Galaxy Aqua 9000 XP User manual

IMPORTANT!
This Step-by-Step guide should be given to the customer
after installation and demonstration.
SERVICE POLICY
In the event of you needing to contact the Galaxy Customer Service Department,
the following procedure should be followed:-
1
If a service call is booked, you or a representative must be present
during the Engineers visit.
Before telephoning the Galaxy Customer Service Department you
should ensure that you have the model number, power rating, serial
number and date of purchase.
The Galaxy Customer Service Department will be able to inform you
whether the fault can be rectified by the provision of a replacement
part or an on site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will
be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee
has been booked and a failure was not product related, or an engineer
arrives and is not able to gain access.
2
3
4
5
Pumped Instantaneous
Electric Shower
Installation Instructions
XP
Customer Service Department
Telephone: 0845 600 5111 Fax: 01489 773053
9.00 am - 5.00 pm Monday to Friday
Technical Hotline
Telephone: 0844 372 7766 Fax: 0844 372 7767
Email: technical-services@applied-energy.com
9.00 am - 5.00 pm Monday to Friday
SERVICE POLICY
In the event of you needing to contact the Galaxy Technical Hotline, the following
procedure should be followed:-
1
If a service call is booked, you or a representative must be present
during the Engineers visit.
Before telephoning the Galaxy Technical Hotline you should ensure
that you have the model number, power rating, serial number and
date of purchase.
The Galaxy Technical Hotline will be able to inform you whether the
fault can be rectified by the provision of a replacement part or an on
site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will
be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee
has been booked and a failure was not product related, or an engineer
arrives and is not able to gain access.
2
3
4
5
7300059 (B)
Technical Hotline
Telephone: 0844 372 7766 Fax: 0844 372 7767
Email: technical.services@redringxpelair.com
8.00 am - 5.30 pm Monday to Friday
SERVICE POLICY
In the unlikely event of a product breakdown during the guarantee period
you should contact our Service and Repair Helpline who will be able to assist
with the repair and advise of the best course of action to be taken.
Please DO NOT remove the product prior to making this call as this may
invalidate your guarantee.
1
If a service call is booked, you or a representative must be present
during the Engineers visit.
Before telephoning the Galaxy Technical Hotline you should ensure
that you have the model number, power rating, serial number and
date of purchase.
The Galaxy Technical Hotline will be able to inform you whether the
fault can be rectified by the provision of a replacement part or an on
site visit by a Qualified Service Engineer.
If the product is no longer covered by the Guarantee, a charge will
be made for the site visit and for any parts supplied.
A charge will be made where a call under the terms of the guarantee
has been booked and a failure was not product related, or an engineer
arrives and is not able to gain access.
2
3
4
5

690 mm
365 mm
252 mm
GUARANTEE
Redring Xpelair Group Ltd
guarantee this Galaxy product for a
period of two years, from date of
purchase, against mechanical and
electrical defects arising from faulty
materials or from poor workmanship,
providing the product has been
installed by a competent person in
accordance with the fitting instructions.
undertake to repair or replace, at
their discretion, without charge,
provided the product has been
properly maintained and operated in
accordance with the operating
instructions. Any component found
to be defective during this period,
as the result of misuse or damage,
or the effects of scaling, will not be
covered by this guarantee (with the
exception of ‘si’ (‘Scalemaster’)
models which are guaranteed
against the effects of scaling).
This product must not be modified,
repaired or taken apart except by a
person authorised by Redring Xpelair
.
This Guarantee is only valid within
the United Kingdom and does not
cover product used commercially.
This Guarantee does not affect your
statutory rights.
Redring Xpelair Group Ltd
Group Ltd
Redring Xpelair Group Ltd.,
Newcombe Way, Peterborough,
Cambridgeshire PE2 6SE
Telephone: 01733 456789 -
Fax: 01733 310606 -
Website: www.galaxy-showers.com
211

Products manufactured by Galaxy are
safe and without risk provided they are
installed, used and maintained in good
working order in accordance with our
instructions and recommendations.
DO NOT connect this shower directly
to the mains water supply.
DO NOT operate shower if frozen, or
suspected of being frozen. It must
thaw out before using.
DO NOT operate the unit if the spray-
head or spray hose becomes
damaged.
DO NOT restrict flow out of the
shower by placing sprayhead in direct
contact with your body.
DO NOT operate the shower if water
ceases to flow during use or if water
has entered inside the unit because
of an incorrectly fitted cover.
WARNING: If re-starting the shower
immediately after stopping, be aware
that a slug of hot water will be
expelled for the first few seconds.
GENERAL
1. Isolate the electrical and water supplies before
removing the cover.
2. Read all of these instructions and retain them for
later use.
3. DO NOT take risks with plumbing or electrical
equipment.
4. Isolate electrical and water supplies BEFORE
proceeding with the installation.
5. The unit must be mounted onto the finished wall
surface (on top of the tiles). DO NOT tile up to unit
after fixing to wall.
6. Contact Customer Service (see back page),
if any of the following occur;
a) If it is intended to operate the shower at pressures
above the maximum or below the minimum stated.
b) If the unit shows a distinct change in performance.
c) If the shower is frozen.
7. If it is intended to operate the shower in areas of
hard water (above 200 ppm temporary Hardness), a
scale inhibitor may have to be fitted.
8. The sprayplate and cartridge must be cleaned
regularly with descalent to remove scale and debris,
otherwise restrictions to the flow on the outlet of the
unit will result in higher temperatures and could also
cause the Pressure Relief Device in unit to operate.
9. This product is not suitable for mounting into
steam rooms or steam cubicles.
PLUMBING
1. The plumbing installation must comply with Water
Regulations, Building Regulations or any particular
regulations as specified by Local Water Company or
Water Undertakers and should be in accordance with
BS 6700.
2. The supply pipe must be flushed to clear debris
before connecting to shower unit.
3. DO NOT solder pipes or fittings within 300mm of
shower, as heat transfer can damage components.
4. DO NOT fit any form of outlet flow control as
the outlet acts as a vent for the heater can.
5. DO NOT use excessive force when making
connections to the flexible hose or sprayhead, finger
tightness is sufficient.
6. Al plumbing connections MUST be completed
BEFORE making the electrical connections.
ELECTRICAL
1. The installation must comply with BS 7671
Requirements for electrical installations’ (IEE wiring
regulations) or any particular regulations as specified
by the local Electrical Supply Company.
2. This appliance MUST be earthed.
3. In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is
intended to be permanently connected to the fixed
wiring of the electrical mains system.
4. Ensure all electrical connections are tight to
prevent overheating.
5. Fuses do not give personal protection against
electric shock.
PACK
CONTENTS
1
SECTION
PACKING CONTENTS
PACK
CONTENTS
2
SECTION
PLEASE READ THIS IMPORTANT
SAFETY INFORMATION
Shower Unit
Showerhead
Showerhead Key
Flexible Hose
Slider Rail Tube
Slider Rail Brackets
Slider Rail Showerhead Holder
Soap Dish
Hose Retaining Ring
Screw Pack
18
SECTION
FILTER MAINTENANCE
INSTRUCTIONS for INSTALLERS
and SERVICE ENGINEERS
It is recommended that the filter is
periodically cleaned in order to maintain
the performance of the shower. It is
essential that this operation is carried out
by a competent person.
SWITCH OFF THE ELECTRICITY
SUPPLY. There is no need to turn off the
mains water supply when cleaning the
filter.
Remove the cover and disconnect the
plug.Turn off the water supply to the unit
by rotating the lever on top of the filter
service shut off valve (Fig.21) anti-
clockwise a quarter turn.
Filter Service
Shut-Off
Valve
Do not rely on the filter service shut off
valve when carrying out repairs or service
to other areas of the shower unit.
Unscrew the three screws in filter cover
(Fig.22) remove cover.Take out filter and
wash under running water. Ensure all
debris etc. is removed.
Replace filter. Replace cover ensuring all
three screws line up. Replace the three
screws. DO NOT OVERTIGHTEN.
Fig.21
Turn unit water supply back on by rotating
the lever on top of the filter service shut
off valve clockwise a quarter turn.
Before replacing the cover, it is strongly
advised to prime the unit by opening the
bleed screw until water drains from it.
Close the bleed screw and connect the
plug to the cover. Replace the cover and
secure with the fixing screws.
Switch on the electric supply and start the
shower on the COLD SETTING ONLY
and with the temperature control rotated
fully anti-clockwise.
When a smooth flow of water is obtained,
the shower can then be used in the
Normal manner.
Filter Cover
Screws
ATTENTION!
NOTE: IN NORMAL USE, IT IS IN
ORDER TO LEAVE THE WATER
SUPPLYPERMANENTLYON TO THE
SHOWER UNIT, BUT AS WITH MOST
ELECTRICAL APPLIANCES, THE
UNIT MUST BE SWITCHED OFF
AT THE ISOLATING SWITCH
WHEN NOT IN USE.
Fig.12Fig.22

6. To enhance electrical safetya30mA residual
current device (RCD) should be installed in all UK
electric and pumped shower circuits. This may be
part of the consumer unit or a separate unit.
7. Switch off immediately at isolating switch if water
ceases to flow during use.
8. Other electrical equipment i.e. extractor fans,
pumps must not be connected to the circuits within
the unit.
9. Switch off at isolating switch when not in use.
This is a safety procedure recommended with all
electrical appliances.
10. As with all electrical appliances it is
recommended to have the shower and installation
checked at least every two years by a competent
electrician to ensure there is no deterioration due to
age and usage.
This book contains all the necessary fitting
and operating instructions for your Galaxy
Aqua 9000 XP pumped electric shower.
Take time to read this book thoroughly
and familiarise yourself with all
instructions before commencing
installation. Please keep it for future
reference.
The shower installation must be carried
out by a competent person and in the
sequence of this instruction book.
Do not attempt any electrical or plumbing
work necessary to install this product
unless you have good practical
experience and adequate understanding
of the IEE regulations and water
regulations
Care taken during the installation will
ensure a long, trouble-free life from your
shower.
SPECIFICATIONS
3
SECTION
INTRODUCTION
Water
Inlet connection – 15mm diameter.
Outlet connection – 1/2” BSP male thread.
Entry Points
Water and cable– bottom, top or back.
Materials
Backplate, cover, controls, sprayhead –
ABS.
Sprayplate –Acetal.
Elements – Minerally insulated corrosion
Resistant metal sheathing.
Dimensions
‘XP’
Height 365 mm
Width 252 mm
Depth 107 mm
Standards and Approvals
Splashproof rating IPX4.
Complies with the requirements of current
British and European safety standards for
household and similar electrical
appliances.
Complies with requirements of the British
Electrotechnical Approvals Board (BEAB).
Meets with Compliance with European
Electrical
Nominal power rating at 240V
8.5kW - (40A MCB rating)
9.5kW – (40A MCB rating)
Nominal power rating at 230V
8.5kW - (40A MCB rating)
9.5kW – (40A MCB rating)
The following points will help you
understand how the shower operates:
A. The electric heating elements operate
at a constant rate at your chosen power
setting. It is the flow rate of the water
Passing through the heater unit which
determines the shower temperature at
any given setting. (The slower the flow the
hotter the water becomes, and the faster
The flow the cooler the water).
B. During the Winter the Cold water supply
will be cooler than in the Summer months.
therefore, the temperature of the water
4
SECTION
ADVICE TO USERS
16
SECTION
ADJUSTING THE
SPRAYHEAD
17
SECTION
SHOWERHEAD CLEANING
INSTRUCTIONS
The showerhead should be cleaned
periodically to remove limescale or debris
which will reduce the performance of the
shower. The frequency of cleaning will
vary according to local water quality.
In hard water areas cleaning will be
needed more often than in soft water
IN SHOWER MAINTENANCE
To break away scale deposits on
a daily basis simply rub your
thumb over the rubber nipples
whilst the shower is running.
Six sprayhead patterns are available.
Ajustment is by turning the bezel on the
sprayhead in either direction until the
dersired pattern is obtained.
Tranquil
Single outer spray
Fresh
Single Inner spray
Excite
Single Centre spray
Allure
Outer & Inner combined spray.
Sensual
Outer & Centre combined spray.
Ecstasy
Centre & Inner combined spray.
5. Throughly clean and rinse
the inside of the showerhead.
6. Replace the two black ‘O’
rings on the rear of the spray
cartridge. A light smear of
petroleum jelly will ensure an
easy location into the grooves.
7. Refit cartridge to the
showerhead and tighten with
the spray key.
1. Engage the key into the
spray cartridge recesses and
turn anti-clockwise to unscrew.
2. Remove the two small black
‘O’ rings from the rear of the
spray cartridge, and rinse ‘O’
rings clean.
4. Ensure all traces of limescale
and limescale remover are
rinsed off.
3. If deposits are stubborn,
immerse and soak the spray
cartridge for several hours in a
proprietary limescale remover.
Then with a small stiff bristled
brush scrub the spray cartridge.
areas. Aliquid non-abrasive bathroom
cleaner may be used on external surfaces
of the handset.

will vary from season to season on any
one setting of the temperature control, e.g.
if you have chosen 'Medium' power for
your preferred shower temperature in the
Summer, you may have to increase that
to 'Full' power during the Winter Months.
C. If for any reason there is a sudden rise
in water temperature, the Aqua 9000 XP
has thermal cut-out devices built-in.
D. Switch off immediately at the isolating
switch if water ceases to flow. Contact
Galaxy Customer Service for advice. If
ever the water becomes too hot and you
cannot obtain cooler water, first check that
the sprayplate in the sprayhead is not
blocked.
DO NOT place items such as soap or
Shampoo bottles on top of the unit. Liquid
could seep through the joint between the
cover and backplate, and possibly
damage the sealing rubber.
Replacement parts can be ordered from
Galaxy Customer Service..
Due to continuous improvement and
Updating, specification may be altered
Without prior notice.
5
SECTION
ELECTRICAL
REQUIREMENTS
WARNING
THIS APPLIANCE MUST BE
EARTHED
The installation, supply cable and
circuit protection must conform with
IEE wiring regulations and be
sufficient for the amperage required.
2. If you are installing a shower with a
kilowatt rating above 9kW, it is
advisable to contact the local
electricity supply company.
3. The electrical rating of the shower is
shown on the rating label (Fig.1)
within the unit.
4. Before making any sort of electrical
connection within the installation,
ensure that no terminal is live. If in
any doubt, switch off the whole
installation at the consumer unit.
5. The shower must be connected to its
own independent electrical circuit.
IT MUST NOT be connected to a ring
main, spur, socket outlet, lighting
circuit or cooker circuit.
6. The electrical supply must be
adequate for the loading of the unit
and existing circuits.
7. Check your consumer unit (main fuse
box) has a main switch rating of 80A
or above and that it has a spare fuse
way which will take the fuse or mcb
necessary for the shower.
8. If your consumer unit has a rating
below 80A or if there is no spare fuse
way, then the installation will not be
straight forward and may require a
New consumer unit serving the house
or just the shower.
9. You will need to contact the local
electricity company.They will check
the circuit and carry out what is
necessary. They will also check the
main bonding.
10. The earth continuity conductor of the
electrical installation must be
effectively connected electrically to all
exposed metal parts of other
MAX SUPPLY HEAD 10 METRES
MIN SUPPLY HEAD 0.08 METRES
RATING 20 MINS ON/60MINS OFF
RATED PRESSURE 0.Pa
THIS SHOWER UNIT WILL NOT
EXCEED A FLOW RATEOF 20 LPM
GALAXY SHOWERS
COVENTRY UK
REGISTERED DESIGN
Model: AQUA 9000XP
8.5KW 240V IPX4
SERIAL No: A9XP70005
1 2 3 4 5 6 7 8 9 10 11 12
The following notes are for guidance only:
1. The shower must only be connected
to a 230-240V ac supply.
Fig.1
‘High’ setting (Double Solid Red Symbol):
Is maximum power setting which
Allows the highest flow achievable
for your preferred temperature.
Temperature adjustment at this
setting is via the temperature
control.
To adjust the shower temperature
The shower temperature is altered by
increasing or decreasing the flow rate of
the water through the shower via the
temperature control (Fig.19b).
After obtaining your preferred shower
temperature, the number can be
remembered as the normal setting and
should only need to be altered to
compensate for seasonal changes in
ambient water temperatures.
NOTE: To decrease the shower
temperature.
Turn the temperature control anti-
clockwise towards the
To increase the shower
temperature.
Turn the temperature control
clockwise towards the higher
numbers; this will decrease the
water flow.
CAUTION: Be certain the showering
temperature is satisfactory by testing
with your hand before stepping under
the sprayhead. There will always be a
time delay of ten to fifteen seconds
between selecting a flow rate and the
water reaching the stable temperature
for that flow rate.
It is recommended that persons who
may have difficulty understanding or
operating the shower controls should
not be left unattended whilst
showering. Special consideration
should be given to young children and
the less able bodied.
Power on indicator (Fig.20)
The Blue power neon will light when the
start/stop button is pressed. This indicates
that power is on to the pump and power
Selector.
15
SECTION
OPERATING FUNCTIONS
Low water pressure cut-out
Should the water pressure fall below the
minimum required to operate the shower,
power will be switched off to the heating
elements preventing any maintained
temperature rises.
Overheat cut-out
During normal operation if an overheat
temperature is sensed, power to the
elements will be reduced. Water will
continue to flow. When the temperature
has cooled sufficiently, power to
the elements will be automatically
restored to the previous setting at the time
of interruption.
Safety cut-out
The unit is fitted with a non re-settable
over-temperature safety device. In the
event of abnormal operation which could
cause unsafe temperatures within the unit,
the device will disconnect the heating
elements. It will require a visit from a
qualified engineer to determine the
nature of the fault and replace the safety
Fig.20
Blue Power
Neon

Twin and Earth PVC Insulated Cable
CURRENT CARRYING CAPACITY
Installed in an
Insulated
Wall
In Conduit or
Trucking Clipped
Direct or
Buried in a
non Insulated
Wall
6mm2 6mm2 6mm2
32A 38A 46A
10mm2 10mm2 10mm2
43A 52A 63A
16mm2 16mm2 16mm2
57A 69A 85A
Note: Cable selection is dependent on de-rating factors
CIRCUIT PROTECTION
Unit
Rating
MCB Cartridge
Fuse
7.0kW 30/32A 30A
7.5kW 32A 35A
8.0kW 40A 35A
8.5kW 40A 45A
9.0kW 40A 45A
9.5kW 40/45A 45A
10.5kW 45A 45A
appliances and services in the room in
which the shower is to be installed, to
conform to current IEE regulations.
11. All exposed metallic parts in the
bathroom must be bonded together
using a cable of at least 4mm2 cross
sectional area. These parts include
metal baths, radiators, water pipes,
taps and waste fittings.
12. For close circuit protection DO NOT
use a rewireable fuse. Instead use a
suitably rated miniature circuit breaker
(MCB) or cartridge fuse (See table A).
13. In the interest of electrical safety a
30mA residual current device (RCD)
should be installed in all UK electric
and pumped shower circuits.This may
be part of the consumer unit or a
separate unit.
14. A 45 amp double pole isolating switch
with a minimum contact gap of 3mm
in both poles must be incorporated in
the circuit.
15. It must have a mechanical indicator
showing when the switch is in the OFF
position, and the wiring must be
connected to the switch without the
use of a plug or socket outlet.
16. The switch must be accessible and
clearly identifiable, but out of reach of
a person using a fixed bath or shower,
except for the cord of a cord operated
switch, and should be placed so that it
is not possible to touch the switch
body while standing in a bath or
shower cubicle. It should be readily
accessible to switch off after using the
shower.
17. Where shower cubicles are located in
any rooms other than bathrooms, all
socket outlets in those rooms must be
Protected by a 30mA RCD.
18. The current carrying capacity of the
cable must be at least that of the
shower circuit protection (See table
B).
.19. To obtain full advantage of the power
provided by the shower, use the
shortest cable route possible from the
consumer unit to the shower.
20. It is also necessary to satisfy the
disconnection time and thermal
constraints which mean that for any
given combination of current demand,
voltage drop and cable size, there is a
maximum permissible circuit length.
21. The shower circuit should be
separated from other circuits by at
least twice the diameter of the cable
or conduit.
22. The current rating will be reduced if
the cabling is bunched with others,
surrounded by thermal loft or wall
insulation or placed in areas where the
ambient temperature is above 30°C.
Under these conditions, de-rating
factors apply and it is necessary to
Tabel ‘A’
Tabel ‘B’
1. To start the shower
Pressing the start/stop button (Fig.19)
switches on the pump allowing water to
immediately flow through the unit.
2. To stop the shower
Press the start/stop button. This initiate
the Phased (Safety) Shutdown feature.
The Phased (Safety) Shutdown feature
lasts for approx 8 seconds, during which,
the indicator light will flash ON & OFF, the
flow of water will be reduced and the
power to the heating elements cut. This
allows the unit to safely flush out any
residual heat. After which the pump
switches off and the water flow will cease
.
WARNING: If re-starting immediately
after stopping, be aware that a slug of
HOT water will be expelled for the first
few seconds.
3. To use the power selector
The power selector (Fig.19a) has four
settings – Cold, Low, Medium and Full
power.
‘Cold’ setting (Solid Blue Symbol):
Is Cold water only.Adjustment at
the temperature control at this
setting will only increase or
decrease the force of the water
from the sprayhead. It will not alter
The water temperature.
‘Low’ setting (Outline Red Symbol):
Is the low setting for extra economy
during hot months. Temperature
adjustment at this setting is via the
temperature control.
‘Medium’ setting (Solid Red Symbol):
Is the medium setting for economy
during warmer months and any
temperature adjustment at this
setting is via the temperature
Control.:
Fig.19
Start/Stop
Button
Power
Selector
Temperature
Control
Fig.19b
COOLER WARMER
COLD
HIGH
MEDIUM
Fig.19a
LOW

The installation must be in accordance
with Water Regulations / Byelaws.
WARNING: Under no circumstances
must this Aqua 9000 XP pumped
shower be connected directly to the
mains water supply.
To ensure activation of the heating
elements, the shower must be connected
to a Cold water supply which is gravity fed
from a static Cold water storage cistern
with a minimum capacity of 114 litres
(25 galls).
There must be a maximum head of water
of 10 metres (33ft) and a minimum head
of 8 cm (3") as measured between the
Bottom of the cistern and the top of the
shower unit. There must be no other Cold
water draw offs between the cistern and
the unit and the pipe must not supply
water to any other tap or fitting at a lower
level.
NOTE: The supply pipe from the cistern
should be on the opposite side to the float
operated valve to prevent air being drawn
into the pipe when the cistern is filling.
If it is intended to operate the shower in
hard water areas (above 200 ppm
select a larger cable size.
23. In the majority of installations, the
cable will unavoidably be placed in
one or more of the above
conditions. This being so, it is
strongly recommended to use a
minimum of 10mm cabling
throughout the shower installation.
24. In any event, it is essential that
Individual site conditions are assessed
by a competent electrician in order to
Determine
6
SECTION
WATER REQUIREMENTS
temporary hardness) a scale inhibitor
should be fitted.
Fig.2 shows a typical system layout. Do
not use jointing compounds on any pipe
fittings for the installation.
WARNING: The shower must not be
positioned where it will be subjected to
freezing conditions.
FOR EASE OF SERVICING, THE UNIT
MUST ALWAYS BE MOUNTED ON THE
SURFACE OF TILED WALLS. NEVER
TILE UP TO THE UNIT.
Refer to Fig.3 for correct siting of the
shower. This product is splash-proof rated
and is approved for use in shower
cubicles and over baths.
However, do not install the unit in a
Position where the sprayhead will
consistently direct water over it.
The shower unit MUST be positioned
vertically.
7
SECTION
SITING OF THE SHOWER
Fig.2
CAUTION
Check there are no hidden cables or
pipes before drilling holes for wall plugs.
Exercise great care when using power
tools near water. The use of a residual
current device (RCD) is recommended.
4. The crimped end of the riser
rail. NOTE If it is necessary to
shorten the rail, use a junior
hacksaw to cut the excess material
from the plain end of the rail.
1. Establish position for the
riser rail, and mark the wall for
the lower mounting bracket.
Make allowances for the tallest
person likely to use the shower
regularly.
2. Use a No 10/5.5mm masonry
drill to make a hole 35mm deep,
and fit the wall plug. (NB some
wall constructions may require the
use of alternative types of wall
fixings).Screw the lower bracket
base to the wall.
3. Locate the crimped end of
the riser rail (Figure 4) into the
mounting bracket, then fit the
upper bracket. Ensure the rail is
vertical, then mark the wall for
the fixing.
5. The three components that
comprise the Handset Height
Adjuster assembly are
produced with alphabetical ‘A’s
and ‘B’s moulded into the end
section of each part. Simply just
match the letter identification of each part with
the central piece i.e. ‘A’ to ‘A’ and ‘B’ to ‘B’ for
correct assembly.
6. With the showerhead height
adjuster lever set a 3 o’clock
and the showerhead holder in
the upright position, slide the
assembly onto the rail. Tighten
to the rail by turning the lever.
14
SECTION
OPERATING THE SHOWER
8. Re-assemble the rail and
screw the upper mounting
bracket in place.
7. To lock the Handset Height
Adjuster at your chosen position
on the rail. Turn the lever up
right. This action is also used for
holding the showerhead at the
angle required.
Maintenance:
Clean regularly with a non-abrasive liquid
bathroom cleaner.
9. Slide the end cap onto the
mounting brackets.
10. Snap the soap dish onto the
rail below the holder assembly.
11. Slide soap dish down the
rail to required position.
12. Firmly attach flexible hose to
the showerhead making sure
sealing washer is in place.
NOTE the adjustable slider grips the
conical end of the hose, not the
handle of the showerhead.
IMPORTANT: Ensure the commissioning
procedure has been carried out.

operates, then water will eject from the
bottom of the unit.
Should this happen, turn off the
electricity and water supplies to the
shower at the isolating switch and
stopvalve. Contact Customer Service
for advice on replacing the PRD.
The PRD is situated adjacent to the
outlet pipe (Fig.4).
To gain access to it, FIRST SWITCH
OFF THE ELECTRICITY SUPPLY,
remove the cover, then unscrew using
suitable wrench or grips.
CAUTION: Do not attempt to replace
the PRD unless competent to do so.
NOTE: Before replacing the cover, it is
strongly advised to prime the unit (see
‘commissioning’).
Allow sufficient room between the ceiling
and the shower to access the cover top
screws.
8
SECTION
PRESSURE RELIEF SAFETY
DEVICE
A pressure relief device (PRD) is
designed into the shower unit which
complies with European standards.
The PRD provides a level of appliance
protection should an excessive build up
of pressure occur within the shower.
DO NOT operate the shower with a
damaged or kinked shower hose, or a
blocked sprayhead which can cause the
PRD to operate.
When commissioning, the sprayhead
must be removed from the flexible hose.
Failure to follow this procedure may also
result in causing the PRD to operate.
Ensure the shower is positioned over a
bath or shower tray because if the PRD
PRD
9
SECTION
FITTING THE SHOWER TO
THE WALL
NOTE: The control knobs are an integral
part of the cover – do not attempt to
remove them.
IMPORTANT: The unit must be mounted
on a flat surface which covers the full
width and length of the backplate. It is
important that the wall surface is flat
otherwise difficulty may be encountered
when fitting the cover and subsequent
operation of the unit may be impaired.
Fig.3
Fig.4
‘COLD' position and the temperature
control is at ‘TEMPERATURE’.
Replace the cover squarely to the
backplate and guide into position so that
the controls locate correctly into the
spindles while at the same time, ensuring
wires are not trapped. Should any
difficulty arise, re-check the points above
Secure the cover in position with the
four retaining screws. DO NOT
OVERTIGHTEN..
Fig.12Fig.18
Fig.17
Fig.16
Switch on the mains electric supply to the
shower at the isolating switch.
Press the ‘START/STOP’ button (Fig.17).
The power indicator will light and the
pump starts to operate.
It will take approximately thirty seconds
for a smooth flow of water to be obtained
whilst air and any debris is being
dispersed from the shower. When a
smooth flow of water is obtained, rotate
the temperature control from ‘1’ to ‘10’
several times (Fig.18) to release any
trapped air within the unit.
Once flushing out has been completed,
stop the water flow by pressing the
‘start/stop’ button.
Because the shower is fitted with Phased
(Safety) Shutdown, the indicator light will
begin flash and water flow will be reduced
for approx 8 seconds before the shower
switches off. During this Phased (Safety)
Shutdown, power to the heating elements
is cut. This allows the unit to safely
disipate any residual heat.
Commissioning is complete. Once the
riser rail is fitted, the shower is ready for
13
SECTION
RISER RAIL & SOAP DISH
FITTING INSTRUCTIONS
TIPS
A piece of insulating or masking tape
applied to the wall before marking out the
fixing holes will help stop the drill from
wandering, particularly on tiled surfaces.
When working near a basin or bath, insert
the plug in the waste fitting so that small
parts cannot be lost. Take care not to drop
accessories or tools into basin or bath.

Unscrew the two top and bottom retaining
screws (Fig.5) and lift the cover from the
backplate. NOTE: Deviations from the
designated entry points will invalidate
product approvals.
required for the Cold water pipe, then a
aperture will need to be cut out of the
cover (Fig.7) and the inlet elbow rotated
to face downward.
If entry is required from the back, rotate
the inlet elbow upwards and fit elbow to
connect to the pipe (Fig.8). Ensure the
hole in which the pipe enters through the
wall is filled in completely in order to
Fig.5
Fig.6
If a top entry is required for the water pipe,
remove the blanking plug in the backplate
(Fig.6) and ensure the inlet elbow so that
It points upward. If a bottom entry is
Fig.7
Bottom Entry
Aperture
‘Cut-Out’
WALL
87 mm
28.5 mm
19 mm
Fig.8
prevent any possible ingress of water into
the cavity area. After choosing the site for
the shower, use the supplied template and
mark the three fixing holes (Fig.9). Drill
and plug to suit the fixing screws supplied.
(The wallplugs provided are suitable for
most brick walls – use an appropriate
masonry drill, but if the wall is
plasterboard or a soft building block, you
must use special wallplugs and an
appropriate drill obtainable from most
hardware stores).
Fig.15
Spindle in
COLD
position
Flat
Fig.12Fig.14
Element(s) to burn out and invalidate
the guarantee.
The first operation of the shower is
intended to flush out any remaining unit
debris, and to ensure the heater unit
contains water before the elements are
switched on.
This operation must be carried out with
the flexible hose (supplied) screwed to the
outlet but without the sprayhead attached.
Ensure the outlet of the flexible hose is
directed to waste and ensure the end of
the hose is below the shower unit.
To ensure the temperature control is
correctly positioned on the stabilising
valve, temporarily place the cover in
position so that the splines engage then
rotate the temperature control knob fully
Anti-clockwise.
Remove the cover and position the
temperature control so that it points
towards ‘TEMPERATURE’(Fig.13).
Position the power selector to the 'COLD'
position (Fig.12).
Ensure power selector is in Cold position
(Fig.14) before continuing.
Ensure the water supply is still turned on
to the shower.
Open the bleed screw adjacent the rubber
hose (Fig.15) by rotating anti-clockwise
slowly until water flows from the drain pipe,
this indicates that any trapped air is
vented and that the pump unit is primed.
The bleed valve must now be closed by
rotating clockwise. DO NOT
OVERTIGTHEN.
Attach to the stop/start switch inside the
cover is a power lead. The socket on the
end of this lead must be connected to the
plug that is situated near the top of the
backplate unit (Fig.16). NOTE: The plug
and socket can only fit one way.
Offer the cover to the backplate unit.
Ensure the power selector is still at the
Bleed Screw
(’XP’ Model)
Fig.13
Fig.12

Screw the two upper fixing screws into
position leaving the base of the screw
heads protruding 6mm (0.25in) out from
the wall. Hook the backplate over the top
screws and fit the lower fixing screw into
position. DO NOT fully tighten the screws
at this stage, as the fixing holes are
elongated to allow for out of square
adjustment after the plumbing connections
have been completed.
10
SECTION
PLUMBING CONNECTIONS
PLUMBING TO PRECEDE WIRING
WARNING: The outlet of the shower acts
as a vent and must not be connected to
anything other than the hose and
sprayhead supplied.
GALAXY ‘AQUA 9000 XP’
FIXING TEMPLATE
VERTICAL CENTRE LINE
HORIZONTAL CENTRE LINE
Fig.9 DO NOT use jointing compounds on
any pipe fittings for the installation.
DO NOT use soldered fittings within
the vicinity of the shower unit.
NOTE: An additional gate valve or fullway
lever valve must be fitted in the water
supply to the shower as an independent
means of isolating the water supply should
maintenance or servicing be necessary.
IMPORTANT: The fitting on the inlet elbow
is a push-in type. The pipework must be
cut with a pipe cutter and all burrs and
rough edges removed from the end of the
tube. The fitting can be used with copper
and plastic pipe. If using chrome plated
copper pipe, remove the first 25mm of
plating completely from the connecting
surface. If it is not completely removed
then the collet will not grip the pipe and
under pressure the pipe may be forced
out.
CONNECTION PROCEDURE: Turn off
water supply either at the mains stopvalve
or the isolating stopvalve to the cistern.
Drain the cistern.
IMPORTANT: The pipework must be
brought direct from the Cold water storage
cistern with no other Cold water draw offs
between the shower and the cistern.
IMPORTANT: Before completing the
connection of the water supply to the
inlet of the shower, flush out the
pipework to remove all swarf and
system debris. This can be achieved by
connecting a hose to the pipework and
turning on the water supply long
enough to clear the debris to waste.
Fit the pipework to the inlet elbow. Ensure
the elbow collet is fully engaged with the
pipe. Although the pipework connection to
the shower is via 15mm diameter
pipework, on long runs use 22mm
diameter piping as far as possible to avoid
restricting the flow to the shower.
Ensure that the backplate of the unit is flat
on the wall and positioned squarely.
Tighten the fixing screws.
Turn on the water supply and check for
leaks in the pipework connection to the
shower. NOTE: At this stage no water can
flow through the unit.
11
SECTION
ELECTRICAL
CONNECTIONS
SWITCH OFF THE ELECTRICITY
SUPPLY
The cable entry points are shown in
(Fig. 10).
The cable can be surface clipped, hidden
Or via 20mm conduit. NOTE: Metal
conduit entry can only be from rear.
Route the cable into the shower unit and
connect to the terminal block (Fig. 11) As
Follows:-
Earth cable to terminal marked ......
Neutral cable to terminal marked ...N
Live cable to terminal marked.........L
E
IMPORTANT: Fully tighten the terminal
block screws and ensure that no cable
insulation is trapped under the screws.
Loose connections can result in cable
Overheating..
Fig.11
NOTE: The supply cable earth conductor
must be sleeved. The outer sheath of the
supply cable must be stripped back to the
minimum. The supply cable must be
secured either by routing through conduit
or in trunking or by embedding in the wall,
in accordance with current IEE regulations.
The use of connections within the unit, or
other points in the shower circuit, to
supply power to other equipment i.e.
extractor fans, pumps etc. will invalidate
the guarantee.
DO NOT switch on the electricity
supply until the cover has been fitted.
Fig.10
12
SECTION
COMMISSIONING
DO NOT switch on the electricity
supply until the following procedure
has been completed and the cover has
been fitted. Failure to do so could
Cause the pump to run dry and
invalidate the guarantee.
Cold position must be selected on
power selector (Fig.14) Before carrying
out any of the steps below. Failure to
do so WILL cause the heating
Table of contents
Other Galaxy Plumbing Product manuals
Popular Plumbing Product manuals by other brands

BELLOSTA
BELLOSTA aperio 2705/S Installation instruction

Peerless Faucet
Peerless Faucet P183510LF quick start guide

azalp
azalp FIR-2C8 installation instructions

American Standard
American Standard Repertoire 0240.001 Specifications

Bradley
Bradley S45-1964 Installation

Sustainable Solutions
Sustainable Solutions Fluid F2002B installation instructions