Yudian AI-208 User manual

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
ARTIFICIAL INTELLIGENCE
TEMPERATURE CONTROLLER
AI-208 (V7.8)
Operation Manual

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
I. Model Order Code
The type of AI-208 is made up of 4 parts:
AI-208 AGL2
Part 1 (Series) Part 2 (Size) Part 3 (Oupt) Part 4 (AUX)
1. (Part 1) Model Series
AI-208, standard temperature controller , 0.3%FS±1℃accuracy.
Multiple thermocouples and RTDs are selectable
Suitable for 0~999℃application. Maximum support two alarms contact output
Universal supply power (100~240VAC)
2. (Part 2) Front panel dimension
Panel Size Front Panel
width×height
Cut Out
width×height Depth Behind Mounting Surface
A1 96×96mm 92×92mm 70mm
B1 160×80mm 152×76mm 70mm
D1 72×72mm 68×68mm 78.5mm
E1 48×96mm vertical 45×92mm 70mm
F1 96×48mm horizontal 92×45mm 70mm
A 96×96mm 92×92mm 100mm
B 160×80mm 152×76mm 100mm
D 72×72mm 68×68mm 95mm
D2 48×48mm 45×45mm 95mm
E 48×96mm 45×92mm 100mm
F 96×48mm 92×45mm 100mm

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
3. (Part 3 and 4) indicate the module installed in OUTP and AUX sockets.
Allowed modules in each socket are as below:
Allowed Type
Module Socket
N L L0/L1 L5 G
3. OUTP (main output) √√
4. AUX (Auxiliary output) √√√
N (or none) no module installed
LRelay contact output module (Capacity: 5A/250VAC, normal open)
L0/L1 Relay contact output module (Capacity: 2A/250VAC, normal open/normal close, spark
absorption at normal open, support AU1 alarm output)
L5 Dual relay output module Output module (Capacity: 2A/250VAC, normal open, support AU1 and
AU2 alarm output)
GSSR voltage output module (30mA/5VDC)
* D1-sized controller is fixed to SSR output(G) and no module option provided, i.e. AI-208-D1-G,
AI-208-D1-G-L0 or AI-208-D1-G-L5 must be specified upon order.
II. TECHNICAL SPECIFICATION
1. Input type : K, E, J, N (thermocouples); Pt100 (resistance temperature detector)
2. Instrument Input range : K, E, J, N (0~+999)℃, Pt100 (0~+800)℃
3. Measurement accuracy : 0.3%FS±1℃
4. Temperature display resolution : 0 or 0.0 (0.0 just for 0~99.9 display)
5. Control mode:
On-off control mode, or
PID control with auto-tuning.
6. Type of Alarm: High limit alarm, Lower limit alarm, Deviation High Alarm and Deviation Low Alarm
with alarm blocking at power on.
7. Power supply voltage rating: 100-240VAC, -15%, +10% / 50-60Hz.
8. Power consumption: ≤2W
9. Ambient temperature: -10~+60℃, Humidity: 0~90RH%

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
III. FRONT PANEL AND OPERATION
① Process Value(PV), or parameter code
② Set Value(SV), alarming code, or value of a parameter
③ Setup key, accessing parameter table, and confirming change.
④ Data shift key, also for activating auto turning
⑤ Data decrease key
⑥ Data increase key
⑦ Status display LED,
OP1 – Output
AU1 – Alarm 1
AU2 – Alarm 2
RUN – Controlling process running
Default display status:
When power is on, the process value (PV) and the set value (SV) are shown. lf the input signal is out of the measurable range (for example,
the thermocouple or RTD circuit is break or input specification is not correctly set), the upper display will blink “orA” and high limit or low
limit of specified input. The instrument will automatically stop the output.
IV. OPERATION DESCRIPTION
● Set Value Setting:
During default display status, if the parameter lock “Loc” isn't locked, user can set setpoint (SV) by pressing YVUkeys. Press V
key to decrease the value, Ukey to increase the value, and Ykey to move to the dot to the desiired digit (acting as a pointer). Keep
pressing Vor Uwill speed up value change. The range of setpoint is limited by parameter SPH with default range 0 to 400.
●Parameter Setting:
During default display status, press and hold 3for 2 seconds will access Field Parameter Table (See V. PARAMETER AND
SETTING). Press 3to proceed to the next parameter. If parameter table have not been locked, press YVUwill change the
parameter. Press and hold Yfor 2 second returns to the preceding parameter. Press Y(don't release) and then press 3
simultaneously jumps out from parameter setting to the default status. The instrument will also jumps out auomatically from the
parameter table if no key is pressed in 30 seconds. Setting Loc=808 and then press 3will access System Parameter Table (See V.
PARAMETER AND SETTING)
●AI artificial intelligence control and auto tuning
When AI artificial intelligence control algorithm is selected (CrL=AI), the P,I, and D parameters can be calculated automatically by
auto-tuning. In default display status, press and hold Yfor 2 seconds, “At” auto-tuning parameter will show. Press Uto change the
value of “At” from “oFF” to “on”, then press 3to activate the auto-tuning. During auto-tuning, the instrument runs on-off control for two
cycles. The instrument will calculate the optimal P, I and D control parameter values and returns to default display. If user want to
interrupt the auto tuning process, press and hold the Yfor 2 seconds. Change “At” from “on” to “oFF” and press 3to confirm. The
auto-tuning process will be cancelled and new P, I and D values will be calculated.
Note 1: The P, I and D parameters obtained from auto-tuning are dependent to the set value. It is recommended to set a set value to an
often-used value or mean value to perform auto-tuning. For the ovens with good heat preservation, the set value can be set at
the highest applicable temperature. Depending on hardware setup, the auto-tuning may take from a few seconds to a few hours.
Note 2: Parameter Ctl (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning. Generally, the smaller the
value of Ctl, the higher the precision of auto tuning. But Ctl parameter value should be large enough to prevent the instrument
from error action around set value due to the oscillation of input. Ctl is recommended to be 2.0.
Note 3: Self-learning function enables the instrument to control better and better after time.

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
V. PARAMETER AND SETTING
Parameter Title Description Range
Field Parameter Table (Press and hold 3for 2 seconds to access)
HIA High limit alarm Alarm on when PV (Process Value) >HIA;
alarm off when PV<HIA-AHY 0~999℃
LoA Lower limit alarm Alarm on when PV (Process Value) < LoA;
alarm off when PV > LoA+AHY 0~999℃
HdA Deviation high
alarm
Alarm on when PV-SV>HdA;
alarm off when PV-SV<HdA-AHY 0~999℃
LdA Deviation low
alarm
Alarm on when PV-SV<LdA;
alarm off when PV-SV>LdA+AHY 0~999℃
Loc Parameter lock
Loc=0: Allowed to change HIA, LoA, HdA, LdA and SV.
Loc=1: Allowed to read only HIA, LoA, HdA, LdA but to change SV.
Loc=2~3: Allowed to change HIA, LoA, HdA. LdA but read only SV.
Loc=4~255: NOT allowed to change any parameters nor SV.
Loc=808, Set to 808 and press 3to unlock the System Parameter Table.
0~255
System Parameter Table (Loc=808 to unlock)
AHY Alarm Hysteresis Avoid frequent alarm on-off action because of the fluctuation of PV
AHY=2 by default. 0~200
AOP Alarm output
assignment
HdA &
(x100)
LdA
LoA
(x10)
HIA
(x1)
0 ±±0 ±0±
1 AU1 ±1AU1 1AU1
2 AU2 ±2AU2 2AU2
5
A
U1
A
U1
6 AU2 AU1
7 ±
A
U1
8 ±
A
U
2
9
A
U1
A
U
2
Example: AOP=901 refers to HdA assigned to AU1, LdA to AU2,
without LoA and HIA to AU1.
0~922
CrL Control mode
zonF : ON-OFF control. When PV>SV, output stops and heating
stops. When PV<SV-AHY, output resumes.
zAI : AI-PID control. The output time proportion can adjusted by
parameter Ctl
Act Acting method
rE: Reverse acting. Increase in measured variable causes a decrease
in the output, such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in
the output, such as refrigerating control.
rEb: Reverse acting with low limit alarm and deviation low alarm
blocking at the beginning of power on.
drb: Direct acting with high limit alarm and deviation high alarm
blocking at the beginning of power on.
rE , dr ,
rEb, drb
P Proportion band
Proportion band in PID with unit ℃or ℉but not the percentage of the
input scale. 1~999
I Time of integral Time of integral in PID. No integral effect when I=0 0~999 sec
d Time of
derivative
Time of derivative in PID with unit 0.1 second. No derivative effect
when d=0 0~999 sec

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
Ctl Control period
Smaller value will result in higher control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 seconds, because small value will
cause the frequent On-Off of mechanical switch and shorten its service
life. Ctl is recommended to be 1/4 – 1/10 of derivative time. When
control under on-off control, Ctl is used as delay time to restart to
protect the compressor.
0.5-300 sec
CHY Control
hysteresis
To avoid frequent relay on-off action, in ON-OFF control mode.
PV > SV, Output turns OFF (Relay opens)
PV < SV-CHY, Output turns ON (Relay closes)
0~200
InP Input
specification
Thermocouples & RTD
0 K
4 E
5 J
7 N
21 Pt100
0~21
dPt Resolution 0 or 0.0 selectable. 0.0 is valid for 0~99.9 ℃ / ℉display
Scb Input shift
Scb is used to make input shift to compensate the error produced by
sensor or input signal.
PV after compensation= PV before compensation + Scb.
-99~+99℃
FIL PV input filter
Higher degree of FIL gives more powerful noise filtering.
Large FIL value stabilized the input signal but the system response
speed will be slow. Generally speaking, 1 to 3 will be used.
If great interference exists, FIL can be gradually increase to limit the
momentary fluctuation among 2 to 5 unit.
When the instrument is being metrological verified, FIL should be set to
0 or 1 to minimize the response time.
0~40
Fru
Selection of
power frequency
and temperature
scale
50C: 50Hz, ℃
50F: 50Hz, ℉
60C: 60Hz, ℃
60F: 60Hz, ℉
SPH Upper limit of SV Maximum value that SV allowed to be.
When SPH=400, the SV range will 0~400℃0~999℃

Yudian (H.K.)Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email:[email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
VI. INSTRUMENT INSTALLATION AND WIRING DIAGRAM
Panel dimension A1, B1, E1 or F1 Panel dimension A, B, E or F
Main Output
Alarm Output
Main Output
Alarm Output
The diagram illustrated is for upright panel dimension A/A1/E/E1.
For panel dimension B/B1/F/F1, please rotate the diagram clockwise by 90 degree.
Panel dimension D (72 x 72mm) Panel dimension D1/D2 (48 x 48mm)
Remarks
1. Thermocouples compensate wires should be directly screwed to the back of the instrument. No extension by normal
conducting wire should be used. Please pay attention to the polarity of the compensate wires.
2. The solid-state relay (SSR) externally connected should provide 2300 V isolation between input/output-to-power line.
(CE requirement)
Table of contents
Other Yudian Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

S+S Regeltechnik
S+S Regeltechnik HYGRASGARD ESFF Operating Instructions, Mounting & Installation

Love Controls
Love Controls C Series instruction sheet

Elitech
Elitech ECS-974neo user manual

iNels
iNels RFTC-150/G/ice manual

Stanton
Stanton SPS5.2 User handbook

Wind & Weather
Wind & Weather RG1736 user manual