
BACnet programming of
FlowCon Intelligent Interface
In this instruction:
AV = Analog Value
BV = Binary Value
MSV = Multi-State Value.
Default values are underlined.
Please also see FlowCon FIT BACnet PICS.
After completing Quick Start-up Sequence set-
ting Baud Rate (MSV.1), MAC Address (MSV.2)
and FIT Configuration (MSV.5) and re-connect-
ing power at specific location start by selecting
your PICV valve in MSV.7:
1 = Green.0 2 = Green.1
3 = Green.2 4 = Green.3
Hereafter trim the pressure sensors (if a solu-
tion with pressure sensors is selected). To trim
the pressure sensors, please check via BACnet
AV.13 (Pressure1) and AV.14 (Pressure2) which
show simple read-out from the two pressure
sensors. Before installation in the system or
withdrawn from the system, the pressure sen-
sors should both read zero (= related to atmo-
spheric pressure). Any deviation from zero shall
be deducted in AV.16 (Press1Correct) and AV.17
(Press2Correct) respectively. If AV.13 reads 10
and should be zero, then value in AV.16 is en-
tered to -10. It is also possible to calibrate based
on another known pressure entity than ATM.
Select flow unit in MSV.39:
1 = l/sec 2 = GPM 3 = l/hr
Select pressure unit in MSV.6:
1 = kPa 2 = psi
Select temperature unit in MSV.3:
1 = °C 2 = °F
Finally select FIT control mode in MSV.4:
1 = ΔT Control
2 = Comfort Control
3 = Smart Control
When set to direct ΔT Control, FlowCon FIT will
work as an energy valve and regulate based
on ΔT target alone. When set to direct Comfort
Control, FlowCon FIT will work as a PICV for
room comfort control. When set to Smart Con-
trol, FlowCon FIT will prioritize room tempera-
ture setting and within designated range, opti-
mize the ΔT.
Provide analog control signal in AV.141 (0% to
100%).
Condition of the FIT System
through BACnet
Besides checking object values already described,
the following information is available through
BACnet.
Please also see FlowCon FIT BACnet
PICS:
Check the current flow rate (not measured)
in AV.68. To know whether the valve is fully
closed, please check the motor position in AV.98
(0%=fully closed). Set max.flow can be changed
or confirmed in AV.62.
Check P1, P2 and ΔP in
AV.13, AV.14 and AV.15.
ΔP alarm can be seen in BV.1.
Valid output only on a solution with pressure
sensors.
Check Water Temperatures T1, T2 and ΔT
in AV.1, AV.2 and AV.3. ΔT Target is changed
or confirmed in AV.4. ΔT Target Deadband is
changed in AV.5
Check Room Temperature in AV.6 and Room
Temperature Target in AV.7. Room Tempera-
ture Deadband is changed in AV.8. Control in-
terval for all water- and room temperatures is set
in AV.9
Check current BTU, accumulated BTU for the
last month and accumulated BTU for the last
year in AV.10, AV.11 and AV.12.
This paper is a supplement to the FlowCon General Instruction
Latest release of any FlowCon material is available on www.owcon.com
FlowCon FIT-G DN40-50 (1 1/2”-2”)
1B95099 - 08/2022
Page 8 of 8