Section 5: ElectricalPage 14
panel to the side panels, hinge the panel forward and allow it to
drop down to gain access to the top of the panel.
3. Remove the two screws securing the terminal block cover and
lift off the cover.
4. Remove the screws securing the cable clamp and open clamp.
5. Route the supply cable through the hole in the rear panel (using
the grommet supplied) and up to the control panel
6. Pass the 4-core cable through the cable clamp and connect to
the boiler control panel terminals as follows:
• Green/Yellow to mains earth (terminal 1)
• Blue to mains neutral (terminal 2)
• Brown to mains live (terminal 3)
• Black to switched live (terminal 19)
On Internal models - pass the 3-core cable from the pump
through the cable clamp and connect to the boiler control
panel terminals as follows:
• Green/Yellow to pump earth (terminal 4)
• Blue to pump neutral (terminal 5)
• Brown to pump live (terminal 6)
7. Tighten the cable clamp and refit the terminal block cover
8. Re-connect the electrical supply and check operation of
heating system controls (programmer, room thermostats, etc.).
9. Refer to Instructions provided with the programmer for
operation and setting.
10. Leave the Programmer and Thermostat Instructions with the
user after installation for their future reference.
5.3.2 Circulating Pump
On the Internal System models, the circulating pump is factory
fitted within the boiler enclosure and the pump is wired to the pump
terminals on the control panel terminal block.
On Internal models the pump should also be connected directly to
the control panel terminal block. Refer to Section 5.3.1.
Connected this way allows the pump to be isolated using the
Boiler ON/OFF switch, on the boiler control panel, for servicing or
maintenance work.
Also, the boiler control automatically provides a short pump 'overrun'
(two minutes) after the burner is shut down (when the heat demand
is interrupted), e.g. when the room thermostat is satisfied. This
pump overrun will not occur if the boiler power supply is interrupted,
e.g. if the boiler ON/OFF switch is set to off.
5.4 VortexBlue Ex ternal Modules
5.4.1 Connecting Power Supply, Pump and Control System
The boiler requires both a switched live, from an external
programmer or control system, in addition to a permanent live
power supply.
Do not interrupt the permanent mains supply to the boiler
with any external control, e.g. a timer, programmer, or room
thermostat.
NOTE
!
The boiler must be wired as shown in Figures 5-4 and 5-5, i.e.
with both a permanent live supply AND a separate switched
live (from the heating system controls).
No permanent live supply to the boiler can result in damage
to the burner. This will not be covered by the boiler product
guarantee.
!WARNING
There is no facility in the Grant VortexBlue External Module for the
fitting of a plug-in timer or programmer.
A 4-core cable (3-core and earth) is required to connect the power
supply and heating controls to the boiler.
A 3-core cable (2-core and earth) is required to connect the
circulating pump to the boiler.
For control system wiring, refer to Figures 5-4 and 5-5.
Ensure that the route and length of the supply cable is such
that the boiler control panel can be fully hinged down without
disconnecting the supply cable from the terminal block.
NOTE
!
The procedure is as follows:
1. Remove the module front door panel, if it has not already been
removed.
2. Remove the four screws securing the front of the control panel
and allow it to drop down to gain access to the top of the
panel.
3. Remove the screws securing the cable clamp and open clamp.
4. Route the supply and pump cables up to the control panel.
5. Pass the 4-core cable through the cable clamp and connect to
the boiler control panel terminals as follows:
• Green/Yellow to mains earth (terminal 1)
• Blue to mains neutral (terminal 2)
• Brown to mains live (terminal 3)
• Black to switched live (terminal 19)
6. Pass the 3-core cable from the pump through the cable clamp
and connect to the boiler control panel terminals as follows:
• Green/Yellow to pump earth (terminal 4)
• Blue to pump neutral (terminal 5)
• Brown to pump live (terminal 6)
7. Tighten the cable clamp and refit the front of the control panel.
8. Re-connect the electrical supply and check operation of
heating system controls (programmer, room thermostats, etc.).
9. Refer to Instructions provided with the programmer for
operation and setting.
10. Leave the Programmer and Thermostat Instructions with the
user after installation for their future reference.
5.4.2 Connection of the Circulating Pump
The circulating pump should be connected directly to the control
panel terminal block. Refer to Section 4.4.1.
Connecting the pump in this way allows it to be isolated using the
Boiler On/Off switch, on the boiler control panel, for servicing or
maintenance work.
Also, when the pump is connected this way, the boiler control
automatically provides a short pump 'overrun' (2 minutes) after the
burner has shut down (when the heat demand is interrupted), e.g.
when the room thermostat is satisfied. This pump overrun will not
occur if the boiler power supply is interrupted, e.g. if the boiler ON/
OFF switch is set to off.
5.5 VortexBlue Internal Combi and Ex ternal Combi
Boilers
5.5.1 Connecting the Power Supply and Control System
For details on the electrical installation requirements for the Combi
or External Combi, please refer to Section 8 of the Installation
Instructions supplied with this boiler.