765041996 Rev. 001 10
Working setpoint and configuration parameters
PARAM. MIN. MAX. U.M. DEF.
GRAMFG
HAV
GRAMKG
HAV
GRAMFG
FAV
GRAMKG
FAV WORKINGSETPOINT
SP r1 r2 °C/°F(1) 0 ‐18 5 ‐18 5
workingsetpoint;seealsor0andr12
PARAM. MIN. MAX. U.M. DEF.
GRAMFG
HAV
GRAMKG
HAV
GRAMFG
FAV
GRAMKG
FAV ANALOGINPUTS
CA1 ‐25 25 °C/°F(1) 0
0 0 0 0
ifP4=0,1or2,roomprobeoffset
ifP4=3,incomingairprobeoffset
CA2 ‐25 25 °C/°F(1) 0 0 0 0 0
evaporatorprobeoffset
CA3 ‐25 25 °C/°F(1) 0 0 0 0 0
ifP4=1,condenserprobeoffset
ifP4=2,criticaltemperatureprobeoffset
ifP4=3,outgoingairprobeoffset
P0 0 1 ‐‐ 1 1 1 1 1
probetype
0=PTC
1=NTC
P1 0 1 ‐‐ 1 0 0 0 0
degreeCelsiusdecimalpoint(duringnormaloperation)
1=YES
P2 0 1 ‐‐ 0 0 0 0 0
unitofmeasurementfortemperature(2)
0=°C(Celsiusdegree;resolutiondependsonP1parameter)
1=°F(Fahrenheitdegree;resolutionis1°F)
P3 0 2 ‐‐ 1 1 1 1 1
evaporatorprobefunction
0=absentprobe
1=defrostprobeandprobedeterminingtheactivityoftheevaporatorfan
2=probedeterminingtheactivityoftheevaporatorfan
P4 0 3 ‐‐ 0 1 1 0 0
fourthinletfunction
0=multifunctioninput(digitalinput)
1=condenserprobe(analoginput)
2=criticaltemperatureprobe(analoginput)
3=outletairprobe(analoginput)(3)
P5 0 4 ‐‐ 0
0 0 0 0
magnitudedisplayedduringnormaloperation
0=ifP4=0,1or2,roomtemperature
ifP4=3,CPTtemperature
1=workingsetpoint
2=evaporatortemperature
3=ifP4=0,“‐‐‐”
ifP4=1,condensertemperature
ifP4=2,criticaltemperature
ifP4=3,outletairtemperature
4=ifP4=0,1o2,“‐‐‐”
ifP4=3,inletairtemperature
P7 0 100 % 50 50 50 50 50
inflowingairtemperaturepercentageforthecalculationoftheCPTtemperature
P8 0 250 0,1s S 100 100 100 100
delayeddisplayoftemperaturechangesasdetectedbytheprobes
PARAM. MIN. MAX. U.M. DEF.
GRAMFG
HAV
GRAMKG
HAV
GRAMFG
FAV
GRAMKG
FAV MAINREGULATOR
r0 0,1 15 °C/°F(1) 2 4 4 4 4
workingsetpointdifferential;seealsor12
r1 ‐99 r2 °C/°F(1) ‐40 ‐20 2 ‐20 2
minimumworkingsetpoint
r2 r1 99 °C/°F(1) 50 ‐10 12 ‐10 12
maximumworkingsetpoint
r4 0 99 °C/°F(1) 0 0 0 0 0
workingsetpointincreaseduringthe“energysaving"function;seealsoi5,i10andHE2
r5 0 1 ‐‐ 0 0 0 0 0
coolingorheatingoperation(4)
0=cooling
1=heating
r6 0 99 °C/°F(1) 0 0 0 0 0
ifr5=0,workingsetpointdecreaseduringthe“rapidcooling”function(onlyifr8=1);seealsor7
ifr5=1,workingsetpointincreaseduringthe“rapidheating”function(onlyifr8=1);seealsor7
r7 0 240 min 30 0 0 0 0
ifr5=0,“rapidcooling”functionduration(onlyifr8=1);seealsor6
ifr5=1,“rapidheating”functionduration(onlyifr8=1);seealsor6
r8 0 2 ‐‐ 0 0 0 0 0
thisfunctioncanbeenabled/disabledwiththekeyFNCV
0=none
1=ifr5=0,“Rapidcooling”function
ifr5=1,“Rapidheating”function
2=“energysaving”function(onlyifr5=0)
r12 0 1 ‐‐‐ 1 1 1 1 1
workingsetpointdifferentialtype
0=asymmetric
1=symmetric
PARAM. MIN. MAX. U.M. DEF.
GRAMFG
HAV
GRAMKG
HAV
GRAMFG
FAV
GRAMKG
FAV COMPRESSORPROTECTIONSYSTEM
C0 0 240 min 0 0 0 0 0
delayinswitchingonofcompressorafterthedeviceswitcheson(5)
C2 0 240 min 3 3 3 3 3
minimumcompressorswitch‐offduration(6)
C3 0 240 s 0 180 180 180 180
minimumdurationofcompressorswitchontime