Operating
1.10 Troubleshooting
1.11 Technical support

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-2- Email:sale[email protected]
m
021-60975591/ 60975592
1.1Safetyinstructions
Information for Your Own Safety
This manual does not contain all of the safety measures for operation of the equipment
(module, device), because special operating conditions, and local code requirements or
regulations may necessitate further measures. However, it does contain information
which must be adhered to in the interests of your own personal safety and to avoid
material damages. This information is highlighted by a warning triangle is represented
as follows, depending on the degree of potential danger.
Warning
Means that failure to observe the instruction can result in death, serious injury or
considerable material damage.
Caution
Means hazard of electric shock and failure to take the necessary safety precautions will
result in death, serious injury or considerable material damage.
Qualified personnel
Commissioning and operation of the equipment (module, device) described in this
manual may only be performed by qualified personnel. Qualified personnel in the
sense of the safety information contained in this manual are persons who are
authorized to commission, start up, ground and label devices, systems and circuits
according to safety and Regulatory standards.
Use for the intended purpose
The equipment (device, module) may only be used for the application cases specified in
the catalog and the user manual and only in connection with devices and components
recommended and approved by DMMetering.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport,
proper storage, installation and assembly, as well as proper operation and
maintenance. When o
p
eratin
g
electrical e
q
ui
p
ment, certain
p
arts of this e
q
ui
p
ment
automatically carry dangerous voltages. Improper handling can therefore result in
serious injury or material damage.
¾Use only isolated tools.
¾Do not connect while circuit is live (hot).
¾Place the meter only in dry surroundings.
¾Do not mount the meter in an explosive area or exposed to dust, mildew and insects.
¾Make sure the used wires are suitable for the maximum current of this meter.
¾Make sure the AC wires are connected correctly before activating the current/voltage to
the meter.
¾Do not touch the meter connecting clamps directly with your bare hands, with metal,
blank wire or other material as you will have the chance of an electricity shock and a
possible chance for health damage.
¾Make sure the protection cover is replaced after installation.
¾Installation, maintenance and repair should only be carried out by qualified personnel.

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-3- Email:sale[email protected]
m
021-60975591/ 60975592
¾Never break the seals and open the front cover as this might influence the functionality
of the meter, and will void any warranty.
¾Do not drop, or allow physical impact to the meter as there are high precision
components inside that may break or render the meter measures inaccurate.
Exclusion of liability
We have checked the contents of this
p
ublication and ever
y
effort has been made to
ensure that the descriptions are as accurate as possible.
However, deviations from the description cannot be completely ruled out, so that no
liability can be accepted for any errors or omissions contained in the information
g
iven.
T
he data in this manual are checked re
g
ularl
y
and the necessar
y
corrections
are included in subsequent editions. We are grateful for any improvements that you
care to suggest.
Subject to technical modifications without notice.
Copyright
Copyright Forlong January 2011 All rights Reserved.
It is prohibited to pass on or copy this document or to use or disclose its contents
without our express permission. Any duplication is a violation of the law and subject
to criminal and civil penalties. All rights reserved, particularly in the event of a
patent award or utility model registration.
1.2 Foreword
Thank you for purchasing the Forlong DRT-370D DIN rail three phase four wire
energy meter. The Forlong DRT-370D energy meter is the most advanced type
electronic kWh meter available at the market. With the Forlong product range we
have introduced a large scale of energy meters on the market suitable for 110V AC
to 400V AC (50 or 60Hz). Besides the normal energy meters we also developed our
own pre-paid meters with chip card, chip card re-loaders and a complete PC
management control system. For more information on other product please contact
our sales department at forlong@china-meters.com or fyl@china-meters.com.
Although we produce the Forlong DRT-370D meter according to IEC 62053-21 and
our quality inspection is very accurate there might always be a possibility that your
product shows a fault or failure for which we do apologize. Under normal conditions
yourproductshouldgiveyouyearsofbenefitandpleasure.Incasethereisproblem
with the energy meter you should contact your dealer immediately. All energy
meters are sealed with a special seal. Once this seal is broken there is no possibility
to claim for warranty. Therefore NEVER open an energy meter or break the seal of
the energy meter. The warranty time is 6 months, after production, and only valid
for construction faults.

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-4- Email:sale[email protected]
m
021-60975591/ 60975592
1.3 Performance criteria:
Operating humidity ≤75%
Storage humidity ≤95%
Operating temperature -10°C - +50°C
Storage temperature -30°C - +70°C
International standard IEC 62053-21
Accuracy class 1
Protection a
g
ainst penetration
of dust and water IP51
Insulatin
g
encased meter of
protective class II
1.4 Specifications:
Nominal voltage (Un) 230/400V AC (3~)
Operational voltage 161/279 – 300/520V AC (3~)
Insulation capabilities:
-ACvolta
g
e withstand 4KV for 1 minute
- Impulse voltage withstand 6KV – 1.2µS waveform
Starting current (Ist) 0.04A
Transitional current(Itr) 1.0A
Minimum current 0.5A
Reference current (Iref) 10A
Maximum current (Imax) 100A
The current measuring range 0.5-10(100)A
Peak current withstand 3000A for 0.01s
O
p
erational fre
q
uenc
y
ran
g
e 50Hz ±10%
Internal power consumption ≤2W / 10VAper phase
Test output flash rate (PULSE LED) 400imp/kWh
pulse output rate 400imp/kWh
1.5 Basic errors:
With balanced
loads
Cosφ=1 ±1.5
0.1Ib Cosφ=0.5L ±1.5
Cosφ=0.8C ±1.5
0.1Ib - Imax Cosφ=1 ±1.0
0.2Ib - Imax Cosφ=0.5L ±1.0
Cosφ=0.8C ±1.0
%
With single phase load
0.1Ib - Imax Cosφ=1 ±2.0
0.2Ib - Imax Cosφ=0.5L ±2.0
%

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-5- Email:sale[email protected]
m
021-60975591/ 60975592
1.6 Description
AFrontpanel
BCover
CBase
DProtectionCover
ESecurityhasp
Material
Front panel PC inflammable retarding
Protection cover ABS/PC alloy inflammable retarding
Cover ABS/PC alloy inflammable retarding
Base ABS/PC alloy inflammable retarding
AB
ED
C

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-6- Email:sale[email protected]
m
021-60975591/ 60975592
1.7 Dimensions
Height 140mm
Height without protection cover 90 mm
Width 70 mm
Depth 64 mm
Size of connection clam
p(
L×H
)
8×8mm
Size of connection clamps(Diagonal) 11.3mm
Weight 0.42 Kg (net)
1.8 Installation
CAUTION
¾Turn off and lock out all power supplying the energy meter and the
equipment to which it is installed before working on it.
¾Always use a properly rated voltage sensing device to confirm that power is
off.
WA
R
NING
¾Installation should be performed by qualified personnel familiar with
applicable codes and regulations.
¾Use isolated tools to install the meter.
¾Fuse or thermal cut-off or single-pole circuit breaker can
’
tbefittedonthe
supply line and not the neutral line.
-We recommend that the connecting wire which is used to connect the meter to
outside circuit should be sized according to local codes and regulations for the
ampacity of the circuit breaker or over current device used in the circuit.
-An external switch or a circuit-breaker should be installed on the inlet wire,
which will be used as a disconnection device for the meter. And there it is
recommended that the switch or circuit-breaker be near the meter so that it is
convenient for the operator.
T
he switch or circuit-breaker should comply with
the specifications of the building electrical design and all local regulations.
-This meter can be installed indoor directly, or in a meter box which is waterproof
outdoor, subject to local codes and regulations.
-To prevent tampering, secure the meter with a padlock or a similar device.
-The meter has to be installed against a wall which is fire resistant.
-The meter has to be installed in a
g
ood ventilated and dr
y
p
lace.
-The meter has to be installed in a protection box when placed in dangerous or
dusty environments.
-The meter can be installed and used after being tested and sealed with a letter
press printing.
-The meter can be installed on a 35mm DIN rail.
-The meter should be installed in an available height so that it is easy to read.
-When the meter is installed in an area with frequent surges due to e.q.
thunderstorms, welding machines, inverters etc, protect the meter with Surge

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-7- Email:sale[email protected]
m
021-60975591/ 60975592
Protection Devices
-After finishing installation, the meter must be sealed to prevent tampering.
-Connection of the wires should be done in accordance with the underneath
connection diagram.
L1 L1 phase wire
L2 L2 phase wire
L3 L3 phase wire
NNeutralwire
20 and 21 Pulse out
p
ut contact
1.9 Operating
Working indication
On the DRT-370D’s front panel, there are three power indicating LED which have
different color from each other. The yellow LED represent L1 phase; the green LED
represent L2 phase; the red LED represent L3 phase. When any phases work normally,
the LED representation will burn. When any phases have failure or no power, the LED
will turn off.
Consumption indication
There is a PULSE LED which is used as indicating power consumption in the front panel
of DRT-370D When consumption happens, the LED will flash. The more quickly LED
flash, the more consumption there is. For this LED, the flash rate is 400 impulses per
kWh (2.5Wh/imp).
Reverse indication
There is REV. LED on DRT-370D front plate. When meter load current flow is reverse,
the LED lighten.
Reading the meter
The DRT-370D energy meter is equipped with a 5+2 LCD display which is used as
recording consumption and can’t be reset to zero.
T
he number system is based on units
of 10.And unit is kWh.

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-8- Email:sale[email protected]
m
021-60975591/ 60975592
Pulse output
The DRT-370D DIN rail energy meter is equipped with a pulse output which is fully
separated from the inside circuit. That generates pulses in proportion to the measured
energy for remote reading purposes and accuracy testing. The pulse output is a polarity
dependant, passive transistor output requiring an external voltage source for correct
operation. For this external voltage source, the voltage (Ui) should is 5-27V DC, and
the maximum input current (Iimax) is 27mA DC. To connect the impulse output,
connect 5-27V DC to connector 20 (anode), and the signal wire (S) to connector 21
(cathode). The meter pulses 800 per kWh (1.25Wh/imp).
1.10 Troubleshooting
CAUTION
¾During repairing and maintenance, do not touch the meter connecting
clamps directly with your bare hands, with metal, blank wire or other
material as you will have the chance of an electricity shock and a possible
chance for health damage.
¾Turn off and lock out all power supplying the energy meter and the
equipment to which it is installed before opening the protection cover to
prevent the hazard of electric shock.
WA
R
NING
¾Maintenance or repair should be performed by qualified personnel familiar
with applicable codes and regulations.
¾Use insulated tools to maintain or repair the meter.
¾Make sure the protection cover is in place after maintenance or repair.

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-9- Email:sale[email protected]
m
021-60975591/ 60975592
Problem Check Solution
No li
g
ht for the
Power supply
indicator (L1, L2
&
L3 LED
)
.
Is AC power
supply connected
to the
meter ?
Is the L1, L2, L3
and
N
connecting
correct ?
Maybe there is
Check switch or circuit-
breaker and fuse or thermal
cut-off.
Reinstallterminalscrewsonthe
L1, L2, L3 and N. Make sure all
screws are fixed. Than there
should be a 230V 50Hz AC
voltage between the terminal
screws on the N and L1 or L2
or L3, when power supply is
input.
Please contact technical
support to replace this meter.
No light for
the
consumption
indicator (PULSE
&SOLED).
Is the
load
running
?
Is the
operating
power too
low ?
Only when load is running, this
LED will flash.
If the operating power is too
low, the spacing interval of the
flashes will take some more
time,thisiswhyitseemslike
the LED isn’t burning.
Please contact technical
support to replace this meter.
Continue.

DR
T
-370D use
r
m
anual
Shanghai Fengyilong Electronic Co. Ltd. ww
w
.china-meters.com
-10- Email:sa[email protected]
m
021-60975591/ 60975592
Problem Check Solution
The register
can
’
t run.
Is there a
power supply
inside the
meter ?
Is the
operating
power too
low ?
Maybe there is
Check that the power supply
indicator ( L1, L2 & L3 LED )
is
burnin
g
.
If the operating power is too
low, the spacing interval of the
pulses will take some more
time, this is why it seems like
the register can’t run.
Please contact technical
support to replace this meter.
No
p
ulse out
p
ut. Is DC power
supply connected
to the
meter ?
Is the
connection
correct ?
Maybe there is
a fault in the
Check the external volta
g
e
source
(Ui) is 5-27V DC.
Check correct connection:
connect 5-27V DC to connector
20 (anode), and the signal wire
(S) to connector 21 (cathode).
Please contact technical
support to replace this meter.
Pulse output
rate wrong.
Maybe there is
a fault in the
inside
circuit.
Please contact technical
support to replace this meter.
1.11 Technical support
Any questions, please contact:
TEL: 021-60975591/60975592
FAX: 021-60975593
Email: sale02@china-meters.com
www.china-metes.com