Foxtron SERInet User manual

User manual
version 1.0
SERInet
converter RS485 / Ethernet
power supply passive PoE or 9 32V
communication indication on the serial
line
galvanic separation RS485 / ETH
installation on the DIN rail (2 modules)
Terminals RJ15 for RS485
1www.foxtron.eu

SERInet is a converter from RS485 to Ethernet (TCP/IP). Converter is possible to be
supplied passive PoE thanks to the Ethernet data cable or by power supply on the
terminals.
Technical specification
bus RS485, Ethernet
speed (ETH) 10/100M
protocol (ETH) TCP/IP
supply voltage 9 32 V
consumption 1,5 W
50 150 (supply 32 9V) mA
consumption (RS485) 5 mA
wires cross section 0,08 – 1,5 mm2
ingress protection degree IP20
galvanic separation RS485 / ETH 4 kV
ambient working temperature 25 ÷ 60 °C
storage temperature 25 ÷ 60 °C
weight 80 g
Consumption depending on voltage supply
2www.foxtron.eu

Signalization
ETH Connection to the Ethernet network
100M
Ethernet speed
it is off 10Mbit
it is on 100Mbit
Tx
Sending of the data on RS485
blinking signalizes outgoing data on the serial line
Rx
incoming communication on RS485 bus
blinking signalizes incoming data to the serial line
3www.foxtron.eu
SERInet
Rx
Tx
Serial / Ethernet Converter
ETH 100M
ETH
passive PoE
9 32V

Terminals connection
SERInet in variant „SERInet RJ“ has on the side two equal connectors RJ15 (another
variant is „SERInet ST“ with six pin screw terminals).
designation description
ETH Ethernet, passive PoE power supply
V+ power supply of the bus RS485, 9 32V
GND ground for power supply of the bus RS485
PEXbus connector PowerExpress bus (type RJ15)
IN 9 32VDC external DC 9 32V (alternative to PoE)
wires preparation:
Power supply
This unit has two power supply options, passive PoE or external supply on the terminals IN
9 32VDC. Consumption in both cases is 1,5W (supply current is in both cases dependent
on the connected voltage).
Passive PoE
Power supply is distributed together with the Ethernet to the ETH
connector. Power supply is inserted in the data cable using the
common passive PoE injector. Supply voltage can be in range 9
32V.
IN 9 32VDC DC power supply 9 32V to the terminal „IN 9 32VDC“
Serial line is galvanically separated from Ethernet network and has its power supply on the
terminals V+ and GND. Supply voltage can be in range 9 32V.
Protocol
Data are sent to the Ethernet network through the TCP/IP protocol.
4www.foxtron.eu
6mm
SERInet
Rx
Tx
Serial / Ethernet Converter
ETH 100M
ETH
passive PoE
9 32V
–
+
IN 9-32VDC
PEXbus (RJ 5)
PEXbus (RJ 5)

Setup
Setup of the SERInet converter is done by web browser. To the address line input the IP
address of the converter. In the factory settings the address is 92. 68. .24
If the address is unknown the converter can be found using DALIconfig program which is
downloadable for free on the www.foxtron.eu
Default Ethernet settings in show in the following picture
5www.foxtron.eu

General TCP settings
Device Name (for DHCP) SERInet name for DHCP server
Addressing Mode
Static –manual setup of the IP address
DHCP – automatic setup of the IP address using
DHCP
Device IP Address IP address of DALInet converter
(for Addressing Mode = Static)
Device Subnet Mask network mask
Device Gateway Default gateway
DNS Server Domain server address
Ethernet Link
Normal – automatic speed choice
100BT Half duplex – Ethernet speed 100Mbps
10BT Half duplex – Ethernet speed 10Mbps
TCP setup for incoming connection
Listen for incoming network
connections
turn on the possibility to connect to the SERInet
converter
Listening network port number of port on which the SERInet waits on
connection
Timeout and disconnect after this
many seconds of inactivity
The inactive time after which the SERInet terminates
the connection. Setting the parameter to 0 is this
function switched off.
Allow new connection if the existing
connection has been idle for this
many seconds
The inactive time after which is allowed to start new
connection. Setting the parameter to 0 is this
function switched off.
TCP setup for outgoing connection
Make outgoing connections
Never – SERInet converter does not create
connections
On power up – SERInet converter creates
connection after connecting power supply.
If serial data received – SERInet converter creates
connection if it receives data on the serial line
Connect on network port port number on which the SERInet creates
connection
Connect/Send to this address IP address on which the SERInet creates the
connection
Timeout and disconnect after this
many seconds of inactivity
The inactive time after which the SERInet terminates
connection it created. Setting the parameter to 0 is
this function switched off.
Retry failed outgoing connections The time after which the SERInet repeats the
6www.foxtron.eu

after this many seconds attempt to create connection
Dividing packets
Enable custom packetization logic packet dividing turn on
Use UDP instead of TCP using UDP instead TCP
Number of characters to
accumulate before sending
TCP/UDP packet( 128Max)
number of characters which will be send in one
message (maximum 128) – data will be also send if
the set time passed or the set character come
Number msec to wait for
accumulated characters:
0 waits forever
the time after which the received characters are
sent.
0 signs that the data will not be sent dependently on
the time.
Flush TCP/UDP frame when this
character is received (Enter NA to
disable)
Decimal character value (ASCII) after which
reception will be sent. If the „NA“ is input no
character is selected. For example CR (carriage
return) is 13.
By pressing the button „Submit New Settings“ the selected settings are saved.
Serial line basic setup is shown in the following picture.
.
Data Port Settings RS 485 Half Duplex – half duplex two wires RS485
RS 485 Full Duplex – full duplex four wires RS485
7www.foxtron.eu

Data Baud Rate
Communication speed choice. Selection is possible from
commonly used speeds. Choice „Custom“ sets the speed
defined by user.
Custom Baud Rate Communication speed chosen by user. Used in the case that in
„Data Baud Rate“ is set „Custom“
Data Bits number of data bits
Data Parity
None – no parity used
Odd – used odd parity
Even – used even parity
Stop Bits number of stop bits
Password setup is shown in the following picture. Password into the web configuration is
not required by default.
For change of password fill the User Name and twice new password. In the case that you
do not want to use password leave the password fields blank. By pressing the button
„Submit New Settings“ you save new password.
8www.foxtron.eu

Power Express (PEX)
In the case of using with Power Express system (PEX) it is suitable to insert
the reduction on the RJ15 connector which is used for PEX bus by default.
Recommended setup „CUSTOM PACKETIZATION“ for PEX bus.
9www.foxtron.eu

Dimensions (in mm)
tel: +420 274 772 527
e mail: [email protected]
web: www.foxtron.eu
10 www.foxtron.eu
45
90
10
58
35
35
Table of contents