GE Multilin 515 User manual

515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL 1
GE
Grid Solutions
Overview
515 Features The GE Multilin 515 Blocking and Test Module has the following features:
• 14 Pole switchbank
• CT inputs short when current switches are opened
• Current injection for each phase
• Ground terminal
• Ability to visually isolate (open) trip relay output circuits
• Cover provided
• Suitable for utility and industrial use
• 515 test plugs available.
Description The 515 Blocking and Test Module provides an effective means of trip blocking, relay
isolation and testing of GE Multilin relays. By opening the switches and inserting test plugs,
phase and residual currents from the primary CTs can be monitored. Currents can be
injected into the relay from a secondary injection test set during commissioning.
Prior to testing, the trip and auxiliary circuits must first be opened to prevent nuisance
tripping; CTs can then be shorted. Conversely, when the test is complete and the relay put
back into operation, the CT switches should be closed first to ensure normal operation of
the relay, prior to closing the trip and auxiliary circuits.
Further Assistance For product support, contact the information and call center as follows:
GE Grid Solutions Worldwide telephone: +1 905 927 7070
650 Markland Street Europe/Middle East/Africa telephone: +34 94 485 88 54
Markham, Ontario North America toll-free: 1 800 547 8629
Canada L6C 0M1 Fax: +1 905 927 5098
Website: http://www.gegridsolutions.com/multilin
515 Blocking and Test System
Instruction Manual
GE Publication Number: 1601-0024-A6
Copyright © 2017 GE Multilin Inc.

2 515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL
Installation
Operation Shorting switches are provided for connection of 3 phase CTs (current transformers) and a
separate core balance ground fault CT or 3 phase CTs connected for residual ground fault
sensing.
When each CT switch is opened, the CT is shorted. It is essential that the CT is connected to
the shorted side of the switch as shown in the following figure, otherwise dangerously high
voltages would be present from the open circuited CTs.
When the switches are open, test plugs can be inserted to either inject signals into the
relay wired to the switches, or monitor signals such as CT current from the switchgear.
Typical Wiring The typical wiring for connecting a 515 to a protective relay is shown below.
FIGURE 1–1: Typical Wiring

515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL 3
The typical wiring for a zero-sequence ground fault is shown below:
FIGURE 1–2: Typical Wiring for Zero-Sequence Ground Fault

4 515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL
Physical Dimensions The 515 Blocking and Test Module consists of a metal chassis attached to the 515 test
switches that slides into the panel. A single cutout in the panel, as per the dimensions
shown below, is required to mount the 515 test switches.
GE Multilin
FIGURE 1–3: Panel Cutout Dimensions and Mounting
Mounting Slide the metal chassis attached to the 515 test switches into the cutout from the front of
the panel. While firmly applying pressure from the front of the 515 module to ensure the
chassis fits snugly, bend out the retaining tabs as shown in FIGURE 1–3: Panel Cutout
Dimensions and Mounting. Usually the retaining tabs will be sufficient to hold the 515
module securely in place. If additional fastening is desired bend out the clamping screw
tabs at both ends of the chassis at right angles. Insert the #8 screws provided in the
accessory pouch into the tapped holes with the vibration proof nut between the tab and
the panel. Tighten each screw until the end of the screw butts firmly against the front
panel. Ensure the nut is installed tightly against the bent tab. Nylon inserts in these nuts
prevent them from vibrating loose. The 515 test switch module should now be securely
mounted to the panel with no movement ready for rear terminal wiring. When completed,
place the front cover over the mounted 515 test module and turn the fasteners at both
ends ¼ turn to lock it in place, as shown in FIGURE 1–3: Panel Cutout Dimensions and
Mounting.
As a safety precaution, a ground screw located on the bottom-right of the rear side of the
module is available to be connected to panel chassis ground.

515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL 5
Detailed Operation To put the 515 Blocking & Test Module into operation, additional parts have been provided:
• 1 package containing at least 28 terminal nuts
• 14 white tags for identification of each of the switches
The 515 provides a means of trip blocking, relay isolation, and testing of GE Multilin relays.
The 515 accomplishes this with a total of 14 switches. There are 6 single pole throw
switches for use with the output relays, and 4 groups of 2 switches each for use with the
current transformers as illustrated in FIGURE 1–1: Typical Wiring.
Isolation or opening of the relay’s output circuits is accomplished with the six switches at
terminals 1 through 6 and 15 through 20. These switches can be used to simply open the
protection relay's output contacts and thus provide a means of blocking trips. The 4
remaining groups of 2 switches at terminals 7 through 14 and 21 through 28 are used for
shorting of the CT inputs, injection of test current, and measuring of CT current. The four
groups correspond to Phase 1 Current, Phase 2 Current, Phase 3 Current, and Ground
Current.
Each group is made up of two switches. The first switch for the Phase 1 group is at terminal
7 and 21 and is configured as shown below.
Note that terminals 7 and 21 are shorted together regardless of whether the switch is
open or closed. The second switch for the Phase 1 group is at terminals 8 and 22. It is
configured as shown below.

6 515 BLOCKING AND TEST SYSTEM – INSTRUCTION MANUAL
Note that this switch operates as make before break. When this switch is closed terminals
8 and 22 are shorted together. When this switch is open, terminals 8 and 22 open and 22
shorts with 7 and 21. This in turn shorts the Phase 1 CT. It is essential that the CT is
connected to the shorted side of the switch as shown below. Otherwise, dangerously high
voltages would be present at the open circuited current transformer. Also note that
currents can be injected into the protection relay from a secondary injection test set.
With the switch between terminals 7 and 21 open and the switch between terminals 8 and
22 closed as shown below, a 515 test plug can be inserted between terminals 7 and 21 to
monitor the CT current. See the following diagram for details. Note that the 515 test plug is
made up of two conductors separated by an insulator.
A detail of the test plug is shown below.
Table of contents
Popular Test Equipment manuals by other brands

Mako
Mako MK5 Operator's manual

Alcohol Countermeasure Systems
Alcohol Countermeasure Systems Alcolock LR Installation and service manual

Triplett
Triplett Fox Jr. instruction manual

Ametek
Ametek Crystal Pressure Operation manual

TSI Instruments
TSI Instruments 8120 quick start guide

Megger
Megger 210170 user guide