RTD Input Module
GFK-1206D
Analog Input Module
4
June 1997
Module ConfigurationOverview
Like other Field Control modules, the RTD Input module is usually configured from the Bus
Interface Unit, using a compatible hand-held programmer. The module will also accept
configuration data from the bus when used in a system that supports such configuration.
The table below summarizes configuration choices and defaults. The module will power up
with the default configuration settings. For configuration instructions, refer to the Bus
Interface Unit User’s Manual.
Module
Parameter Description Default Choices
AnalogInput
DataLength Word length of the module’s analog input
data in the BIU’s analog input (AI) data table. 40–4
AnalogInput
DataReference Startingoffsetforthemodule’sanaloginput
dataintheBIU’s analog input(AI)table. userselectable
DiscreteInput
DataLength Bitlengthforthemodule’soptional status
datainthe BIU’s discrete input(I)table. 32 0–32
DiscreteInput
DataReference Startingoffsetforthemodule’sstatusdata
intheBIU’s discrete input (I)table. userselectable
Discrete
OutputData
Length
Bitlengthforthemodule’soptional
fault-clearingbitsintheBIU’sdiscrete
output(Q)table.
8 0–8
DisceteOutput
DataReference Startingoffsetforthemodule’soptional
fault-clearingbitsintheBIU’sdiscete
outputtable.
userselectable
AnalogOutput
DataLength Word lengthfor analog output data in the
BIU’sanalogoutput(AQ) table. Should not
beusedformostapplications.
0 0–4
AnalogOutput
DataReference Startingoffsetforthemodule’sanalog
outputdata inthe BIU’sAQ table. userselectable
LineFrequency Specifiesthelinefrequency. 60Hz 50 Hz,60 Hz
ChannelActive Specifiesif the channelshouldreturndata
andalarms.Ifachannelis“inactive”space
isstillallocatedforit.
Active Inactive(off),Active(on)
Units Theconversion type for each RTD. Deg C tenths of ohms, tenths of degrees C, or
tenths of degrees F
RTD Type The type of RTD used for each channel. 100PT
385 10PT, 25 PT, 25.5 PT 392, 100PT 385, 100 PT
3902,100PT392,100PT3923,100PT3916,
1KPT 375,10 CU, 10 CU 427, 50 CU 427, 100
CU427, 100 NI, 100NI 618, 120 NI672 604
NI/FE518,1KNI/FE527,500Ohm,3000
Ohm
WireType The type of field wiring for each RTD. 3 Wire 3 Wire, 4 Wire
AlarmLow The low alarm limit for the channel, in
engineeringunits. –200 –32,768 to +32,767
AlarmHigh The highalarm limit for the channel, in
engineeringunits. 800 –32,768 to +32,767
Resistance Anoptionalresistanceadjustment,intenths
ofohms. 00to3276.7