GÜDE Expert Sensor Box 7213 User manual

Manual
Expert Sensor Box 7213
Expert Sensor Box 7214
© 2022 GUDE Systems GmbH
Manual Ver. 1.3.1
from Firmware Ver. 1.3

2
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH

3
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Table of contents
1. Device Description 5
1.1 Security Advice .............................................................................................................. 6
1.2 Content of Delivery ........................................................................................................ 6
1.3 Description ..................................................................................................................... 6
1.4 Installation ...................................................................................................................... 7
1.4.1 Terminal Assignment ............................................................................................... 8
1.5 Redundant Voltage Supply ........................................................................................... 9
1.6 Technical Specifications .............................................................................................. 10
1.7 Sensor ........................................................................................................................... 10
2. Operating 13
2.1 Operating the device directly ..................................................................................... 14
2.2 Control Panel ................................................................................................................ 14
2.3 Maintenance ................................................................................................................ 16
2.3.1 Maintenance Page ................................................................................................. 18
2.3.2 Configuration Management ................................................................................... 19
2.3.3 Bootloader Activation ............................................................................................. 21
3. Configuration 23
3.1 Output Ports ................................................................................................................ 24
3.1.1 Watchdog ............................................................................................................... 25
3.2 Input Ports .................................................................................................................... 27
3.3 Ethernet ........................................................................................................................ 28
3.3.1 IP Address ............................................................................................................... 28
3.3.2 IP ACL ..................................................................................................................... 30
3.3.3 HTTP ....................................................................................................................... 31
3.4 Protocols ....................................................................................................................... 32
3.4.1 Console ................................................................................................................... 32
3.4.2 Syslog ..................................................................................................................... 33
3.4.3 SNMP ...................................................................................................................... 34
3.4.4 Radius ..................................................................................................................... 36
3.4.5 Modbus TCP ........................................................................................................... 37
3.4.6 MQTT ...................................................................................................................... 38
3.5 Clock .............................................................................................................................. 39
3.5.1 NTP ......................................................................................................................... 39
3.5.2 Timer ...................................................................................................................... 40
3.5.3 Timer Configuration ............................................................................................... 40
3.6 Sensors .......................................................................................................................... 47
3.6.1 Port Switching ......................................................................................................... 48
3.7 E-Mail ............................................................................................................................ 49

4
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Table of contents
4. Specifications 51
4.1 Automated Access ....................................................................................................... 52
4.2 Messages ....................................................................................................................... 52
4.3 IP ACL ............................................................................................................................ 54
4.4 IPv6 ................................................................................................................................ 55
4.5 Radius ............................................................................................................................ 55
4.6 SNMP ............................................................................................................................ 56
4.6.1 Device MIB 7213 .................................................................................................... 59
4.6.2 Device MIB 7214 .................................................................................................... 60
4.7 SSL ................................................................................................................................. 62
4.8 Console .......................................................................................................................... 64
4.8.1 SSH .......................................................................................................................... 68
4.8.2 Console Cmd 7213 ................................................................................................. 69
4.8.3 Console Cmd 7214 ................................................................................................. 75
4.9 Modbus TCP .................................................................................................................. 83
4.9.1 Sensor Tables ......................................................................................................... 89
4.10 MQTT ............................................................................................................................. 89
4.10.1 Example HiveMQ .................................................................................................... 92
5. Support 94
5.1 Data Security ................................................................................................................ 95
5.2 Contact .......................................................................................................................... 95
5.3 Declaration of Conformity .......................................................................................... 96
5.4 FAQ ................................................................................................................................ 96
98
Index

Device Description

6
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
1 Device Description
1.1 Security Advice
·The device must be installed only by qualified personnel according to the following in-
stallation and operating instructions.
·The manufacturer does not accept responsibility in case of improper use of the device
and particularly any use of equipment that may cause personal injury or material dam-
age.
·The device contains no user-maintainable parts. All maintenance has to be performed
by factory trained service personnel.
·The device may only be connected via a low voltage power supply to 230V AC (50 Hz
or 60 Hz) power supply sockets.
·The device is intended for indoor use only. Do NOT install them in an area where ex-
cessive moisture or heat is present.
·Because of safety and approval issues it is not allowed to modify the device without
our permission.
·The device is NOT a toy. It has to be used or stored out of range of children.
·Care about packaging material. Plastics has to be stored out of range of children.
Please recycle the packaging materials.
·In case of further questions, about installation, operation or usage of the device, which
are not clear after reading the manual, please do not hesitate to ask our support team.
1.2 Content of Delivery
The package includes:
·Expert Sensor Box 7213 / 7214
·Power supply unit 7903 (12V DC, 1 A) (for 7213-1, 7213-2, 7213-3)
·Quick Start Guide
1.3 Description
Depending on the model, the Expert Sensor Box 7213 / 7214 offers several environ-
mental sensors. The device has the following features:
Devices with voltage input:
·Temperature Sensor (Expert Sensor Box 7213-1 / 7214-1)
·Sensors for temperature and humidity (Expert Sensor Box 7213-2 / 7214-2)
·Sensors for temperature, humidity and air pressure (Expert Sensor Box 7213-3 /
7214-3)
Devices with additional Power-over-Ethernet (PoE):
·Temperature Sensor (Expert Sensor Box 7213-11 / 7214-11)
·Sensors for temperature and humidity (Expert Sensor Box 7213-12 / 7214-12)
·Sensors for temperature, humidity and air pressure (Expert Sensor Box 7213-13 /
7214-13)

7
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
General:
·Connection for 2 optional sensors for ambient monitoring (temperature, humidity and
air pressure)
·Console commands via SSH and Telnet
·SSH support with public key and passwords
·Programmable timetables for console commands
·Dual TCP/IP stack with IPv4 and IPv6 support (IPv6-ready)
·Control and monitoring of the device via Ethernet with an integrated web server with
SSL encryption (TLS 1.1, 1.2, 1.3)
·Configuration with CGI parameters and JSON messages via HTTP (REST API)
·SNMP (v1, v2c and v3, traps)
·MQTT 3.1.1 Support
·Modbus TCP support
·Radius support
·Generation of messages (e-mail, syslog and SNMP traps) depending on sensor meas-
urement limits
·Firmware update during operation via Ethernet possible
·Encrypted e-mails (SSL, STARTTLS)
·Access protection through IP access control
·Low own consumption
·Developed and produced in Germany
Additionally with Expert Sensor Box 7214:
·An additional input for redundant voltage supply (12 V DC 1 A)
·A switchable, potential-free relay output with change-over contact (NO and NC), high
switching capacity 36 V, 3 A
·The relay has high contact reliability even at very small loads
·Switch state and switch-on delay (0 ... 9999 seconds) can be set for the relay output
after power failure
·Programmable timetables and turn-on/turn-off sequences
·A watchdog (ICMP / TCP) can be assigned to the output port
·Passive signal input for polling NO/NC devices (e.g., smoke detector, leak sensor,
door contact)
·The signal input has a 12 V connector for supplying the NO/NC devices
1.4 Installation
1. Connector Sensor Port 1

8
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
2. Connector Sensor Port 2
3. Ethernet connector (RJ45) (with Pwr3 = only devices with PoE)
4. Status LED
5. Connector (Pwr1) for power supply 12 V DC, 1 A
1. Housing for integrated Sensor
2. Connector (Pwr2) for power supply 12 V DC, 1 A (only ESB 7214)
3. Passive input (only ESB 7214)
4. Potential-free relay output (only ESB 7214)
5. Select Button
Power Supply
If the device has PoE or a second input for the supply voltage, all voltage sources can be
connected at the same time. This allows redundancy in the power supply.
Start-up the device
·Connect the device (Pwr1 oder Pwr2) to the AC Adaptor (12 V DC, 1 A).
·Optional connect the device to a second AC Adaptor (12 V DC, 1 A).
·Plug the network cable into the Ethernet (RJ45).
·Attach the optional external sensors to the connectors.
·Connect the passive inputs and relay outputs to compatible devices.
1.4.1 Terminal Assignment
The terminal assignment of the terminals is printed on the housing surface:

9
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
The digital signal input (input ports) goes to the logic state "LOW"
when the pin "In" and the center pin "GND" are bridged, otherwise the
state is "HI". The text outputs associated with the "LOW" and "HI"
states can be defined in the Input Ports configuration . In the de-
fault configuration, the logic states are inverted so that the state "HI"
is assumed for a bridged contact.
This means that there is only a connection between the center pin
(COM) and the NC-pin (Normally Closed) for the output ports in the
"Off" state. If the relay is in the "On" state, then there is only contact
from the center pin (COM) to the NO-pin (Normally Open).
As an alternative to the connection of "In" and "GND", voltages of up to 24 V (= VIn-
max) can be connected to the input "In". For voltages less than 4 V the state goes to
"LOW", for voltages greater than 8 V the "HI" state is assigned.
1.5 Redundant Voltage Supply
If the device and the connected switch support Power-over-Ethernet, the power supply
via PoE has priority and the device is powered only via PoE. Alternatively, the device can
be supplied via up to two power supply units. If both power supplies (only ESB 7214) are
connected at the same time, the current is split up. The current distribution depends on
the difference between the output voltages of the two power supplies.
27

10
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
1.6 Technical Specifications
Interfaces
(only ESB 7214)
(only ESB 7214)
(only ESB 7214)
1 x socket for power supply
2 x RJ45 for external sensors
1 x Ethernet connector RJ45
1 x additional socket for power supply
1 x switchable output
1 x passive signal input
Network connectivity
10/100 MBit/s 10baseT Ethernet
Power Supply
AC Adaptor (12V DC, 1 A)
Power-over-Ethernet Module
PoE Module (not all models)
802.3af (802.3at Type 1) PoE, Class 0
Environment
·Operating temperature
·Storage temperature
·Humidity
0°C - 50 °C
-20°C - 70 °C
0% - 95% (non-condensing)
Case
Powdered steel case
Measurements
80 mm x 100 mm x 34 mm (H x W x D)
90 mm x 100 mm x 34 mm (H x W x D) (with
flaps)
Weight
approx. 280g
Plug for power supply connection:
System terminal 2-pole
AK1550/2-3.5-GREEN
Connector for switching outputs and signal inputs:
System terminal 3-pole
AK1550/3-3.5-GREEN
1.7 Sensor
Two external sensors can be connected to the Expert Sensor Box 7213 / 7214. The fol-
lowing sensors are currently available

11
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
Product Name
7101
7104-1
7105-1
7106-1
Calibrated
Sensor
-
7104-2
7105-2
7106-2
Cable length
2m
2m
2m
2m
Connector
RJ45
RJ45
RJ45
RJ45
temperature range
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
air humidity range
(non-condensing)
-
-
0-100%, ±3%
(maximum) and
±2% (typical)
0-100%, ±3%
(maximum) and
±2% (typical)
air pressure range
(full)
-
-
-
± 1 hPa (typical)
at 300 ... 1100
hPa, 0 ... +40 °C
air pressure range
(ext)
-
-
-
± 1.7 hPa (typical)
at 300 ... 1100
hPa, -20 ... 0 °C
Protection
IP68
-
-
-

12
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Device Description
Product Name
7201
7202
Cable length
-
-
Connector
RJ45
RJ45
temperature range
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
air humidity range
(non-condensing)
-
0-100%, ±3% (maximum) and
±2% (typical)
The sensors are detected automatically after connection. The green LED on the RJ45
sensor connector then lights up permanently. If the sensor value is displayed perman-
ently on the display, the green LED flashes. The sensor values are displayed directly
on the "Control Panel" website:
A click on the link in the "Name" column opens the display of the Min and Max values.
The values in a column can be reset using the "Reset" button. The "Reset" button in the
name column deletes all stored Min and Max values.

Operating

14
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
2 Operating
2.1 Operating the device directly
Status-LED
The Status LED shows the different states of the device:
·red: The device is not connected to the Ethernet.
·orange: The device is connected to the Ethernet and waits for data from the DHCP
server.
·green: The device is connected to the Ethernet and the TCP/IP settings are allocated.
·periodic blinking: The device is in Bootloader mode.
Switching the relay with the button (only ESB 7214)
Press and hold the button for a total of 6 seconds. After the first 3 seconds the status
LED flashes in a long ON, short OFF rhythm. Wait another 3 seconds, and the status
LED flashes in a twice short, and once long rhythm. At this moment, press the button
once again briefly to switch the relay, or if you wait 6 seconds instead, the device re-
turns to its initial state.
2.2 Control Panel
The relay output, the passive signal input and the additional input for the power sup-
ply are only available on the Expert Sensorbox 7214. The possibility of power supply via
Power-over-Ethernet (PoE) also varies depending on the model.
Access the web interface: http://"IP-address" and log-in.
The web page provides an overview of the switching state, the sensor, as well as the ex-
ternal sensors, provided that they are connected. When the port is clicked, a panel with
buttons to control the port appears:

15
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
The Port icon is green when the relay is closed, or red in the open state. An additional
small clock icon indicates that a timer is active. Timer can be activated by delay, reset
or batch mode.
An activated Watchdog is represented by an eye icon. An "X" means, that the address
that should be observed, could not be resolved. Two circular arrows show a booting
status.
The port can be switched manually with the "On" and "Off" buttons. If the port is turned
on, it can be turned off by pressing the "Reset" button, until after a delay it turns itself on
again. The delay time is determined by the parameter Reset Duration, which is de-
scribed in the chapter "Configuration - Output Ports ". The "Close" button dissolves
the panel again.
Batchmode
The port can be set for a selectable period of time to the state "switch on" or "switch
off". After the selected time it is automatically switched to the second preselected state.
Optionally the device can be switched via a Perl script or external tools like wget. More
information is available on our support wiki at www.gude.info/wiki.
The web page contains a status overview of the passive signal input, the time since the
last change, and a counter of the switching cycles. The name and text for a logical state
of the input is configured in the chapter Configuration-Input Ports .
24
27

16
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
The voltage inputs (Pwr1 and Pwr2) shows if they are connected to a power supply or
Power-over-Ethernet (PoE) is active.
2.3 Maintenance
The actual device generation with IPv6 and SSL allows all maintenance functions in the
web interface to be carried out on the Maintenance Page .
Maintenance in the web interface
The following functions are available from the maintenance web page:
·Firmware Update
·Change the SSL certificate
·Load and save the configuration
·Restart the device
·Factory Reset
·Jump into the Bootloader
·Delete the DNS cache
Upload Firmware, Certificate or Configuration
On the Maintenance Page , select the required file with "Browse .." in the sections
"Firmware Update", "SSL Certificate Upload" or "Config Import File Upload" and press
"Upload". The file is now transferred to the update area of the device and the contents
are checked. Only now, pressing the "Apply" button will permanently update the data, or
abort with "Cancel".
Only one upload function can be initiated with a reboot, eg. you cannot transmit firm-
ware and configuration at the same time.
If after a firmware update, the web page is not displayed correctly anymore, this may
be related to the interaction of Javascript with an outdated browser cache. If a Ctrl-F5
does not help, it is recommended that you manually delete the cache in the browser op-
tions. Alternatively, you can test start the browser in "private mode".
During a firmware update, old data formats are sometimes converted to new struc-
tures. If an older firmware is newly installed, the configuration data and the energy
meters may be lost! If the device then does not run correctly, please restore the factory
settings (e.g. from the Maintenance Page ).
18
18
18

17
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
Actions in Bootloader mode
If the web interface of the device is no longer accessible, the device can be put into
Bootloader mode (see chapter Bootloader activation ). The following functions can be
executed using the GBL_Conf.exe application:
·Set IPv4 address, net-mask and gateway
·Turn HTTP password on and off
·Turn IP-ACL on and off
·Factory Reset
·Allow jump from firmware to bootloader
·Restart the device
For devices with relays, entering or exiting the bootloader mode does not change
the state of the relays as long as the operating voltage is maintained.
The GBL_Conf.exe program is available free of charge on our website www.gude.info and
can also be found on the enclosed CD-ROM.
Interface GBL_Conf
To check the network settings with GBL_Conf.exe, start the program and choose "All
Devices" in the "Search" menu. From the list select the appropriate device. The lower
part of the left half of the window now shows the current network settings of the device. If
the IP address is displayed with the default settings (192.168.0.2), either no DHCP
server is present on the network, or there could be no free IP address assigned to it.
·Activate the Bootloader Mode (see Chapter Bootloader Mode) and choose in menu
"Search" the item "Bootloader-Mode Devices only"
·Enter the desired settings in the edit window and save them with "Save Config".
·Deactivate the boot loader mode for the changes to take effect. Select again "All
Devices" in the "Search" menu of GBL_Conf.exe.
21

18
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
The new network configuration is now displayed.
Changing the configuration with gbl_conf.exe is explicitly only allowed in bootloader
mode!
Factory Reset
The device can be reset to the factory default via the web interface from the Maintenance
Page or from the Bootloader mode (see chapter Bootloader activation ). All TCP/IP
settings are reset in this operation.
If a unit is set to factory defaults, an uploaded certificate or updated firmware will be
preserved.
2.3.1 Maintenance Page
This section provides access to important functions such as Firmware Update or Restart
Device. It is advisable to set an HTTP password for this reason.
Firmware Update: Start a firmware update.
18 21

19
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
SSL Certificate Upload: Saves your own SSL certificate. See chapter "SSL " for the
generation of a certificate in the right format.
Config Import File Upload: Loads a new configuration from a text file. To apply the new
configuration, a "Restart Device" must be executed after the "Upload".
Config File Export: Saves the current configuration in a text file.
Saving the configuration should only be carried out in an SSL connection, since it
contains sensitive password information (even if it is encrypted or hashed).
Restart Device: Restarts the device without changing the status of the relays.
Some functions such as a firmware update or changing of the IP-address and HTTP
settings require a restart of the device. A jump to the boot loader or a restart of the
device lead by no means to a change of the relay states.
Restore Fab Settings and Restart Device: Performs a restart and resets the device to
factory default .
Enter Bootloader Mode: Jumps into bootloader mode, where additional settings can be
made with GBL_Conf.exe.
Flush DNS Cache: All entries in the DNS cache are discarded and address resolutions
are requested again.
Config/Status View: status.html: Displays the status.html page with the JSON data.
Config/Status Download: export.json: Direct file download of JSON data from status.hml.
2.3.2 Configuration Management
The device configuration can be saved and restored in the maintenance area .
The "Config File Export" function can be used to save the current configuration as a text
file. The syntax used in the configuration file corresponds to the commands of the Telnet
console. If the configuration of a device is to be restored from a text file, load the file with
"Upload" and restart the device with "Restart Device".
Saving the configuration should only be carried out in an SSL connection, since it
contains sensitive password information (even if it is encrypted or hashed). For the same
reasons, it is advisable to carefully handle the generated configuration files when archiv-
ing.
Editing the configuration file
62
22
18

20
Expert Sensor Box 7213/7214 © 2022 GUDE Systems GmbH
Operating
It is possible to customize a saved configuration file with a text editor for your own
needs. For example, one scenario would be to use a script language to automate the
creation of many customized versions of a configuration, then equip a large number of
devices with an individualized configuration. Also Upload and restart with CGI commands
can be done in scripting languages. With use of the comment sign "#" you can quickly
hide single commands or add personal notes.
If you modify a configuration file manually, it is not always clear which limits are allowed
for parameters. After uploading and restarting, commands with invalid parameters are ig-
nored. Therefore, the generated configuration includes comments describing the bound-
aries of the parameters. Where "range:" refers to a numeric value, and "len:" to a text
parameter. E.g:
email auth set 0 #range: 0..2
email user set "" #len: 0..100
The command "system fabsettings" from the beginning of a generated configuration file
brings the device into the factory state, and then executes the individual commands that
modify the configuration state. It may be desirable to make the changes relative to the
current configuration, and not out of the factory state. Then the "system fabsettings"
should be removed.
No output of default values
The configuration file contains (with exceptions) only values which differ from the default.
The command "system fabsettings" (go to the factory state) from the beginning of a gen-
erated configuration file should not be removed, otherwise the device can get incom-
pletely configured.
Configuration via Telnet
The configuration files can in principle also be transferred in a Telnet session, but then
the settings are changed during operation, and not completely when restarting, as it
would have been the case with an upload. It can happen that events are triggered at the
same time as the device is configured. One should therefore:
a) disable the function
b) completely parametrize
c) reactivate the function
An example:
email enabled set 0
email sender set "" #len: 0..100
email recipient set "" #len: 0..100
email server set "" #len: 0..100
email port set 25
email security set 0 #range: 0..2
email auth set 0 #range: 0..2
email user set "" #len: 0..100
email passwd hash set "" #len: 0..100
email enabled set 1 #range: 0..1
Other manuals for Expert Sensor Box 7213
1
This manual suits for next models
1
Table of contents
Popular Network Hardware manuals by other brands

ADC
ADC ETP-64 Specification sheet

Matrix Switch Corporation
Matrix Switch Corporation MSC-2HD2432L product manual

Newtec
Newtec NTC/2142 user manual

Elk
Elk ELK-M1XEP installation manual

EdgeWave
EdgeWave iPrism Web Security Administration guide

JDS Uniphase
JDS Uniphase IP Video Test Option HST-3000 Specifications