GE Multilin 350 Manual

GE Consumer Industrial
Electrical Distribution
Project Name: Sludge Dewatering and Odor Control at Plant 1
Project No. P1-101
Specification: Revision: 0
02/01/2016
16340
Medium Voltage Switchgear
Volume 1 of 3
Equipment Tag(s): Shop Order
SWITCHGEAR SWGR-Q-A ( 15LSWGR901 ) 111027-01
SWITCHGEAR SWGR-Q-B ( 15LSWGR902 ) 111027-04
Manufacturer: General Electric / Powell BPD
Address: 12305 Kurland Drive
City, State, Zip Houston, TX 77034
Website: www.geindustrial.com
GE Base Requisition #: 480-Z7612
Local Service Representative: GE Energ- Engineering Services
Address: 3601 East LaPalma Ave.
City, State, Zip Anaheim, CA 92806-2119
Phone: 888-GE4-SERV or 540-387-8617
Website: www.geindustrial.com
Operation & Maintenance Manuals
gimagination at work

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Designation Loop Tag Shop Order
SWITCHGEAR SWGR-Q-A 15LSWGR901 111027-01
SWITCHGEAR SWGR-Q-B 15LSWGR902 111027-04
12.47KV SERVICE CENTER ADDITIONS ** 111027-01
Equipment List
Medium Voltage Switchgear
Page 1 of 1

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Tab 1
Device Data Sheets
Key Components

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Drawing
Manufacturer Catalog Number Reference Mark Loop Tag
GE/Multilin 350-E-P5-G5-H-E-S-N-N-1E-D-N 350 15LITG901
15LITG903
15LITG907
15LITG911
15LITG902
15LITG904
15LITG908
15LITG912
Feeder Protection Relay
Type 350
Data Sheet

270
Distribution Feeder Protection
gDigital Energy
Protection and Control
•Phase, neutral and ground TOC and IOC
•Undervoltage, overvoltage, frequency
•Neutral/ground directional
•Negative sequence Overcurrent
•ANSI, IAC, IEC, flex curves
•Cable Thermal Model Protection
•Breaker Failure
•Cold Load Pick Up
•Four-shot auto-reclose
•8 digital inputs, 7 contact outputs
•Two setting groups
Metering & Monitoring
•Event Recorder: 256 events
•Oscillography with 32 samples per cycle
•IRIG-B clock synchronization
•Relay health diagnostics
•Security audit trail
•Metering - current, voltage, power, frequency
User Interface
• 4 line display for easy viewing of key data
• 10 LED indicators for quick diagnostics
• Front USB and rear RS485 serial communications
• Multiple Communication Protocols:
IEC 61850
IEC 61850 GOOSE,
MODBUS TCP/IP, MODBUS RTU,
DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
EnerVistaTM Software
•EnerVista Software- an industry-leading suite of software
tools that simplifies every aspect of working with Multilin
devices.
•Quick & easy configuration requiring minimal settings for
most feeder applications.
350
FEEDER PROTECTION SYSTEM
Intuitive and Innovative Feeder Protection
Multilin™
• Easy to use and intuitive overcurrent protection and control
for feeder applications.
• Effortless draw-out construction eliminates requirement for
test switches and reduces downtime
• Environmental monitoring system to alarm on destructive
operating conditions and plan preventative maintenance
• Easy to use interface and set up in one simple step
• Accelerated Life Cycle Tested to ensure reliability of relay
operation under abnormal conditions
• Advanced power system diagnostics to increase reliability
through fault and disturbance recording capabilities
• Flexible communications with multiple ports & protocols
to allow seamless integration into new and existing
infrastructure
• Arc flash mitigation via zone inter-tripping, flex curves, and
multiple settings group
• Powerful Security Audit Trail tool to increase security and
minimize system risks by tracking setting changes
• Application flexibility with the use of programmable logic
elements
•Industrial feeders with enhanced breaker monitoring
diagnostics, etc.
•Distribution utility down stream breaker protection
•Medium voltage Utility feeders with advanced control features
Cold Load Pickup, auto reclose, multiple settings group, etc
FEATURES
APPLICATIONS
KEY BENEFITS

350
Feeder Protection System
271
Distribution Feeder Protection
Overview
The 350 relay is a member of the 3 Series
family of Multilin relays. This protective
device is used to perform primary circuit
protection on medium voltage feeders and
down stream protection for distribution
utilities.
The basic protection function of this relay
includes multiple phase, ground, and
neutral time and instantaneous overcurrent
elements for coordination with upstream
and downstream devices. Additionally, the
device provides essential feeder breaker
control features such as cold load pick up
blocking, breaker failure, and auto reclose.
The robust 350 streamlines user work
flow processes and simplifies engineering
tasks such as configuration, wiring, testing,
commissioning, and maintenance. This
cost-effective relay also offers enhanced
features such as diagnostics, preventative
maintenance, arc flash mitigation and
security.
Easy to Use and Configure
Easy to Use
Drawout Construction
The 350 offers a complete drawout
feature eliminating the need for rewiring
after testing has been concluded. The
withdrawable feature also eliminates the
need to open the switch gear door and
disconnect communication cables, eg.
Ethernet fiber, copper, RJ45, etc prior to
removing the relay from the chasis
Effortless Retrofit
The small and compact 350 enables
multiple relays to be mounted side by
side on medium voltage panels. It also
allows easy retrofit into existing S1 and S2
cutouts with adapter plates.
Easy to Configure
Fast & Simple Configuration
The 350 requires minimal settings for
configuring standard feeder protection
applications. The entire feeder protection
setup can be completed in one easy step.
Advanced
Communications
Easy integration into new or
existing infrastructure
With several Ethernet and serial port
options, and a variety of protocols, the
350 provides advanced and flexible
communication selections for new and
existing energy management, SCADA, and
DCS systems.
Easy to Configure- 1 simple step Advanced & Flexible
Communication Options
Easy to Use- Draw out case Diagnostic Alarms

272
350
Feeder Protection System
Distribution Feeder Protection
350 RELAY
TRIP
BUS
LOAD
3
1
52
CLOSE
50G/
51G
50P 50N
79
50G 51G
22
21
METERING
TRANSIENT RECORDER
EVENT RECORDER
51N51P 50_2
111
49
1
1
27P 59P 27X 59X 59_2 59N 81U 81O
CLP 50BF 79
111111
22
MONITORING
BUSVT
Protection Features
Multiple Options
Several option for protection &
communications are provided to match
basic to high end application requirements.
Protection
The 350 feeder protection system offers
protection, control and monitoring in one
integrated, economical and compact
package.
Timed Overcurrent (Phase, Ground,
Neutral)
The 350 has three-phase TOC elements
which enables coordination with upstream
and downstream protection devices such
as fuses, overload relays, etc to maximize
fault selectivity and minimize interruptions
and downtime.
Multiple time current curves are available
including IAC, IEC, ANSI and IEEE curves.
Additional user programmable flex curves
can be used to customize and meet
specific coordination requirements. The
TOC has both linear and instantaneous
reset timing function to coordinate with
electro-mechanical relays
Instantaneous Overcurrent (Phase,
Ground, Neutral)
The instantaneous element provides
fast clearance of high magnitude
faults to prevent damage to the power
infrastructure and the equipment
connected to it.
Enhanced Diagnostics
Preventative Maintenance
The 350 allows users to track relay exposure
to extreme environmental conditions by
monitoring and alarming at high ambient
temperatures. This data allows users to
proactively schedule regular maintenance
work and schedule upgrade activities.
The diagnostics data enables the user to
understand degradation of electronics due
to extreme conditions.
Cost Effective
Robust Design
The 350 is subjected to Accelerated
Life Testing (ALT) to validate accurate
relay function under specified normal
conditions. The device is further tested for
durability through Highly Accelerated Life
Testing (HALT) where it undergoes extreme
operating conditions. The robust 350
design ensures long term operation.
Reduced Life Cycle Cost
The 350 is designed to reduce total
installation and life cycle cost for feeder
protection. The draw out construction
of the device reduces downtime during
maintenance and decreases extra
wiring needed for relay testing and
commissioning.
Neutral Overcurrent
The neutral signal is derived as the residual
sum of the three phase CTs eliminating the
need for an additional ground sensor.
Sensitive Ground Overcurrent
Sensitive ground protection feature
detects ground faults on high impedance
grounded systems in order to limit damage
to conductors and equipment. Special
low ratio CT’s are used for this purpose to
detect low magnitude ground faults.
Over/Under Voltage Protection
Overvoltage / Undervoltage protection
features can cause a trip or generate
an alarm when the voltage exceeds a
specified voltage setting for a specified
time.
Frequency Protection
The 350 offers overfrequency and
underfrequency elements to improve
network (grid) stability using voltage
or frequency based load shedding
techniques.
It also provides back up protection when
protecting feeders and other frequency
sensitive power equipment.
Arc Flash Mitigation
The 350 relay is equipped with multiple
setting groups and two user definable
inverse curves -FlexCurves A and B for
fast and reliable arc-flash mitigation and
breaker operation. In the event of an arc-
Device
Number Function
27P Phase Undervoltage
27X Auxiliary Undervoltage
49 Thermal Model
50P Phase Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50G Ground/Sensitive Ground
Instantaneous Overcurrent
50BF Breaker Failure
50_2 Negative Sequence Overcurrent
51P Phase Timed Overcurrent
51G Ground Timed Overcurrent
51N Neutral Timed Overcurrent
59P Phase Overvoltage
59X Auxiliary Overvoltage
59N Neutral Overvoltage
59_2 Negative Sequence Overvoltage
67G Ground Directional Overcurrent
67N Neutral Directional Overcurrent
79 Autoreclose
81U Underfrequency
81O Overfrequency
CLP Cold Load Pickup
ANSI Device Numbers & Functions
Latched Lockout available as a standard feature

350
Feeder Protection System
273
Distribution Feeder Protection
flash, the relay can be set to communicate
to any upstream or downstream devices
via IEC 61850 GOOSE messaging.
Cable Thermal Model
The cable thermal modelelement protects
feeder cables against overheating due
to excessive load. It estimates the
temperature rise of current carrying
conductors based on the amount of
current flow (I2R) and alarms when
temperature rise exceeds a threshold
value. This protection feature is essential
to ensure the longevity of electrical
feeders; particularly important to prevent
premature cable failures, expensive repair
costs and system down time.
Neutral/Ground Directional
Overcurrent
The directional ground overcurrent isolates
faulted feeders in ring bus or parallel feeder
arrangements. It also allows detection of
back feed of fault current from feeders
with motors.
Control
Cold Load Pick Up
Cold Load Pick up allows automatic or
manual blocking or raising of trip settings
for a period after the breaker has been
closed. This feature adapts the pick up
of overcurrent elements to override the
higher overload currents resulting from
re-energization of feeder after a long
period of time.
Breaker Failure
The Breaker Failure function is used to
determine when a trip command sent to
a breaker has not been executed within
a selectable time delay. In the event of
a breaker failure, the 350 will issue an
additional signal to trip the breakers
connected to the same busbar or signal
the trip of upstream breakers.
Autoreclose
Reclose can be initiated externally or from
an overcurrent protection. Up to four
reclose operations are available, each
with a programmable dead time. For each
reclose shot, the relay can be programmed
to block any overcurrent element.
Automation and
Integration
Inputs & Outputs
The 350 features the following inputs and
outputs for monitoring and control of
typical feeder applications:
• 8contactInputswithprogrammable
thresholds
• 2FormAoutputrelaysforbreakertrip
and close with coil monitoring
• 5FormCoutputrelays
IEC 61850 GOOSE
The 350 supports IEC 61850 Logical Nodes
which allows for digital communications
to DCS, SCADA and higher level control
systems.
In addition, the 350 also supports IEC
61850 GOOSE communication, providing
a means of sharing digital point state
information between 350’s or other IEC
61850 compliant IED’s.
• Eliminatestheneedforhardwiring
contact inputs to contact outputs via
communication messaging.
• Transmitsinformationfromonerelayto
the next in as fast as 8 ms.
• Enablessequencecoordinationwith
upstream and downstream devices.
• WhenBreakerOpenoperation
malfunctions, GOOSE messaging sends
a signal to the upstream breaker to trip
and clear the fault.
Logic Designer
Sixteen logic elements available for applications such as manual control, interlocking, and peer to peer tripping.

274
350
Feeder Protection System
Distribution Feeder Protection
Logic Elements
The 350 relay has sixteen Logic Elements
available for the user to build simple
logic using the state of any programmed
contact, virtual, remote input or the output
operand of a protection or control element.
The logic provides for assigning up to three
triggering inputs in an “AND/OR” gate for
the logic element operation and up to
three blocking inputs in an “AND/OR” gate
for defining the block signal. Pickup and
dropout timers are available for delaying
the logic element operation and reset
respectively.
Virtual Inputs
Virtual inputs allow communication devices
the ability to write digital commands to
the 350 relay. These commands could be
open/close the breaker, changing setting
groups, or blocking protection elements.
Multiple Settings Group
Two separate settings groups are stored in
nonvolatile memory, with only one group
active at a given time. Switching between
setting groups 1 and 2 can be done by
means of a setting, a communication
command or contact input activation.
The two settings groups allow users to store
seasonal settings- such as for summer and
winter or alternate profiles such as settings
during maintenance operations.
Monitoring & Diagnostics
Event Recording
Events consist of a broad range of change
of state occurrences, including pickups,
trips, contact operations, alarms and self
test status. The 350 relay stores up to
256 events time tagged to the nearest
millisecond. This provides the information
required to determine sequence of
events which facilitates diagnosis of relay
operation. Event types are individually
maskable in order to avoid the generation
of undesired events, and includes the
metered values at the moment of the
event.
Oscillography/ Transient Fault
Recorder
The 350 captures current and voltage
waveforms and digital channels at 32
samples per cycle. Multiple records can
be stored in the relay at any given time
with a maximum length of 192 cycles
Oscillography is triggered either by internal
signals or an external contact.
Trip/Close Coil Monitoring
The 350 can be used to monitor the
integrity of both the breaker trip and closing
coils and circuits. The supervision inputs
monitor both the battery voltage level,
while the outputs monitor the continuity of
the trip and/or closing circuits, by applying
a small current through the circuits.
Basic Metering
Metered values include:
• Current:Ia,Ib,Ic,In,Ig,Isg
• Phase-to-phaseandphase-to-ground
voltages for bus and line: Van, Vbn, Vcn,
Vab, Vbc, Vca
• Activepower(3-Phase)
• Reactivepower(3-Phase)
• Frequency
Advanced Device Health
Diagnostics
The 350 performs comprehensive device
health diagnostic tests during startup
and continuously at runtime to test
its own major functions and critical
hardware. These diagnostic tests monitor
for conditions that could impact system
reliability. Device status is communicated
via SCADA communications and the front
panel display. This continuous monitoring
and early detection of possible issues helps
improve system availability by employing
predictive maintenance.
IRIG-B
IRIG-B is a standard time code format
that allows time stamping of events
to be synchronized among connected
devices within 1 millisecond. An IRIG-B
input is provided in the 350 to allow time
synchronization using a GPS clock over a
wide area. The 350 IRIG-B supports both
AM and DC time synchronization with
an auto detect feature that removes the
requirement for manual selection.
Power System Troubleshooting
Analyze power system disturbances with transient fault recorder and event records

350
Feeder Protection System
275
Distribution Feeder Protection
Temperature Monitoring
The 350 continually monitors ambient
temperature around the relay and
alarms when the device is exposed to
extreme temperatures and undesirable
conditions such as air-conditioning
unit or station heater failures.
The EnerVista Viewpoint maintenance
tool allows users to review and analyze
the time period a 350 relay is exposed to
certain temperature ranges.
Security
Security Audit Trail
The Security Audit Trail feature provides
complete traceability of relay setting
changes at any given time and is NERC
CIP compliant. The 350 maintains a history
of the last 10 changes made to the 350
configuration, including modifications to
settings and firmware upgrades. Security
Setting Reports include the following
information:
• IfPasswordwasrequiredtochange
settings
• MACaddressofusermakingsetting
changes
• Listingofmodifiedchanges
• Methodofsettingchanges-Keypad,
Front serial port, Ethernet, etc.
Password Control
With the implementation of the Password
Security feature in the 350 relay, extra
measures have been taken to ensure
unauthorized changes are not made to
the relay. When password security is
enabled, changing of setpoints or issuing
of commands will require passwords
to be entered. Separate passwords
are supported for remote and local
operators, and separate access levels
support changing of setpoints or sending
commands.
Advanced
Communications
The 350 incorporates the latest
communication technologies making it
the easiest and the most flexible feeder
protection relay for use and integration
into new and existing infrastructures. The
350 relay provides the user with one front
USB and one rear RS485 communication
port. Also available with the 350 is a rear
communication port with Ethernet Fiber
and Copper. Through the use of these
ports, continuous monitoring and control
from a remote computer, SCADA system or
PLC is possible.
The 350 supports popular industry
standard protocols enabling easy, direct
integration into electrical SCADA and HMI
systems. The protocols supported by the
350 include:
• IEC61850
• IEC61850GOOSE
• DNP3.0
• ModbusRTU
Trace any setting changes with security audit trail

276
350
Feeder Protection System
Distribution Feeder Protection
• ModbusTCP/IP
• IEC60870-5-103
• IEC60870-5-104
These protocols make it easy to connect to
a Utility or Industrial automation system,
eliminating the need for external protocol
converter devices.
EnerVistaTM Software
The EnerVistaTM suite is an industry
leading set of software programs that
simplifies every aspect of using the 350
relay. The EnerVista suite provides all the
tools to monitor the status of the protected
asset, maintain the relay, and integrate
the information measured into DCS or
SCADA monitoring systems. Convenient
COMTRADE and sequence of event
viewers are an integral part of the 350 set
up software and are included to ensure
proper protection and system operation.
Simplified Feeder Setup
The 350 Feeder Protection System
includes a simplified setup process. This
simplified feeder setup consists of minimal
settings and can be accessed through
the relay front panel or via the EnerVista
Setup software. Once the information is
entered, the simplified setup will generate
a settings file, provide documentation
indicating which settings are enabled, and
an explanation of the parameters entered.
Viewpoint Monitoring
Viewpoint Monitoring is a simple to use
and full featured monitoring and data
recording software package for small
systems. Viewpoint monitoring provides a
complete HMI package with the following
functionality:
• Plugandplaydevicemonitoring
• Systemsinglelinemonitoringand
control
• Annunciatoralarmscreens
• Trendingreports
• Automaticeventretrieval
• Automaticwaveformretrieval
Display
A 4 line liquid crystal display (LCD) allows
visibility under varied lighting conditions.
When the keypad and display are not
being used, the metering summary page is
displayed to show critical metered values.
LEDs
The 350 relay has ten LED’s that provide
status indication for various conditions
of the relay and the system. The LED
indications are color coded to indicate the
type of event.
Fast and accurate configuration in one simple screen. 3 Series setup software protection summary for viewing a summary
of Protection & Control configuration.
Feeder protection settings in one easy step

350
Feeder Protection System
277
Distribution Feeder Protection
Typical Wiring Diagram
Mounting
5.350” 0.010”
(131.1 mm 0.25mm)
±±
4.100” 0.010”
(104.1 mm 0.25 mm)
±
±
0.200”
(5.1 mm)
Φ
6.900” 0.010”
(175.3 mm 0.25 mm)
±
±
6.000” 0.010”
(152.4 mm 0.25 mm)
±
±
4.000” 0.010”
(101.6 mm 0.25 mm)
±
±
C
L
C
L
898728.CDR
POWER SUPPLY
B1 A1 B2
+
-
chassis
gnd
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
DIGITAL INPUTS
52a(C1 #1)
52b(C1 #2)
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
ETHERNET
RJ45 mTRJ
10/100 BASE-T100 BASE-FX
USB
TYPE B
A5
A6
A7
A2
A3
A4
A8
A9
A10
A11
A12
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
V
V
4WIRE USB
4WIRE ETHERNET
USB
+
+
F5 F4 F3
--
++
RS485
IRIG-B
F1F2
COMMUNICATIONS
+
-
CONTROL
POWER
ABC
FEEDER
BUS Vts
52
E5 D5 E6 D6 E7 D7 E8 D8
I
A
I
A
I
B
I
B
I
C
I
C
I
G
I
G
FEEDER Cts
CONNECT AUX_VT
AS REQUIRED
VOLTAGEINPUTS
WYEVT
CONNECTION
E9 D9 E10D10E11D11E12D12
V
A
V
A
V
B
V
B
V
C
V
C
V
X
V
X
7 CRITICAL
FAILURE
RELAY
3AUXILIARY
4AUXILIARY
5AUXILIARY
6AUXILIARY
2CLOSE
1 TRIP
OPEN DELTA VT CONNECTION
E9 D9 E10D10 E11D11
OPTIONAL
DIRECTION OF POWER FLOW FOR POSITIVE WATTS
POSITIVE DIRECTION OF LAGGING VARs
Front Panel
Rear Pane l
350
Feeder Protection System
52a
52b
Breaker Aux Contacts
C11
C12 COMMON
CHASSIS GND
CURRENT INPUTS
PERSONAL
COMPUTER
OUTPUT CONTACTS
SHOWN WITH NO
CONTROL POWER
TRIP
CIRCUIT
CLOSE
CIRCUIT
TRIP
COIL
CLOSE
COIL
52b
52a
GROUND
BUS
SEE COMMUNICATIONS WIRING
IN INSTRUCTION MANUAL
1A OR 5A
COM
GE Multilin
COM
RS485
GROUND
BUS

278
350
Feeder Protection System
Distribution Feeder Protection
7.935”
6.621”
1.725” 7.795”
3.960”
6.820”
DISPLAY:
4 line text for easy viewing of key data
LEDs:
10 LED indicators for quick diagnostics
KEYPAD:
Ten button keypad for access to device interrogation
and change of settings.
FRONT PORT:
Electrically isolated front USB communication port
Front
Rear
Top
Side
SETPOINT GROUP 1, 2:
These indicators are continuously on if corresponding
group provides settings for protection elements.
TRIP:
Indicator turns on when relay detects a trip condition.
Operates the Trip Relay to open the breaker.
ALARM:
While relay detects an alarm condition, indicator
flashes.
PICKUP:
Indicator lights steady when any protection feature
pickup threshold exceeded.
User Interface
Dimensions

350
Feeder Protection System
279
Distribution Feeder Protection
Technical Specifications
PHASE/NEUTRAL/GROUND TIME OVERCURRENT
(51P/51N/51G)
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 x CT
Dropout Level: 97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I < 1 x CT
Curve Shape: ANSI Extremely/Very/Moderately/
Normally Inverse
Definite Time (0.05 s base curve)
IEC Curve A/B/C/Short
IAC Extreme/Very/Inverse/Short
User Curve, FlexCurve™ A/B
(programmable curves)
Curve Multiplier: 0.05 to 20.00 in steps of 0.01
Reset Time: Instantaneous, Linear
Time Delay
Accuracy:
±3% of expected inverse time or 1
cycle, whichever is greater
Level Accuracy: per CT input
SENSITIVE GROUND TIME OVERCURRENT (51SG)
Pickup Level: 0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level: 97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.002 x CT @ I < 0.1 x CT
Curve Shape: ANSI Extremely/Very/Moderately/
Normally Inverse
DefiniteTime
IEC Curve A/B/C/Short Inverse
IAC Extreme/Very/Inverse/Short
Inverse
User Curve, FlexCurve™ A/B
Curve Multiplier: 0.05 to 20.00 in steps of 0.01
Reset Time: Instantaneous, Linear
Time Delay
Accuracy:
±3% of expected inverse time or 1
cycle, whichever is greater
Level Accuracy: per CT input
OVERFREQUENCY (81O)
Pickup Level: 40.00 to 70.00 Hz in steps of 0.01
Dropout Level: Pickup -0.03 Hz
Time Delay: 0.0 to 600.0 s in steps of 0.1
Time Delay
Accuracy:
0 to 6 cycles (Time Delay selected)
Operate Time: Typically 10 cycles @ 0.1Hz/s
change
Level Accuracy: ±0.01 Hz
METERING SPECIFICATIONS
Parameter Accuracy Resolution Range
3-Phase Real Power (MW) ±1% of full scale 0.1 MW ±3000 MW
3-Phase Reactive Power
(Mvar)
±1% of full scale 0.1 Mvar ±3000 Mvar
3-Phase Apparent Power
(MVA)
±1% of full scale 0.1 MVA 3000 MVA
Power Factor ±0.05 0.01 -0.99 to 1.00
Frequency ±0.05 Hz 0.01 Hz 40.00 to 70.00 Hz
EVENT RECORDER
Number of events: 256
Header: relay name, order code, firmware
revision
Content: event number, date of event, cause
of event, per-phase current, ground
current, sensitive ground current,
neutral current, per-phase voltage
(VTs connected in “Wye”), or phase-
phase voltages (VTs connected in
“Delta”), system frequency, power,
power factor, thermal capacity
Data Storage: Retained for 3 days
CLOCK
Setup: Date and time Daylight Saving Time
IRIG-B: Auto-detect (DC shift or Amplitude
Modulated)
Amplitude modulated: 1 to 10 V pk-pk
DC shift: TTL
Input impedance: 40kOhm ± 10%
RTC Accuracy: ± 1 min / month
LOGIC ELEMENTS
Number of logic
elements:
8
Trigger source
inputs per
element:
3
Block inputs per
element:
3
Supported
operations:
AND, OR, NOT, Pickup / Dropout
timers
Pickup timer: 0 to 6000 ms in steps of 1 ms
Dropout timer: 0 to 6000 ms in steps of 1 ms
BREAKER CONTROL
Operation: Asserted Contact Input, Logic
Element, Virtual Input, Manual
Command
Function: Opens / closes the feeder breaker
AUTORECLOSE
Reclose attempts: Up to 4 shots
Time Delay
Accuracy:
0 to 3 cycles (AR Dead Time selected)
Elements: Inputs, Outputs, Breaker Status (52
status)
BREAKER FAILURE
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01
Dropout Level: 97 to 98% of pickup
Time Delay
Accuracy:
0 to 1 cycle (Timer 1, Timer 2)
Level Accuracy: per CT input
COLD LOAD PICKUP BLOCKING
Operation: Automatically (current level), or by
command (asserted input)
Function: Block IOC functions, raise TOC pickup,
for selected period of
time
Time Delay
Accuracy:
0 to 1 cycle (block Time)
±50ms(outagetime?≤?5min)
±1 s (outage time > 5 min)
AMBIENT TEMPERATURE
High Temperature
Pickup:
20°C to 80°C in steps of 1°C
Low Temperature
Pickup:
-40°C to 20°C in steps of 1°C
Time Delay: 1 to 60 min in steps of 1 min
±50ms(outagetime?≤?5min)
±1 s (outage time > 5 min)
Temperature
Dropout:
Configurable 90 to 98% of pickup
Temperature
Accuracy:
±10°C
Timing Accuracy: ±1 second
BREAKER TRIP COUNTER
Trip Counter Limit
(Pickup):
1 to 10000 in steps of 1
TRANSIENT RECORDER
Buffer size: 3 s
No. of buffers: 1x192, 3x64, 6x32
No. of channels: 14
Sampling rate: 32 samples per cycle
Triggers: Manual Command
Contact Input
Virtual Input
Logic Element
Element Pickup/Trip/Dropout/Alarm
Data: AC input channels
Contact input state
Contact output state
Virtual input state
Logic element state
Data storage: RAM - battery backed-up
PHASE/NEUTRAL/GROUND NEGATIVE SEQUENCE
INSTANTANEOUS OVERCURRENT (50P/50N/50G/50_2)
Pickup Level: 0.05 to 20 x CT in steps of 0.01 x CT
Dropout Level: 97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I <1 x CT
Time delay: 0.00 to 300.00 sec in steps of 0.01
Operate Time: <30ms@60Hz(I>2.0xPKP,Notime
delay)
<35ms@50Hz(I>2.0xPKP,Notime
delay)
Time Delay
Accuracy:
0 to 1 cycle (Time Delay selected)
Level Accuracy: per CT input
SENSITIVE GROUND INSTANTANEOUS OVERCURRENT
(50SG)
Pickup Level: 0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level: 97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.002 x CT @ I < 0.1 x CT
Time delay: 0.00 to 300.00 sec in steps of 0.01
Operate Time: <30ms@60Hz(I>2.0xPKP,Notime
delay)
<35ms@50Hz(I>2.0xPKP,Notime
delay)
Time Delay
Accuracy:
0 to 1 cycle (Time Delay selected)
Level Accuracy: per CT input
NEUTRAL DIRECTIONAL
Directionality: Co-existing forward and reverse
Polarizing: Voltage, Current, Dual
Polarizing Voltage: V0calculated using phase voltages
(VTs must be
connected in “Wye”)
- V0measured by Vaux input (3V0
provided by an external
open delta connection).
Polarizing Current: Ig
MTA: From 0° to 359° in steps of 1°
Angle Accuracy: ±4º
Operation Delay: 20 to 30 ms
GROUND DIRECTIONAL
Directionality: Co-existing forward and reverse
Operating: Ground Current (Ig)
Polarizing Voltage: V0calculated using phase voltages
(VTs must be connected
in “Wye”)
- V0measured from Vaux input. (3V0
provided by an external
open delta connection).
MTA: From 0° to 359° in steps of 1°
Angle Accuracy: ±4º
Operation Delay: 20 to 30 ms
PHASE/AUXILIARY UNDERVOLTAGE (27P/27X)
Minimum Voltage: Programmable from 0.00 to 1.25 x VT
in steps of 0.01
Pickup Level: 0.00 to 1.25 x VT in steps of 0.01
Dropout Level: 101 to 104% of pickup
Curve: Definite Time, Inverse Time
Time Delay: 0.0 to 600.0 s in steps of 0.1
Operate Time: Time delay ±30 ms @ 60Hz (V < 0.85
xPKP)
Time delay ±40 ms @ 50Hz (V < 0.85
xPKP)
Time Delay
Accuracy:
±3% of expected inverse time or 1
cycle, whichever is greater
Level Accuracy: Per voltage input
PHASE/AUXILIARY/NEUTRAL/NEG SEQ OVERVOLTAGE
(59P/59X/59N/59_2)
Minimum Voltage: Programmable from 0.00 to 1.25 x VT
in steps of 0.01
Pickup Level: 0.00 to 1.25 x VT in steps of 0.01
Dropout Level: 96 to 99% of pickup
Time Delay: 0.0 to 600.0 s in steps of 0.1
Operate Time: Time delay ±35 ms @ 60Hz (V > 1.1
xPKP)
Time delay ±40 ms @ 50Hz (V > 1.1
xPKP)
Time Delay
Accuracy:
0 to 1 cycle (Time Delay selected)
Level Accuracy: Per voltage input
UNDERFREQUENCY (81U)
Minimum Voltage: 0.00 to 1.25 x VT in steps of 0.01
Pickup Level: 40.00 to 70.00 Hz in steps of 0.01
Dropout Level: Pickup +0.03 Hz
Time Delay: 0.0 to 600.0 s in steps of 0.1
Time Delay
Accuracy:
0 to 6 cycles (Time Delay selected)
Operate Time: Typically 10 cycles @ 0.1Hz/s
change
Level Accuracy: ±0.01 Hz

280
350
Feeder Protection System
Distribution Feeder Protection
TYPE TESTS
Dielectric voltage
withstand:
2.3KV
Impulse voltage
withstand:
EN60255-5 5KV
Damped
Oscillatory:
IEC 61000-4-18
IEC 60255-22-1 2.5KVCM,1KV
DM
Electrostatic
Discharge:
EN61000-4-2/
IEC 60255-22-2 Level 4
RF immunity: EN61000-4-3/
IEC 60255-22-3 Level 3
Fast Transient
Disturbance:
EN61000-4-4/
IEC 60255-22-4 Class A and B
Surge Immunity: EN61000-4-5/
IEC 60255-22-5 Level 3 & 4
Conducted RF
Immunity:
EN61000-4-6/
IEC 60255-22-6 Level 3
Power Frequency
Immunity:
EN61000-4-7/
IEC 60255-22-7 Class A & B
Voltage
interruptionand
Ripple DC:
IEC 60255-11 15% ripple,
200ms
interupts
Radiated &
Conducted:
Emissions
CISPR11 /CISPR22/
IEC 60255-25 Class A
Sinusoidal
Vibration:
IEC 60255-21-1 Class 1
Shock & Bump: IEC 60255-21-2 Class 1
Siesmic: IEC 60255-21-3 Class 2
Power magnetic
Immunity:
IEC 61000-4-8 Level 5
Pulse Magnetic
Immunity:
IEC 61000-4-9 Level 4
Damped Magnetic
Immunity:
IEC 61000-4-10 Level 4
Voltage Dip &
interruption:
IEC 61000-4-11 0, 40, 70, 80%
dips, 250/
300 cycle
interrupts
Damped
Oscillatory:
IEC 61000-4-12 2.5KVCM,1KV
DM
Conducted RF
Immunity 0-150khz:
IEC 61000-4-16 Level 4
Voltage Ripple: IEC 61000-4-17 15% ripple
Ingress Protection: IEC 60529 IP40 front ,
IP10 Back
Environmental
(Cold):
IEC 60068-2-1 -40C 16 hrs
Environmental (Dry
heat):
IEC 60068-2-2 85C 16hrs
Relative Humidity
Cyclic:
IEC 60068-2-30 6day variant 2
EFT: IEEE/ANSI C37.90.1 4KV,2.5Khz
Damped
Oscillatrory:
IEEE/ANSI C37.90.1 2.5KV,1Mhz
RF Immunity: IEEE/ANSIC37.90.2 20V/m
80-1Ghz
ESD: IEEE/ANSIC37.90.3
UL508
8KVCD/15KV
AD
e83849NKCR
Safety: UL C22.2-14
UL1053 e83849NKCR7
e83849NKCR
PHASE & GROUND CURRENT INPUTS
CT Primary: 1 to 6000 A
Range: 0.02 to 20 × CT
Input type: 1 A or 5 A (must be specified with
order)
Nominal
frequency:
50/60 Hz
Burden: <0.1 VA at rated load
Accuracy: ±1% of reading at 1× CT
±3% of reading from 0.2 to 20 × CT
±20% of reading from 0.02 to 0.19
× CT
CT withstand: 1 second at 100 × rated current
2 seconds at 40 × rated current
continuous at 3 × rated current
HIGH RANGE POWER SUPPLY
Nominal: 120 to 240 VAC 125 to 250 VDC
Range: 60 to 300 VAC (50 and 60 Hz)
84 to 250 VDC
Ride-through time: 35 ms
TRIP / CLOSE SEAL-IN
Relay 1 trip seal-in: 0.00 to 9.99 s in steps of 0.01
Relay 2 close
seal-in:
0.00 to 9.99 s in steps of 0.01
ALL RANGES
Voltage withstand: 2 × highest nominal voltage for 10
ms
Power
consumption:
15 W nominal, 20 W maximum
20 VA nominal, 28 VA maximum
LOW RANGE POWER SUPPLY
Nominal: 24 to 48 VDC
Range: 20 to 60 VDC
SERIAL
RS485 port: Opto-coupled
Baud rates: up to 115 kbps
Response time: 1 ms typical
Parity: None, Odd, Even
Maximum
Distance:
1200 m (4000 feet)
Isolation: 2 kV
Protocol: Modbus RTU, DNP 3.0,
IEC 60870-5-103
ETHERNET (COPPER)
Modes: 10/100 MB (auto-detect)
Connector: RJ-45
Protocol: Modbus TCP/IP, DNP 3.0,
IEC 60870-5-104, IEC 61850 GOOSE
USB
Standard
specification:
Compliant with USB 2.0
Data transfer rate: 115 kbps
CERTIFICATION
Low voltage directive EN60255-5 /
EN60255-27 / EN61010-1
CE: EMC Directive EN60255-26/
EN50263, EN61000-6-2, UL508
North America: cULus UL1053, C22.2.No 14
ISO: Manufactured under a registered
quality program ISO9001
ETHERNET (FIBER)
Fiber type: 100 MB Multi-mode
Wavelength: 1300 nm
Connector: MTRJ
Transmit power: -20 dBm
Receiver
sensitivity:
-31 dBm
Power budget: 9 dB
Maximum input
power:
-11.8 dBm
Typical distance: 2 km (1.25 miles)
Duplex: half/full
Protocol: Modbus TCP/IP, DNP 3.0,
IEC 60870-5-104, IEC 61850 GOOSE
CONTACT INPUTS
Inputs: 8
Selectable
thresholds:
17, 33, 84, 166 VDC
Recognition time: 1/2 cycle
Debounce time: 1 to 64 ms, selectable, in steps of 1
ms
Continuous
current draw:
2 mA
Type: opto-isolated inputs
External switch: wet contact
Maximum input
voltage:
300 VDC
SENSITIVE GROUND CURRENT INPUT
CT Primary: 1 to 600 A
Range: 0.002 to 3 × CT
Input type: 1 A or 5 A (must be specified with
order)
Nominal
frequency:
50/60 Hz
Burden: <0.1 VA at rated load
Accuracy: ±1% of reading at 0.1× CT
±3% of reading from 0.02 to 3 × CT
±20% of reading from 0.002 to 0.019
× CT
CT withstand: 1 second at 100 × rated current
2 seconds at 40 × rated current
continuous at 3 × rated current
PHASE/AUX VOLTAGE INPUTS
Source VT: 0.12 to 65 kV / 50 to 220 V
VT secondary: 50 to 240 V
VT ratio: 1 to 5000 in steps of 1
Nominal
frequency:
50/60 Hz
Accuracy: ±1.0% of reading
Voltage withstand: 260 VAC continuous
FORM-A VOLTAGE MONITOR
Applicable voltage: 20 to 250 VDC
Trickle current: 1 to 2.5 mA
FORM-C RELAYS
Configuration: 5 (five) electromechanical
Contact material: silver-alloy
Operate time: <8 ms
Continuous
current:
10 A
Make and carry
for 0.2s:
30 A per ANSI C37.90
Break (DC
inductive, L/R=40
ms):
24 V / 1 A 48 V / 0.5 A 125 V / 0.3
A 250 V / 0.2 A
Break (DC
resistive):
24 V / 10 A 48 V / 6 A 125 V / 0.5
A 250 V / 0.3 A
Break (AC
inductive):
720 VA @ 250 VAC Pilot duty A300
Break (AC
resistive):
277 VAC / 10 A
FORM-A RELAYS
Configuration: 2 (two) electromechanical
Contact material: silver-alloy
Operate time: <8 ms
Continuous
current:
10 A
Make and carry
for 0.2s:
30 A per ANSI C37.90
Break (DC
inductive, L/R=40
ms):
24 V / 1 A 48 V / 0.5 A 125 V / 0.3
A 250 V / 0.2 A
Break (DC
resistive):
24 V / 10 A 48 V / 6 A 125 V / 0.5
A 250 V / 0.3 A
Break (AC
inductive):
720 VA @ 250 VAC Pilot duty A300
Break (AC
resistive):
277 VAC / 10 A
DIMENSIONS
Size: Refer to Dimensions Chapter
Weight: 4.1 kg [9.0 lb]
OPERATING ENVIRONMENT
Ambient operating
temperature:
–40°C to +60°C [-40°F to +140°F]
Ambient storage /
shipping
temperature:
–40°C to +85°C [-40°F to +185°F]
Humidity: Operating up to 95% (non
condensing) @ 55C (As per
IEC 60068-2-30 Variant 2, 6days)
Pollution degree: II
Overvoltage
category:
III
Ingress Protection: IP40 Front , IP10 back

350
Feeder Protection System
281
Distribution Feeder Protection
110609 - V19
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
Accessories for the 350
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• Buya350online
• Viewthe350brochure
Note: 1) G1/G5 and S1/S5 must match corresponding P1/P5 - there cannot be 5A and 1A mixing
Visit www.GEMultilin.com/350 to:
Ordering
350 E ** ** * * * * * ** D * Description
Base Unit 350
Language E English
Phase Currents P1 1A three phase current inputs
P5 5A three phase current inputs
Ground Currents G1 1A ground current input
G5 5A ground current input
S1 1A sensitive ground current input
S5 5A sensitive ground current input
Power Supply L24 - 48 Vdc
H125 - 250 Vdc/120 - 240Vac
Faceplate SStandard faceplate (LCD, full menu, actual values and setpoints) with 8 Inputs, 7 Outputs (2 Form
A, 5 Form C) --- Only for 350
EStandard faceplate (LCD, full menu, actual values and setpoints) with 10 Inputs, 7 Outputs (2 Form
A, 5 Form C)
Current Protection SStandard Overcurrent Protection - 50P(1), 50G(1), 50N(1), 51P(1), 51G(1), 51N(1)
EExtended Overcurrent Protection - 49, 50P(2), 50G(2), 50N(2), 51P(1), 51G(1), 51N(1)
MAdvanced overcurrent protection - 49, 50P(2), 50G(2), 50N(2), 51P(1), 51G(1), 51N(1), 50_2 (46)
Control NNo Selection
CCLP, 50BF, Autoreclose (79), Lockout (86)
Options NNo Selection
DDirectional Neutral Overcurrent Protection 67N(1), 67G(1)
MVoltage Metering
RNeutral and Ground Directional elements 67N(1), 67G(1) + Voltage Metering
PVoltage Protection, Neutral and Ground Directional elements - 27P(1), 27X(1), 59P(1), 59N(1),
59X(1), 59_2(1), 81O(2), 81U(2), 67N(1), 67G(1)
Communications SN Standard :Front USB, Rear RS485 : Modbus RTU, DNP3.0, IEC 60870-5-103
1E Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104
2E Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104, IEC 61850
GOOSE
3E Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104, IEC 61850
Case Design DDraw-out Design
Harsh Environment N None
HHarsh Environment Conformal coating

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Requisition: 480-Z7612 - MV Shop Order: 111027-01
SWITCHGEAR SWGR-Q-A ( 15LSWGR901 )
Item: 1 Part Number: PVGX1A1A2A2202G1A1
Qty: 4 UOM: EA
Description: POWERVAC BKR PVG - POWER-VAC EQUIPMENT BREAKER
X - 15.0KV - 40KA
1 - 1200A RATING
A - RETROFIT CODE - NONE
1 - REVISION 1
A - NO CAP SWITCHING
2 - 5-CYCLE BKR
A - 60 HZ. RATING
2 - 125VDC CLOSE COIL STANDARD WIRING
2 - 125VDC TRIP COIL - 1ST
0 - NO 2ND TRIP COIL
2 - 125VDC CHARGING MOTOR
G - SEISMIC/UL LABEL/CERTIFIED TEST REPORTS
1 - NO FAST BUS TRANSFER
A - NO DIELECTRIC ENHANCEMENTS
1 - NO SPECIALS
Summary Drawing
Mark Mark Breaker Loop Tag
001 52M1 Q00 15LMBK901
001 52A1 Q01 15LFBK903
001 52A2 Q02 15LFBK907
001 52A3 Q03 15LFBK911
Device Data Sheet
Breaker Information Sheet
Sheet B

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Requisition: 480-Z7612 - MV Shop Order: 111027-04
SWITCHGEAR SWGR-Q-B ( 15LSWGR902 )
Item: 1 Part Number: PVGX1A1A2A2202G1A1
Qty: 4 UOM: EA
Description: POWERVAC BKR PVG - POWER-VAC EQUIPMENT BREAKER
X - 15.0KV - 40KA
1 - 1200A RATING
A - RETROFIT CODE - NONE
1 - REVISION 1
A - NO CAP SWITCHING
2 - 5-CYCLE BKR
A - 60 HZ. RATING
2 - 125VDC CLOSE COIL STANDARD WIRING
2 - 125VDC TRIP COIL - 1ST
0 - NO 2ND TRIP COIL
2 - 125VDC CHARGING MOTOR
G - SEISMIC/UL LABEL/CERTIFIED TEST REPORTS
1 - NO FAST BUS TRANSFER
A - NO DIELECTRIC ENHANCEMENTS
1 - NO SPECIALS
Summary Drawing
Mark Mark Breaker Loop Tag
001 52M2 Q50 15LMBK902
001 52B1 Q51 15LFBK904
001 52B2 Q52 15LFBK908
001 52B3 Q53 15LFBK912
Device Data Sheet
Breaker Information Sheet
Sheet B

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Requisition: 480-Z7612 - MV Shop Order: 111027-01
12.47KV SERVICE CENTER ADDITIONS
Item: 2 Part Number: PVGY1J1A2A2202G1A1
Qty: 1 UOM: EA
Description: POWERVAC BKR PVG - POWER-VAC EQUIPMENT BREAKER
Y - 15.0KV - 50KA
1 - 1200A RATING
J - RETROFIT CODE - 13.8kV, 750MVA, 77kA C&L
1 - REVISION 1
A - NO CAP SWITCHING
2 - 5-CYCLE BKR
A - 60 HZ. RATING
2 - 125VDC CLOSE COIL STANDARD WIRING
2 - 125VDC TRIP COIL - 1ST
0 - NO 2ND TRIP COIL
2 - 125VDC CHARGING MOTOR
G - SEISMIC/UL LABEL/CERTIFIED TEST REPORTS
1 - NO FAST BUS TRANSFER
A - NO DIELECTRIC ENHANCEMENTS
1 - NO SPECIALS
Summary Drawing
Mark Mark Breaker Loop Tag
** ** 110B 15LFBK902
Device Data Sheet
Breaker Information Sheet
Sheet B

Sludge Dewatering and Odor Control at Plant 1 Specification: 16340
Project No. P1-101 Medium Voltage Switchgear
Manufacturer Catalog Number Drawing Reference Mark
Basler BE1-27A3EE1JA1S3F BE1-27
Data Sheet
Undervoltage Relay
Type BE1-27
This manual suits for next models
4
Table of contents