Goodlife G Series User manual

G-Series Automatic On/O Timer Instruction Manual
Before Getting Started
2. Operating your Guardian G2 Propane Cannon
Time Indicator
Important: Before installation, ensure the tank valve is closed.
Remove the caps from the gas ttings on the timer. Cut the hose line
between the propane tank regulator and the cannon at a distance of
approximately 4–6”from the tank.
Slide the hose clamps over the end of each hose and t the hoses to
each gas tting. Connect the hose from the propane tank/regulator on
to the left timer gas tting (marked “IN”). Connect the hose from the
cannon on to the right timer gas tting (marked “OUT”). Tighten the
hose clamps over each gas tting.
Remove the front cover by unscrewing the 4 screws in each corner of the timer housing.
Remove the drive unit from the housing and insert the AA battery.
Flip the drive unit over to access the timer unit. The timer unit is a 24-hour timer which
rotates in a counter-clockwise direction. 1 revolution equals a 24-hour day. The timer
automatically sets a daily start/stop time of the propane cannon each day at a specied
time (1 on/o period per day), creating an operational period between 10–19 hours.
To adjust the timer, loosen the milled nut while holding the timer unit. Do not loosen or
remove the milled nut while holding the drive unit. This could damage the drive unit.
1. Installing your G-Series Automatic Timer
2. Setting the Automatic Timer
General Information
• Read entire manual before use.
• Gas cannons and timers are for outside use only.
• Do not smoke when near the device or during operation.
• This timer is intended for use with any Guardian Propane
Scare Cannon. It is intended to operate on LP gas.
• Avoid rough handling of the timer, especially shocks and
bumps, as the device operates on sensitive components.
Gas Fittings: IN OUT
• The timer cannot be used at temperatures below 14°F (-10°C).
• To avoid leakage, keep the gas hose and ttings free of dust and debris.
• Warning:To prevent gas leakage, do not dismantle any parts in the valve assembly or timer drive unit. The timer has certain
components that can only be repaired by trained technicians.
Please note, the timer does not regulate the time between cannon blasts; the gas regulator controls blast frequency. The
automatic timer controls gas ow to the cannon at specied times (one on/o period per day).
Included In Your Package
G-Series Automatic On/O Timer
Hose Clamp (2)
AA Battery
Drive Unit
Timer
Housing
Timer
Unit

G-Series Automatic On/O Timer Instruction Manual
Setting The Operating Time
The Timer Unit is composed of 4 parts:
1. The Milled Nut: loosens and tightens in order to adjust the
timing settings.
2. The 24-hour Timer: Used to set time of day and timing
interval for cannon operation.
3. The Upper Cam Disc: Selects start time of cannon
operation.
4. The Lower Cam Disc: Selects stop time of cannon
operation.
NOTE:The upper and lower cam discs open the gas valve by
raising the internal lever as the timer unit rotates. When the
cam discs are in the ‘o’ position, a space of 3/8” to 5/8” should
been seen between the lever and cam discs. Lowering the lever
stops the gas ow.
Hold the timer unit still to loosen the milled nut. Align the
24-hour Timer so that the actual time of day points to the time
indicator line located to the upper right of the drive unit.
NOTE: The timer is based on military time. For example, “15”
corresponds to 3:00pm.
Turn the upper cam disc (just beneath the 24-hour timer) so
that the left corner peak corresponds to the required starting
time (start), and turn the lower cam disc so that the end (right)
corner corresponds to the required end time (stop).
Once the operating time is set, tighten the milled nut while
holding the timer unit in place. Flip the drive unit over
and insert it back into the housing unit so that the battery
compartment is facing outward.
Place the front cover back on the housing unit. Ensure the
screws are properly tted and that the cover and housing are
tightly sealed to prevent moisture from entering the housing.
Open the valve on the propane tank. The timer will now
operate automatically.
Store the timer in a dry and dust-free location when not in use.
For long-term storage, remove the battery and protect the gas
ttings by placing the caps back on each tting. Install a new
battery at the beginning of each operating season.
In the above example, the current time is 3:00pm. The number 15 on
the 24-hour timer points to the current time indicator.
The cannon is set to operate between 6:00am and 6:00pm, as set by
the upper and lower cam discs. The starting point, or left corner, of
the upper cam disc points to the digit 6 on the 24-hour timer. The
end point, or right corner, of the lower cam disc points to the digit
18 on the 24-hour timer.
Note that the cam discs create a continuous raised edge that
will manually raise the internal lever to allow gas ow.
15
18
6
More Details
Toll Free: 1-800-657-8214
Outside US: 1-541-245-4488
Website:
pestrepellerultimate.com
Email:
We’re Here to Help
Contact Us
Don’t worry, we’ve got you covered! Your cannon is backed by our 1-Year Manufacturer’s Warranty, which protects against
any defects due to manufacturing. For more information, go to pestrepellerultimate.com/pages/warranty. Please visit
pestrepellerultimate.com and start a chat with one of our friendly customer service agents, or contact us using the information
below.
Time
Indicator
Lower
Cam Disc
Upper
Cam Disc
Milled
Nut
Start Time
End Time
24-hour
Timer
Table of contents
Popular Timer manuals by other brands

Dewenwils
Dewenwils HPST16M instruction manual

Component Design
Component Design TM8 operating instructions

Orbit
Orbit WaterMaster 57114 installation manual

Intermatic
Intermatic EI205 Series instructions

Autonics
Autonics FXS Series product manual

Orbit
Orbit WaterMaster 57674 Installation manual & users manual