
13
It is the responsibility of the installer to follow the manufacturers’
recommendationsandtoverifythatallvent/fluepipingandconnec-
tors are compatible with furnace flue products. Additionally, it is
theresponsibilityoftheinstallerto ensure thatall piping and con-
nectionspossessadequatestructuralintegrityandsupporttopre-
ventfluepipeseparation,shifting,orsaggingduringfurnaceopera-
tion.
DUALCERTIFICATION:NON-DIRECT/DIRECTVENT
Thisfurnaceisdualcertifiedandmaybeinstalledasanon-direct
vent(singlepipe)ordirectvent(dualpipe)appliance. Anon-direct
ventinstallation requires only avent/flue pipe, whilea directvent
installation requires both a vent/flue pipe and a combustion air
intakepipe. Refertotheappropriatesectionfordetailsconcerning
piping size, length, number of elbows, furnace connections, and
terminations.
T
O
AVOID
BODILY
INJURY
,
FIRE
OR
EXPLOSION
,
SOLVENT
CEMENTS
MUST
BE
KEPT
AWAY
FROM
ALL
IGNITION
SOURCES
(
I
.
E
.,
SPARKS
,
OPEN
FLAMES
,
AND
EXCESSIVE
HEAT
)
AS
THEY
ARE
COMBUSTIBLE
LIQUIDS
.
A
VOID
BREATHING
CEMENT
VAPORS
OR
CONTACT
WITH
SKIN
AND
/
OR
EYES
.
WARNING
Two-orthree-inchnominaldiameterPVCSchedule40pipemeet-
ing ASTM D1785, PVC primer meeting ASTM F656, and PVC
solventcementmeetingASTMD2564specificationsmustbeused.
Fittings must be DWV type fittings meeting ASTM D2665 and
ASTM D3311. Carefully follow the pipe manufacturer’s instruc-
tionsfor cutting, cleaning,andsolventcementingofPVC.
Theuseof Schedule 40PVCorABS cellularcore (FoamCore)
plasticpipeisalsoacceptableasaflue/ventandintakepipemate-
rial. PVC primer meetingASTM F656 and PVC solvent cement
meetingASTMD2564specificationsmustbeused.Fittingsmust
be DWV type fittings meeting ASTM D2665 andASTM D3311.
Carefullyfollowthemanufacturesinstructionsforcutting,cleaning
andsolventcementingofPVC.
MATERIALSANDJOININGMETHODS
AsanalternativetoPVCpipe,primer,solventcement,andfittings,
ABSmaterialswhichareincompliancewiththefollowingspecifi-
cations may be used. Two-or-three-inchABS Schedule 40 pipe
must meetASTM D1527 and, if used in Canada, must be CSA
listed. Solvent cement for ABS to ABS joints must meet ASTM
D2235 and, if used in Canada, must be CSA listed. The solvent
cementforthePVCtoABStransitionjointmustmeetASTMD3138.
Fittings must be DWV type fittings meeting ASTM D2661 and
ASTMD3311and,ifusedinCanada,mustbeCSAlisted. Care-
fully follow the manufacturers’ instructions for cutting, cleaning,
andsolventcementingPVCand/orABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long
radius (Long sweep 1/4 bend DWV) types conforming toASTM
D3311. Amediumradius (1/4 bendDWV) elbowmeasures3 1/
16”minimumfromtheplaneofoneopeningtothecenterlineofthe
other opening for 2” diameter pipe, and 4 9/16” minimum for 3”
pipe.
PROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES
Adhere to these instructions to ensure safe and proper furnace
performance.Thelength,diameter,andnumberofelbows ofthe
vent/flue pipe and combustion air pipe (when applicable) affects
the performance of the furnace and must be carefully sized. All
pipingmustbeinstalledinaccordancewithlocalcodesandthese
instructions.
Pipingmustbeadequatelysecuredandsupportedtoprohibitsag-
ging,jointseparation,and/ordetachmentfromthefurnace. Hori-
zontalrunsofvent/fluepipingmustbesupportedeverythreetofive
feetandmust maintain a 1/4 inch perfootdownwardslope,back
towardsthefurnace,toproperlyreturncondensatetothefurnace’s
drain system. Allowances should be made for minor expansion
and contraction due to temperature variations. For this reason,
particularcaremustbetaken to securepiping when along run is
followedby a shortoffsetof less than40inches.
Precautionsshouldbetakentopreventcondensatefromfreezing
insidethevent/fluepipeand/oratthevent/fluepipetermination. All
vent/fluepipingexposedtotemperatures below 35°Fforextended
periodsoftimemustbeinsulatedwith1/2”thickclosedcellfoam.
Alsoall vent/flue pipingexposed outdoorsinexcess of thetermi-
nationsshowninthismanual(orinunheatedareas)mustbeinsu-
latedwith1/2” thickclosedcellfoam. Inspectpipingforleaksprior
to installing insulation.
TERMINATIONLOCATIONS
NOTE: RefertoLocationRequirementsandConsiderationsfor
combustionair contaminantrestrictions.
The following bullets and diagram describe the restrictions con-
cerningtheappropriatelocationofvent/fluepipeandcombustion
airintakepipe(whenapplicable)terminations. RefertoNon-Direct
Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping lo-
cated in this section for specific details on termination construc-
tion.
• All terminations (flue and/or intake) must be located at
least12inchesabovegroundlevelortheanticipatedsnow
level.
• Vent terminations (non-direct and direct vent) must
terminateatleast3feetaboveanyforcedairinletlocated
within10feet.
NOTE: Thisprovisiondoesnotapplytothecombustion
airintaketerminationofadirectventapplication.
• Theventterminationofanon-directventapplicationmust
terminate at least 4 feet below, 4 feet horizontally from,
or1footaboveanydoor,window,orgravityairinletinto
anybuilding.
• The vent termination of a direct vent application must
terminate at least 12 inches from any opening through
whichfluegasesmayenterabuilding(door,window,or
gravityairinlet).
• Theventterminationofventpiperunverticallythrougha
roofmustterminateatleast12inchesabovetheroofline
(ortheanticipatedsnowlevel)andbeatleast12inches
from any vertical wall (including any anticipated snow
buildup).