USER MANUAL G-913-P01 PAGE 6
PPUH „GECO” Sp. z o.o. ISSUE I AS OF 2018.09.13
5.2 Description of the conditions for transitions between states:
From POWERUP (after about 5 seconds from turning on a power supply):
to RUN mode –after making sensor calibration and stabilization of power supply
from RUN mode:
to ALARM mode –after detecting a fault of one of the sensors
from ALARM mode:
to RUN mode –when the sensor failure is removed
6WORKING IN ALARM MODE
When the sensor failure is detected G-913 recorder is moving to ALARM state. This is signaled
by quick flashing of the LED in the specific sequence:
1 blink -> break - short circuit of the NTC-1 sensor
2 flashes -> break - opening the NTC-1 sensor
3 flashes -> break - short circuit of the NTC-2 sensor
4 flashes -> break - opening the NTC-2 sensor
If more than one alarm occurs, the alarm codes are displayed one after another. The alarm states
are recorded in the register as Err + (sensor opening) and Err (sensor short-circuit) instead of the
registered temperature.
7POWER LOSS
If the recorder detects a loss of the main power supply, after the voltage recovery, information about
the date and time of the power supply return and the duration of the decay is recorded in the log.
8STANDARD WORK
The device has the task of recording the indications from two temperature sensors. The
device starts to work after approx. 5 seconds. since the power is detected, the recorder performs
the first measurement. Each subsequent measurement is saved at a specific frequency (default: 5
min). The device can store 30,000 measurements. Data recording is circular, i.e. after overflow of
memory the oldest measurements are overwritten, thus the last 30000 measurements are
constantly stored in memory. Mixing data to a USB drive does not delete them from the recorder.
Each correct data registration is confirmed by a short blink of the diode.
During the operation of the device, it is possible to read the measurement register at any time,
and change the date and time settings.
After inserting the USB device into the device, the LED lights up permanently and goes out
only after USB operation.