GESTRA TRG 5-6 User manual

1
EN
English
Temperature Sensor
TRG 5-6..
Original Installation Instructions
818597-05

2
Contents
Page
Important notes
Usage for the intended purpose...............................................................................................................4
Function..................................................................................................................................................4
Safety note..............................................................................................................................................4
Directives and standards
Pressure Equipment Directive 2014/34/EU..............................................................................................5
Functional Safety acc. to IEC 61508 ........................................................................................................5
DIN EN 14597 .........................................................................................................................................5
Approvals for Marine Applications ...........................................................................................................5
ATEX (Atmosphère Explosible) .................................................................................................................5
Note on the Declaration of Conformity / Declaration by the Manufacturer ..........................................5
Technical data
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68........................................................6
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68........................................................7
Scope of supply ......................................................................................................................................7
Tolerances of the precision resistor according to EN 60751....................................................................8
Name plate / marking .............................................................................................................................8
Installation
Dimensions TRG 5-63 and TRG 5-64.......................................................................................................9
Key .........................................................................................................................................................9
Dimensions TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68....................................................................10
Key .......................................................................................................................................................10
TRG 5-63 and TRG 5-64........................................................................................................................11
TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68.......................................................................................11
Tools.....................................................................................................................................................11
Examples of installation ........................................................................................................................12
Electrical connection
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68, terminal box.................................13
Key .......................................................................................................................................................13

3
Contents
Page
Electrical connection
Connecting the temperature sensor.......................................................................................................14
Connecting the measuring element.......................................................................................................14
Wiring diagram for temperature sensor .................................................................................................15
Tools.....................................................................................................................................................15
Key .......................................................................................................................................................15
Troubleshooting
Indication, diagnosis and remedy ..........................................................................................................16
Measure the fluid temperature ..............................................................................................................16
Safety note............................................................................................................................................17
Replacing the temperature measuring element .....................................................................................17
Spare Parts ...........................................................................................................................................17
Removing and disposing of the temperature sensor
Removing and disposing of temperature sensor TRG 5-63 or TRG 5-64.................................................18
- continued -

4
Important notes
Usage for the intended purpose
The temperature sensor TRG 5-6.. in conjunction with temperature switches TRS 5-50, TRS 5-52 or
with temperature transmitter TRV 5-40 are designed for measuring temperatures in steam or hot water.
Danger
The temperature sensors TRG 5-63 or TRG 5-64 are screwed into vessels or pipes. When
loosening the temperature sensor steam or hot water might escape! This presents the risk
of severe scalding all over the body!
It is therefore essential not to dismantle the temperature sensor unless the boiler pressure
is verified to be 0 bar.
The temperature sensor becomes hot during operation.
Risk of severe burns to hands and arms.
Before carrying out installation and maintenance work make sure that the equipment is cold.
Safety note
Safety temperature limiters/monitors
are items of equipment with safety function (PED) and must only be
installed, wired and commissioned by qualified and competent staff.
Retrofitting and maintenance work must only be performed by qualified staff who - through adequate
training - have achieved a recognised level of competence.
The temperature sensors TRG 5-63, TRG 5-65, TRG 5-66 and TRG 5-67 feature one integrated platinum
resistance thermometer Pt 100 to EN 60751 each.
The temperature sensors TRG 5-64 and TRG 5-68 are equipped with two platinum resistance
thermometers Pt 100 for the connection of additional indicating equipment.
The ohmic resistance of the resistance thermometer changes as a function of temperature. If a
constant current is applied, the voltage produced by the change of resistance is measured and further
processed in the temperature switch or temperature transmitter.
The temperature sensor can be used as measuring transducer for
na safety temperature monitor/limiter in conjunction with temperature transmitter TRV 5-40 and
control unit NRS 1-40.1
na temperature monitor/controller in conjunction with temperature transmitter TRV 5-40 and
switching controller TRS 5-40
na safety temperature monitor/limiter in conjunction with temperature switch TRS 5-50
na temperature monitor in conjunction with temperature switch TRS 5-52
Function
Attention
The name plate specifies the technical features of the equipment. Note that any piece of
equipment without its specific name plate must neither be commissioned nor operated.

5
Directives and standards
Pressure Equipment Directive 2014/68/EU
Safety temperature limiters/monitors are safety accessories as defined in the Pressure Equipment
Directive (PED). The temperature switch TRS 5-50 and the temperature transmitter TRV 5-40 (together
with control unit NRS 1-40.1) in conjunction with temperature sensors TRG 5-6.. are EC type approved
according to EN 12952/EN 12953. These Directives state, among other things, the requirements made on
limiting systems and equipment for steam boiler plants and (pressurised) hot-water installations.
Functional Safety acc. to IEC 61508
The temperature switch TRS 5-50 and the temperature transmitter TRV 5-40 (together with control unit
NRS 1-40.1) in conjunction with temperature sensors TRG 5-6.. are certified to IEC 61508.
This standard
describes the functional safety of safety-related electrical/electronic/programmable electronic
systems.
The equipment combination TRG 5-6.. + TRS 5-50 corresponds to a type B subsystem with Safety
Integrity Level (SIL) 3.
The combination TRG 5-6.. + TRV 5-40 (with NRS 1-40.1) corresponds to a type B subsystem with
Safety Integrity Level (SIL) 2.
According to the European Directive 2014/34/EU the equipment must not be used in explosion-risk
areas.
ATEX (Atmosphère Explosible)
DIN EN 14597
The temperature sensor TRG 5-6.. in conjunction with temperature switches TRS 5-50 and TRS 5-52
or in conjunction with temperature transmitter TRV 5-40 (together with control unit NRS 1-40.1)
is type
approved to DIN EN 14597.
DIN EN 14597 describes and specifies the requirements made on (safety) temperature limiters/monitors.
Approvals for Marine Applications
The temperature sensor TRG 5-6.. in conjunction with
temperature switch TRS 5-50
is approved for
marine applications.
Note on the Declaration of Conformity / Declaration by the Manufacturer
For details on the conformity of our equipment according to the European Directives see our Declaration
of Conformity or our Declaration of Manufacturer.
The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under
www.gestra.com/documents or can be requested from us.

6
Technical data
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
Measuring element (3-wire connection)
TRG 5-63
1 x Pt 100 to EN 60751, class A*)
TRG 5-64
2 x Pt 100 to EN 60751, class A*)
TRG 5-65, TRG 5-66
1 x Pt 100 to EN 60751, up to 300°C class A*), > 300°C class B*)
TRG 5-67
1 x Pt 100 to EN 60751, class B*)
TRG 5-68
2 x Pt 100 to EN 60751, class B*)
Service pressure, service temperature
TRG 5-63, TRG 5-64
Nominal length 100, 160, 250 mm
36 bar at 251°C
Nominal length 400 mm
18 bar at 400°C
TRG 5-65, TRG 5-66
160 bar at 345°C
120 bar at 540°C
TRG 5-67, TRG 5-68
150 bar at 600°C
Admissible flow velocity
TRG 5-63, TRG 5-64
Air 25 m/s
Superheated steam 25 m/s
Water 3 m/s
Nominal length 400 mm
Water 2.4 m/s
TRG 5-65, TRG 5-66, TRG 5-67, TRG 5-68
Air 60 m/s
Superheated steam 60 m/s
Water 5 m/s
Mechanical connection
TRG 5-63, TRG 5-64
Thread G ½ A, ISO 228
TRG 5-65, TRG 5-66, TRG 5-67, TRG 5-68
Welding sleeve
Protection tube, welding sleeve
Dimensions see pages 9, 10

7
Materials
TRG 5-63, TRG 5-64
Protection tube 1.4571, X6CrNiMoTi17122
TRG 5-65, TRG 5-66
Welding sleeve 1.7335
TRG 5-67, TRG 5-68
Welding sleeve 1.4961
Ambient temperature at terminal box
Max. 70°C
Protection
IP 66 to DIN EN 60529
Cable entry / Electrical connection
EMC cable gland with integral cable clamp M 20x1.5
Weight
TRG 5-63, TRG 5-64
approx. 0.5 kg
TRG 5-65, TRG 5-66
approx. 0.6 kg
TRG 5-67, TRG 5-68
approx. 1 kg
Approvals:
EC Type approval PED Pressure Equipment Directive 2014/68/EU,
EN 12952-11, EN 12953-09: Requirements made on limiting equipment
for boilers.
Functional Safety acc. to EN 61508: Functional safety of safety-related electrical/electronic/
SIL 3 programmable/electronic systems
Type approval DIN EN 14597:
Requirements made on safety temperature limiters/monitors
DIN Registration number (see name plate)
TRG 5-6../ TRV 5-40, NRS 1-40.1 DIN safety temp. monitor (/limiter)
STW(STB) 117908
TRG 5-6../ TRV 5-40, NRS 5-40 DIN temp. controller/monitor (TR/TW) 1182
TRG 5-6../ TRS 5-50 DIN safety temp. monitor (/limiter) STW(STB) 1230
TRG 5-6../ TRS 5-52 DIN temp. monitor (TW) 1232
Marine applications In accordance with classification society, GL 47399-12 HH
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
Technical data
Scope of supply
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
1 Temperature sensor
1 Installation manual
- continued -
- continued -

8
Technical data
Name plate / marking
Fig. 1
Equipment designation
Nominal
length
Application
range
Manufacturer
CE Marking
Material number
*) Class A and B, admissible tolerances of the precision resistor
Tolerances of the precision resistor according to EN 60751
Temperature in °C
Admissible deviation in °C
Admissible deviation in Ω
±2
±1.5
±1
±0.5
±4
±3
±2
±1
-200 -100 0 100 200 300 400 500 600 700 800
Class B °C
Class A °C
Class B Ω
Class A Ω
TRG 5-63
0525
L: 100
36 bar / 251°C
STW-STB 117908,1230;TW 1182,1232
392938
Münchener Str. 77 D-28215 BremenGESTRA AG
1x Pt 100
Klasse A
1.4571 IP 65
G
/
12
Measuring element
DIN Registration number
Material number Protection Mechanical
connection Disposal note
- continued -

9
Installation
Dimensions TRG 5-63 and TRG 5-64
Fig. 2
84120
15
∅26
∅9
∅9
1
[mm]
2
[mm]
100 30
160 30
250 30
400 30
27 mm A. F.
G½ A, ISO 228
Fig. 3
Ra 3.2
Ra 12.5
G½ A, ISO 228
∅26
0.5
1Length of protection tube
2Temperature-sensitive length
Key
3Joint ring ∅ 13 x 26
4Sealing surface
4
4
3
27
1
2

10
5
[mm]
6
[mm]
7
[mm]
8
[mm]
9
[mm]
0
[mm]
TRG 5-65 115 30 25 18 40 9
TRG 5-66 140 30 25 18 65 9
TRG 5-67 200 30 25 24 65 12.5
TRG 5-68 200 30 25 24 65 12.5
Installation
Dimensions TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
Fig. 4
84140
8
∅11
7
6
17/24 A. F.
0
Key
5Length of welding sleeve
6Temperature-sensitive length
7Threaded part
8 Diameter of welding sleeve
9Cone-shaped part
0Tip of cone-shaped part
- continued -
5
9

11
Note
nTo install the temperature sensor in a pipe, weld the elbow conto it. This ensures that
the temperature sensitive part 2, 6of the temperature sensor is immersed in the
fluid against the flow direction Fig. 7 and Fig. 8
nInstall the temperature sensor such that the temperature-sensitive part 2, 6is
permanently immersed in the fluid. Fig. 2 and Fig. 4
nThe seating surfaces of the threaded standpipe or the flange provided on the vessel
must be accurately machined, see Fig. 3.
nDo not completely insulate the temperature sensor. See examples of installation in
vessel Fig. 5 and Fig. 6
nOnly qualified welders certified according to EN 287-1 may weld welding sleeves into
lines or vessels.
Attention
Installation
TRG 5-63 and TRG 5-64
1. Check seating surfaces. Fig. 3
2. Put joint ring 3onto the sealing surface of the threaded standpipe or flange provided on the
vessel (select joint ring material according to the range of application). Fig. 3
3. Screw in the temperature sensor and fasten it with an open-end spanner 27 mm A. F. The torque
required when cold is 150 Nm.
TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
1. Provide a penetration for the socket-weld end on site.
2. Unscrew the upper part of the temperature sensor from the welding sleeve 5.
3. Weld the welding sleeve 5in place. Arc-weld the equipment in place, applying welding process
111 and 141 in accordance with ISO 4063.
4. Put copper ring onto welding sleeve 5and screw the upper part of the temperature sensor into
the welding sleeve 5. Fasten the upper part of the temperature sensor when cold with an open-
end spanner (17 or 24 mm A. F.).
Tools
nOpen-end spanner 17 mm A. F.
nOpen-end spanner 24 mm A. F.
nOpen-end spanner 27 mm A. F.
- continued -

12
Installation
Examples of installation
Fig. 5
Fig. 8
c
a
≥ 100
c
Fig. 6
Fig. 7
≥ 100
a
- continued -
b b

13
Electrical connection
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68, terminal box
f
e
d
Fig. 9
g
a
Protection tube / welding sleeve
bThermal insulation
cElbow
dTop of terminal box
eMeasuring insert
fTerminal box
gEMC cable gland M 20 x 1.5
Key

14
Electrical connection
Connecting the temperature sensor
Connecting the measuring element
1. Take cover doff the terminal box f.
2. Unscrew dome nut hof cable gland gand take out the lamellar insert j. Fig. 9 and 10
3. Cut off outer cable sheath mand expose braided screen kover a length of approx. 10 - 15 mm.
4. Push dome nut hand lamellar insert jwith sealing ring ionto the cable m.
5. Bend braided screen koutwards at a right angle (90°).
6. Fold braided screen ktowards outer sheath, i. e. by another 180°.
7. Push lamellar insert jwith sealing ring iinto gland body land turn it briefly around both sides
of the cable axis and snap anti-rotation element into place.
8. Firmly screw on dome nut h.
9. Connect the connecting cable in accordance with the wiring diagram to the measuring element e.
10. Replace cover dand tighten screw securely.
m
Fig. 10
h
ij
k
l
To connect the temperature sensor please use:
nTo connect the temperature transmitter TRV 5-40:
screened four-core cable, e. g. Ölflex 110 CH,
manufactured by Lapp, 4 x 0.5 mm². Max. length 25 m.
nTo connect the temperature switches TRS 5-50 and TRS 5-52: Multi-core screened control cable,
min. conductor size 0.5 mm2, e. g. LiYCY 3 x 0.5 mm2, max. length 100 m.
Note that only the cable gland of the temperature sensor provides the screen.

15
Electrical connection
hDome nut
iSealing ring
jLamellar insert
kBraided screen
lGland body
mScreened cable
Key
Attention
nPlease observe the installation & operating manuals for the temperature transmitter
TRV 5-40 and the temperature switches TRS 5-50 and TRS 5-52.
nMake sure that connecting cables leading to the equipment are segregated and run
separately from power cables.
Wiring diagram for temperature sensor
Note
Additional equipment such as indicating devices can be connected to the terminals marked in
yellow and black of the TRG 5-64 and TRG 5-68.
Tools
nScrewdriver, size 2.5, completely insulated according to DIN VDE 0680-1
nScrewdriver, size 8
- continued -
Fig. 11
5
3
2
6
yellow black
red
TRG 5-63, TRG 5-65,
TRG 5-66, TRG 5-67
TRG 5-64
TRG 5-68
black
TRV 5-40
TRS 5-5..
TRV 5-40
TRS 5-5..

16
Attention
Before carrying out the fault diagnosis please check:
Supply voltage:
Is the temperature transmitter or temperature switch supplied with the mains voltage
specified on the name plate?
Wiring:
Is the wiring in accordance with the wiring diagram?
Troubleshooting
Indication, diagnosis and remedy
Faults indicated by the seven-segment display (TRS 5-52)
or the seven-segment display on the right (TRV 5-40, TRS 5-50)
Error code Error Remedy
E.xxx Temperature sensor defective, temperature
reading too low. Check whether the temperature sensor outputs cor-
rect readings (see Fig. 12). If there are any deviations
please replace the measuring element with a new one.
Check the sensor lines (short circuit, interruption?).
E.xxx Temperature sensor defective, temperature
reading too high.
Measure the fluid temperature
Use table Fig. 12 to ascertain the current temperature of the fluid via the resistance value of the Pt 100.
1. Take cover doff the terminal box .
2. Connect test cable directly to the measuring element e.
3. Use an ohmmeter for measuring the resistance value.
4. Look up the corresponding resistance value in the table, interpolate if necessary and read off the
temperature.
5. After measurement replace cover dand fix it securely in place.
°C 0 10 20 30 40 50 60 70 80 90 100 Ω/deg
0 100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50 0.385
100 138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84 0.373
200 175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03 0.361
300 212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06 0.350
400 247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93 0.338
500 280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65 0.327
600 313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21 0.315
700 345.21 384.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61 0.304
800 375.61 378.59 381.55 384.50 387.45 390.38 0.295
Basic values of the precision resistors according to DIN 43760 for Pt 100.
Fig. 12
Fault code see installation and operating manuals for
temperature transmitter TRV 5-40 and for tempe-
rature switches TRS 5-50 and TRS 5-52.

17
Troubleshooting - continued -
Attention
nRefer to the installation and operating manuals of the temperature transmitter
TRV 5-40 and the temperature switches TRS 5-50 and TRS 5-52 for commissioning,
for more information on indicated fault code E.xxx and for further diagnosis and
troubleshooting.
nPlease replace the measuring element if the temperature measured by the
temperature sensor deviates from the plant temperature.
nThe measuring element must also be replaced by a new one if a malfunction occurred
and the rated service pressure and temperature limits were exceeded.
Replacing the temperature measuring element
The temperature measuring element ecan be replaced during operation if necessary.
1. Disconnect supply voltage (TRV 5-40, TRS 5-50, TRS 5-52).
2. Take cover doff the terminal box .
3. Disconnect the measuring element e.
4. Slacken fixing screws for measuring element. Pull out measuring element.
5. Insert new measuring element and fasten fixing screws.
6. Re-attach the measuring element e.
7. Replace cover dand tighten screw securely.
8. Apply supply voltage.
Safety note
Safety temperature limiters/monitors
are items of equipment with safety function (PED) and must only be
installed, wired and commissioned by qualified and competent staff.
Retrofitting and maintenance work must only be performed by qualified staff who - through adequate
training - have achieved a recognised level of competence.
Temperature sensor type Designation Item Stock code #
TRG 5-65: Nominal length 5= 115 mm, Fig. 4 Measuring element, 1x Pt 100 e392962
TRG 5-66: Nominal length 5= 140 mm, Fig. 4 Measuring element, 1x Pt 100 e392963
TRG 5-67: Nominal length 5= 200 mm, Fig. 4 Measuring element, 1x Pt 100 e392946
TRG 5-68: Nominal length 5= 200 mm, Fig. 4 Measuring element, 2x Pt 100 e392948
Spare Parts

18
Removing and disposing of the temperature sensor
Removing and disposing of temperature sensor TRG 5-63 or TRG 5-64
1. Disconnect supply voltage (TRV 5-40, TRS 5-50, TRS 5-52).
2. Take cover doff the terminal box .
3. Disconnect the measuring element eand pull line mout of the cable gland.
4. Before removing the equipment make sure that is is neither hot nor under pressure.
For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal.
Danger
The temperature sensors TRG 5-63 or TRG 5-64 are screwed into vessels or pipes. When
loosening the temperature sensor steam or hot water might escape! This presents the risk
of severe scalding all over the body!
It is therefore essential not to dismantle the temperature sensor unless the boiler pressure
is verified to be 0 bar.
The temperature sensor becomes hot during operation.
Risk of severe burns to hands and arms.
Before carrying out installation and maintenance work make sure that the equipment is cold.
If faults occur that are not listed above or cannot be corrected, please contact our service centre or
authorized agency in your country.

19
For your Notes

20
818597-05/05-2017cm (808704-05)
·
GESTRA AG
·
Bremen
·
Printed in Germany
GESTRA AG
Münchener Straße 77
28215 Bremen
Germany
Telefon +49 421 3503-0
Telefax +49 421 3503-393
E-mail [email protected]
Web www.gestra.de
Agencies all over the world: www.gestra.de
Table of contents
Popular Temperature Controllers manuals by other brands

METER
METER TEROS 06 manual

American Standard
American Standard ZZSENSAL0400AA Installer's guide

METER
METER RT-1 quick start guide

Advantage
Advantage SENTRA SR Series instruction manual

S+S Regeltechnik
S+S Regeltechnik THERMASGARD ASTF Operating Instructions, Mounting & Installation

Yudian
Yudian AI-208 Operation manual