USER'S GUIDE
Installation & Operation
Instructions
Level & Flow Monitor
Model SLT 5.0
Manual Series B.1.4

Note: This page has been left blank intentionally.

Page 3
SLT 5.0 Level and Flow Monitor
INDEX
CONNECTIONS: ...............................................................................................4
KEYPAD SYSTEM............................................................................................6
CALIBRATION MENU.....................................................................................7
RUN....................................................................................................................8
MESSAGE..........................................................................................................8
STATUS..............................................................................................................8
PASSWORD.......................................................................................................9
UNITS/MODE..................................................................................................10
CALIBRATION................................................................................................11
CHANNEL SETUP ..........................................................................................14
RELAY PARAMETERS..................................................................................15
SPECIAL FUNCTIONS...................................................................................16
SENSOR MOUNTING/LOCATION...............................................................18
SENSOR MOUNTING METHODS ................................................................20
APPLICATIONS HOTLINE............................................................................27
PRODUCT RETURN PROCEDURE ..............................................................28
APPENDIX A - OPTIONS...............................................................................30
DATA LOGGING (Optional)...........................................................................33
CONVERSION GUIDE ...................................................................................35
SPECIFICATIONS...........................................................................................36
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
Available in Adobe Acrobat pdf format

Page 4
SLT 5.0 Level and Flow Monitor
CONNECTIONS:
POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz . No
adjustments are necessary for voltages within this range.
Optional DC input model requires 9-32 VDC/9 Watts. Connect to + and - terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with CE electrical safety standards, AC power input and relay
connection wires must have conduit entry to the instrument enclosure. Installation requires a switch,
overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked
as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V).

Page 5
SLT 5.0 Level and Flow Monitor
CONNECTIONS

Page 6
SLT 5.0 Level and Flow Monitor
KEYPAD SYSTEM
The following diagram shows the SLT 5.0 menu system. Arrows show the four directions to leave a
menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown.
Move the cursor (underline) under numerals and increase or decrease numerals with the and keys.
To store calibration values permanently (even through power interruptions), press the .

Page 7
SLT 5.0 Level and Flow Monitor
CALIBRATION MENU

Page 8
SLT 5.0 Level and Flow Monitor
RUN
The main display shows the units selected from the Units/Mode menu, Level,
Range, Flow, HRT, and Volume rate being measured, TOTALIZER and RELAY
states. The SLT 5.0 will start-up with this display and will return to this screen
after a timeout if keys are not pressed in other menus.
MESSAGE
Press from the RUN display to view status of the data logger and error/warning
messages provided by the instrument. The word Message will appear on the RUN
display if error messages are being generated by the instrument. Refer to the
manual section Error/Warning Messages for a description. Press to return to the
main display.
STATUS
Press from the RUN display to view instrument status. Range will be displayed
in linear units.
Tot Displays the current totalizer reading.
EC Displays echo confidence.
Relays Energized relays will display as a white character on a black
background.
24 HR LOG (Data Logging option only)
Press from the RUN display to view a formatted flow report from instruments
with a built-in data logger. Press to scroll down one day or repeatedly to scroll
to a specific date. Up to 365 days can be stored. Newest date will overwrite the
oldest. Press to return to the main display.

Page 9
SLT 5.0 Level and Flow Monitor
PASSWORD
The password (a number from 0000 to 9999) prevents unauthorized access to the
Calibration menu.
From the Run display press the key to get to Password. Factory default
password is 0000 and if it has not been changed press the to proceed to the
Menu Selections screen.
If a password is required, press to place the cursor under the first digit and or
to set the number, then to the second digit, etc. Press or to proceed to
the Menu Selections screen.
A new password can be stored by going to Special Functions/New Password.

Page 10
SLT 5.0 Level and Flow Monitor
UNITS/MODE
From Mode press the and then the or to select Level,Range, Flow,
HRT or Volume.
Range mode displays distance from the sensor to the target or liquid surface
like a tape measure. Range mode is useful to measure the exact
distance from the sensor to the zero level during calibration, or to
monitor "outage" or free space in a tank.
Level mode can be used to measure tank level in linear units, or "Head"
(height of flow) in an open channel for comparison with a flume
manufacturer's flow tables.
Volume Volume mode displays tank inventory in engineering units like
gallons or liters.
HRT Horizontal Round Tank mode sets the SLT 5.0 to calculate and
display volume units in a horizontal round tank.
Flow mode is for open channel flow through a flume or weir.
From Volume HRT or Flow press to make your selection. (Range or
Level mode will bypass the Volume units selection menu). Volume Hrt or Flow
modes will give you the additional choice of volumetric units:
ft3 - cubic feet
USG - US gallons
USMG - US million gallons (FLOW only)
IG - Imperial gallons
IMG - Imperial million gallons (FLOW only)
m3 - cubic meters
L - liters
bbl - U.S. oil barrel
Press the to store your selection then the to the next menu item and to
enter.
Linear
press the key and then the or to select your units
of measurement. Press the to store your selection.
Time
press and then or to select day, hr, min or
sec.
Temperature
press and then or to select Cor F
(Centigrade or Fahrenheit).
Press or to return to the Menu Selections screen.

Page 11
SLT 5.0 Level and Flow Monitor
CALIBRATION
Press the to Calibration and to enter. Use or to position before
each menu item and to enter. When settings are completed press to store and
return to the Calibration menu.
Min Range Distance from the sensor face to highest expected level.
Max Range Distance from sensor to Zero level
MaxVol For Volume and HRT mode only. Enter the maximum volume of
the vertical or horizontal tank.
Damping Minimum damping allows fast response to level changes.
Increasing damping slows the SLT 5.0's response to level changes
and is ideal to smooth the display and outputs in turbulent
conditions. Damping value is shown in percent (0-99%). Some
experimentation may be required to select the optimum damping
value. A value of 1% is recommended for most applications. For
fast level changes (up to ½ inch/sec - 13 mm/sec), a Damping
value of 1% is recommended.
LOE Time Press and or to change the number of seconds without
receiving an echo before the SLT 5.0 displays ECHO LOSS, and
Control relays change state as calibrated under Relay Parameters.
Factory default is 30 seconds and is recommended for most
applications, Minimum is 1 second and maximum is 99 seconds.
Press from the Units/Mode display to return to Menu Selections.

Page 12
SLT 5.0 Level and Flow Monitor
CALIBRATION
- for Level/Inventory Applications
1. Before starting the calibration determine:
a) MAX RANGE = ________________ (Maximum
range = distance from Sensor to Zerolevel)
b) MAX LEVEL = ________________
(Maximum level of product being measured)
c) MIN RANGE = ________________
(Distance from sensor to Max Level)
Minimum range = MAX RANGE - MAX LEVEL
(must be at least 8" / 203 mm depending on sensor model)
2. Check the maximum range with the sensor installed by:
a) When liquid is at zero level press to view the Range reading in the
Status menu. Use this range measured by the SLT 5.0 as the Max Range
setting.
or
b) Carefully measure distance from sensor to zero level with a tape measure,
and use this measurement as the Max Range setting.
MINIMUM RANGE:
At CALIBRATION
- Press to get to Min Range
- Press to move the cursor under the digits
- Use or to set the minimum range
Note: Min Range must be at least 12" (30.5 cm) for PZ32T sensors, 16" (40.6 cm)
for PZ52T and PZ34 sensors and 8" for PZ15 sensors. For correct tank volume
calculation in Hrt mode Min Range must be the actual distance from the end of
the sensor to the top of the tank.
MAXIMUM RANGE:
Press to get to Max Range
Enter Max Range determined above.

Page 13
SLT 5.0 Level and Flow Monitor
CALIBRATION
- for Open Channel Flow
1. Before starting the calibration determine:
a) MAX RANGE = ____________________
(Maximum range = distance from the Sensor to Zero flow point)
b) MAX LEVEL = ____________________
(Maximum level of flow through flume or weir)
c) MIN RANGE = __________________
(Distance from sensor to Max Level)
Minimum range = MAX RANGE - MAX LEVEL
(must be at least 8" / 20.3 cm depending on sensor model).
2. Check the maximum range with the sensor installed by:
a) When liquid is at zero level press to view the Range reading in the
Status menu. Use this range measured by the SLT 5.0 as the Max Range
setting.
or
b) Carefully measure distance from sensor to zero level with a tape measure,
and use this measurement as the Max Range setting.
NOTE: The SLT 5.0 will not detect targets beyond user entered MaxRg.

Page 14
SLT 5.0 Level and Flow Monitor
CHANNEL SETUP

Page 15
SLT 5.0 Level and Flow Monitor
RELAY PARAMETERS
Relay Press and or to select a corresponding relay number (2
relays are standard, 4 additional are optional).
Function Press or to select Off, Temperature, Pulse and
Level.
Temperature References temperature reading from the
SLT 5.0 ultrasonic sensor (air temperature
at the sensor location). Press and and
set the relay On and Off set points.
Pulse Press and set digits to the flow volume
increment required between relay pulses.
Use this feature for remote samplers,
chlorinators or totalizers. Minimum time
between pulses is 2.25 seconds and pulse
duration is 350 milliseconds.
Level Press to Mode and to select Pump,
Low Alarmor Hi Alarm.
Note: Function setting Level will change according to selections made under
Units/Mode eg Level,Range,Flow, Volume or HRT.
Press to return to Menu Selections.
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.

Page 16
SLT 5.0 Level and Flow Monitor
SPECIAL FUNCTIONS
Language Select English, French or Spanish and press .
Analog Out Select 4-20mA or 0-5V mode for the analog output.
Backlight Select High, Medium or Low for continuous
backlight.
Select Key Hi/Lo for high backlight for 1 minute
after a keypress and then Lo backlight until a key is
pressed again.
Select Key High, Med or Low for backlight for 1
minute after a keypress and then backlight off until a
key is pressed again.
Reset Totalizer Press and select Yes to erase and restart the
totalizer at zero.
Restore Defaults Select Yes and press to erase all user settings and return
the instrument to factory default settings
New Password Select any number from 0000 to 9999 and press .
Default setting of 0000 will allow direct access to the
calibration menus. Setting of any password greater
than 0000 will require the password to be entered to
access the calibration menus.
Press to return to Menu Selections.

Page 17
SLT 5.0 Level and Flow Monitor
SIMULATION
Exercises the 4-20mA (0-5V) output, digital display and control relays.
Test Select Maximum and press to simulate maximum Flow, Range or
Level and to output 20mA (5V) to the analog channel.
Select Minimum and press to simulate minimum Flow, Range or
Level and to output 4mA (0V) to the analog channel.
To simulate and intermediate Flow, Range or Level set Test to Actual
and then enter a value for the Flow, Range or Level. The analog
output and control relays will respond to the simulated value.

Page 18
SLT 5.0 Level and Flow Monitor
SENSOR MOUNTING/LOCATION
- Tank Level/Inventory Applications
Each SLT 5.0 Level Transmitter includes a non-
contacting ultrasonic sensor. The sensor must be
installed in a position to obtain unobstructed echoes
from the liquid or material being measured.
Mount the sensor away from pipes, ladders, or
structural members which might cause continuous false
echoes.

Page 19
SLT 5.0 Level and Flow Monitor
SENSOR MOUNTING LOCATION
- Tank Level/Inventory Applications
SENSOR MOUNTING
Each sensor is equipped with a ¾ inch "isolation coupling" which MUST be used in your installation. A
threaded nipple or length of conduit may be used to position the sensor at the desired height.
The sensor should be hand-tightened (like a light bulb) by turning the sensor stem only. DO NOT use a
wrench and do not over tighten. DO NOT clamp the sensor below the isolation coupling.

Page 20
SLT 5.0 Level and Flow Monitor
SENSOR MOUNTING METHODS