Elite Steam +030222075 Rev. 3.4 – Sept. 2011
20
5.5 Using the GFX3 Humidistat
Press to select OFF, MANUAL or AUTO mode (if outdoor sensor is connected).
OFF mode: The humidifier is turned off.
MANUAL mode: The GFX3 will work to maintain the single humidity selected. You can set
your desired humidity level by pressing or . The humidifier will turn ON or OFF
according to your manual setting. (The humidifier will operate when the measured relative
humidity falls more than 2% below the set point.) Humidity will have to be lowered when
weather is colder or if condensation is suspected.
AUTO mode: The GFX3 will automatically raise the humidity as the outdoor temperature
increases. This provides the highest possible humidity. The GFX3 will automatically lower the humidity as temperatures drop. This
minimizes the risk of condensation on cold surfaces like windows. You can adjust the Auto Humidity Index Set Point from 0 (low) to
10 (high) by pressing or . The Humidity Index is based on the outdoor temperature and indoor humidity. The humidifier will
switch ON/OFF according to the calculated auto humidity index set point. Lower Index settings are for older homes with less
insulation and vapor barriers. Higher Index settings are for newer homes with complete vapor barriers, triple pane windows and high
R value insulation. If condensation occurs reduce Index setting by 2 points until condensation stops.
NOTE If the outdoor temperature sensor fails, flashes and the unit will default to MANUAL mode.
To toggle between indoor / outdoor temperature and indoor humidity: Press .
To change the temperature unit: Press °C / °F.
To set the temperature / humidity offset in MANUAL or AUTO mode:
1. Simultaneously press and when viewing the temperature or humidity reading.
2. Use or to change the setting (-3 to 3).
3. Press and simultaneously or wait 5 seconds to confirm and move onto the next setting.
WARNING: Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.
5.6 Alarms
In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple
alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although
still active alarms will continue to display.
Dis
play Description Action Red
Led Alarm
Relay Notes
-- Remote on-off open Unit disabled Off Off
EE Internal memory error Unit disabled On On
E0 Control board configuration not valid Unit disabled On On Turn off, check control board, reprogram
E1 High current alarm Unit disabled On On Turn off, check connections, check
cylinder (no limescale bridges between
electrodes, no electrodes short-circuited)
E2 Low production, low supply water
conductivity or excessive
foam/limescale in the cylinder
Unit disabled.
Press “reset/sel” key for 1 seconds to reset. On On Check supply water conductivity (too
low?), replace the cylinder.
E3 Cylinder almost exhausted, already
used for 2000 hrs Press “reset/sel” key for 1 seconds to reset. Off Off Change cylinder (not urgent)
E4 Fill alarm, unable or slow fill
(current does not increase within
timeout)
Press “reset/sel” key for 1 seconds to reset, otherwise
the warning will be reset automatically every 10
minutes until the supply water is available again.
On On Check water supply and fill valve; check
drain pump for leakage
E5 Drain alarm, unable to drain
(current does not decrease within
timeout)
Press “reset/sel” key for 1 seconds to reset On On Check drain pump and drain connection
E6 Cylinder exhausted
(critical performance detected) The warning is automatically reset if Elite Steam can
produce the demand, otherwise turn off and then on. Off Off Change cylinder (urgent)
E7 Foam detected Press “reset/sel” key for 1 seconds to reset Off Off If it continues, do some cleaning cycles
(read chap. “Starting with a new
cylinder”)
E8 Cylinder lifetime expired (3000 hours) Unit disabled: Reset the hour counter (read chap.
Resetting the hour counter”) On On Change the cylinder if necessary
E9 High controller temperature (above
176 °F / 80 °C) The warning is automatically reset if the temperature
decreases below 176 °F / 80 °C. Off Off Check the ambient temperature, replace
the controller.
Suggested
Setting Outdoor
Temperatures
15% -20˚F -29˚C
20% -10˚F -23˚C
25% 0˚F -18˚C
30% +10˚F -12˚C
35% +20˚F - 7˚C
40% +30˚F - 1˚C