
2.
3.
4.
5.
6.
Ifan air-cooled atlercooler isto be used, provisions
to bypass the aftercooler must be made. Since coid
air contains very little moisture, successful opera-
tion can be achieved without the ailercoder.
Provide at least some simple shelter such as a
plywood windbreak to protect against drifting
snow.
Use only Gardner-Denver@ AEONm 9000 lubri-
cant.
Monitor unit carefully during start-up and operation
to be sure it is functioning normally.
Specify NEMA 4enclosure for electrical devices.
Extreme Cold Weather Operation (Down To -40”F)
In addition to the above, the following should be pro-
vided:
1. it will be necessary to provide shutters or to block
off part of the cooler in some manner since the
cooier is greatly oversized for operation in these
low temperatures. Since shutters are not provided
as a factory option, blocking off aportion of the
cooler with plywood should be satisfactory.
2. Auto operation should not be used in extreme
environments.
3. Some means of providing heat during shutdown
should be provided. There are various methods to
accomplish this, but since openings are not pro-
vided for sump heaters, the use of radiant heaters
is recommended. The heaters should be sized to
provide at ieast a+10°F environment for coolers,
motor and sump. Figure 3-2 shows how these
might be located in atypical installation and sizes
required.
Remember unsheltered (outside) installations should be
avoided where possible. Instaiiation next to aheated
building where enough heat can be used to keep the
compressor room above freezing will save many com-
plications in the operation and installation of the unit.
Referto Engineering Data Sheet 13-9411, available from
an authorized Gardner-Denver distributor, for the advan-
tages of using the heat recovered from rotary compres-
sors. This heat recovery could easiiy pay for an
adequate shelter for the unit.
AUXILIARY AIR RECEIVER -An auxiiiary air receiver is
not required if the piping system is large and provides
sufficient storage capacity to prevent rapid cycling.
When used, an air receiver should be of adequate size,
provided with arelief valve of proper setting, apressure
gauge and ameans of draining condensate.
MOISTURE SEPARATOR/TRAP -Since unit is
equipped with abuiit-in aftercooler, acombination mois-
ture separator and trap is furnished with the unit.
CONTROL PIPING -Control piping is not necessary
since the Electra-Screw@ unit isfactory wired and piped
for the control system specified.
INLET LINE -Where an inlet line isused between the air
fiiter and the compressor, it must be thoroughly cleaned
on the inside to prevent dirt or scaie from entering the
compressor. If welded construction is used, the line
must be shot blasted and cleaned to remove welding
scale. In either case, the iniet line must be coated
internally by galvanizing or painting with amoisture and
oii-proof sealing lacquer. Up to ten (1O) feet in length,
the inlet line shouid be the fuil size of the inlet opening
on the compressor. If an extra-long line is necessary,
the pipe size shouid be increased according to Inlet Line
Chart below.
Accessibility for inlet air filter servicing must be consid-
ered when relocating the filters from the unit to aremote
location.
DISCHARGE SERVICE LINE -The discharge service
line connection is made at the upper right hand corner
of the cooler, viewed from the oil cooler side, Ahand
operated valve, (air service valve) must be instalied
between the unit and the customer’s air ystem. When
8
manifolding two or more Electra-Screw units on the
same line, each unit is isolated by the check vIve inthe
unit discharge line. If an Electra-Screw 8unit is
manifolded to another compressor, be sure the other
compressor has acheck valve in the line betw en the
8
machine and the rnanifoid. If an Electra-Screw and a
reciprocating compressor are manifolded together, an
air receiver must be located between the two units.
IDANGER
IDischarge air used for breathing will
cause severe injury or death.
Consult filtration specialists for addi-
tional filtration and treatment equip-
ment to meet health and safety
standards.
BLOWDOWN VALVE PIPING -The biowdown valve is
fried with amuffler for operation indoors. Ifthe installa-
tion requires, the muffler may be removed and the blow-
INLET LINE LENGTHS
Length of Inlet Line Diameter of Pipe Size
Oto 10 Feet ........................................................................................................... Same as Compressor Inlet Opening
lo to 17 Feet ...........................................................................................................One Size Larger Than Inlet Opening
17 to 38 Feet .........................................................................................................Two Sizes Larger Than Inlet Opening
13-3-809 Section 2Page 3