
CAP 303
INLET AIR
A clean air supply is required for the satisfactory
operation of your compressor.
The inlet air filter supplied with the compressor
is of sufficient size and design to meet all normal
operating conditions
\
If it is necessary for inlet air to be taken from an
outside source, the piping should be at least the
diameter of the air filter inlet. If the distance is
over twenty (20) feet the diameter needs to be
enlarged to reduce restriction. The piping must
be corrosion resistant and cleaned thoroughly
after fabrication. The inlet must be protected to
prevent rainwater and small animals from
entering the inlet piping.
AIR DISCHARGE
Your compressor is equipped with an oil/air
cooler. On air-cooled units the cooling fan is of
sufficient size to provide adequate cooling of the
compressed air and the compression oil passing
through this cooler. We recommend a thorough
cleaning of the cooler fins periodically by
vacuum or compressed air to insure a restriction
free flow of air from the cooling fan through the
oil/air cooler.
WATER-COOLED UNITS
The cooling water supply should be checked to
make sure the flow is sufficient. The chart shown
in Figure 3-1 lists approximate minimum water
flow rates in U.S. gallons per minute at various
temperatures into the heat exchanger(s). The
water flow rate shown will cool the compressor
oil to approximately 140° F. The compressor
discharge temperature should be maintained at
160° F to 180° F under most conditions. The
water outlet temperature from the heat
exchanger will be approximately 110° F, which is
the maximum recommended to prevent heat
exchanger tube fouling and corrosion. Higher
than listed water flow rates will decrease the
water outlet temperature.
Inlet air must not contain any flammable
or toxic gases. These gases will be
concentrated by the compressor and
could result in property damage, personal
injury or death.
Inlet air containing reactive gases will
cause failure of the lubricant and
compressor. Insure an air supply that is
well clear of any reactive gases.
HP Inlet Water Temperature
60°F 70°F 80°F 90°F
15 1.6 2.0 2.8 4.0
20 2.2 2.8 3.7 5.5
25 2.8 3.3 4.3 6.5
30 3.1 4.0 5.5 8.0
40 4.4 5.5 7.3 1.0
50 5.5 6.5 8.5 13.0
Figure 3-1
Water Flow Rates (U.S. gal/min)
The size of the incoming water supply piping
should be at least equal to the connections
provided with the compressor.
ELECTRICAL CONNECTIONS
All internal wiring has been done at the factory.
Wiring of the power supply to the compressor
should be done by a qualified electrician to
comply with the National Electric Code, state
code and any local codes in accordance with the
wiring diagram specific to your compressor
model shown in the “SPECIFICATIONS” section
of this manual.
Inadequate airflow will cause the
compressor to run hot which can cause
damage to the compressor and increase
oil carryover.
Water-cooled units must not be exposed to low
temperatures below 40°F, 4.4°C.
7