19 | P a g e
•At the end of this initialization operation, a sequence of characters will be shown on the display to indicate the selected output
and voltage, according to the following scheme:
oCH + size (kg/h) + U + voltage (1 = 115V, 2 = 230V)
1. CH01U1 = 1.6 kg/h 115V
2. CH02U1 = 2.2 kg/h 115V
3. CH03U2 = 3.3 kg/h 230V Default setting is Option 3 if no selection is made
4. CH04U2 = 4.5 kg/h 230V
oIf no selection is made within 10 seconds, the unit will start using the default setting Option 3. The unit can beconfigured
again the next time it is turned on.
oThe unit can produce steam even if not configured but the warning ‘EH’ will be shown on the display.
•The yellow power LED comes on and steam unit is ready to operate.
•The green LED ‘cloud’ will light up when the boiler electrodes are powered on and creating steam.
4.5 Starting With A New Steam System or Replacement Steam Cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function as follows:
1. Switch the 5500 Steam Humidifier off.
2. Press and hold both buttons, “RESET/SEL” and “DRAIN/ENTER”, and switch the 5500 Steam Humidifier back on. When the
wrench blinks then release the two buttons.
3. Press and hold “RESET/SEL” until the display shows 04.
: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press “RESET/SEL” until the display
goes back to the normal operating mode and restart from step 1.
4. Press “DRAIN/ENTER” (minimum 1 second): the cleaning starts and the display shows PC.
During the cleaning,the electrodes are powered and water in the cylinder rises until it touches the high-level sensoror thephasecurrent
equals 20A, whichever occurs first. After either of theevents is detected, the boiler is fully dischargedwith the electrodes un-powered(the drain
pump and thedrain tempering valve areactivated for 3minutes). It is recommended that two cleanings areperformed when starting a new
steam unit. After the cleaning ends, the humidifier begins its regular function. When starting the unit with a new or empty cylinder, it may take a
significant amount of time (hours) for the unit to build up enough mineral concentration to reach ratedcapacity. This time can be shortened by
theaddition ofa teaspoon of salt or ¼ of an antacid tablet throughthe steamoutlet ontop ofthe cylinder.
5. Operating the 5500 Steam Humidifier
5.1 Displaying Information
By pressing the “reset” button for 2 seconds, the display will loop from amperage to production in % of the maximum production to
the hour counter and back to amperage: Figure 5.a
1. Amperage: it is the value of the current that flows through the water, causing it to boil (default display).
2. Production %: it is the current production expressed as a percentage of the humidifier’s capacity.
3. Hour counter: counts the operating hours, proportional to the % of cylinder production (this must be reset whenever the
cylinder is replaced). For example, if the cylinder has worked for 100 hours at 50% production, the number of proportional
operating hours is 50. The value is expressed in tens of hours, so for example when the display shows 13, the real number of
operating hours is between 130 and 139 hours. Once 1990 hours have elapsed (199 on the display), the hours are displayed in
hundreds. Example: 21 = 2100 hours.
5.2. Select Signal Type
The steam humidifier is pre-set for the included GFX4 humidistat (signal type 0). If the included GFX4 humidistat is used, this
section may be omitted. If another humidistat is used, review this section to see if changes are needed.
Note: select the correct control signal type on the keypad before connecting the control wiring. If no selection is made within 3
seconds, the software automatically returns to normal operating mode.
1. Switch steam humidifier off.
2. Press and hold both buttons “reset” and “drain” and switch the 5500 Steam Humidifier back on. When the wrench blinks,
release the two buttons.
3. Press “RESET/SEL” until the display shows 02. : DO NOT confirm any value higher than 04. If 05 or higher is
displayed, press “RESET/SEL” until the display goes back to the normal operating mode and restart from step 1.
4. Press “DRAIN/ENTER” (minimum 1 second) to confirm: the display shows “P1” then the current signal type and “set”.
5. Press “RESET/SEL” to change signal type between 0 and 1:
0 = On-Off humidistat such as the GeneralAire®“M” or “GFX” series humidistat.
1 = external 0...10 Vdc modulating signal such as the GeneralAire®ADCD series humidistat.
6. Press “DRAIN/ENTER” (minimum 1 second) when done to confirm the new value of P1 and exit to the normal operating mode.
7. Switch steam humidifier off: you can now proceed with connecting the control wiring.