GSL electronics UPS240-1210 User manual

Page 1 of 2
Model:
UPS240-1210
Unit 2, 110 Station Road, Seven Hills ,NSW, 2147, Australia
12 Volt 10 Amp Switchmode
Uninterruptable Power Supply
Operating Instructions
Please read these instructions before use
The unit is for bench mounted operation providing approx. 13.65VDC at 10Amps. An output mating connector kit is provided
with each unit. The unit has been designed specifically for telecommunications applications demanding high reliability under
heavy usage with low noise, fully automatic and unattended operation.
Applications:
Power Supply Mode: It may be used to power equipment that normally runs on a 12 Volt battery e.g. mobile
communication equipment. The unit will run loads requiring up to 10 Amp output. It is fully protected against overload and
short circuit and also incorporates overvoltage shut down facility.
Battery Charger Mode: As a lead acid battery charger it will provide a safe method of restoring discharged batteries. When
batteries are heavily discharged the unit can provide 10 Amps continuous charging current. Fully charged batteries can be
left connected to the unit indefinitely with no adverse effect on the lifetime of the batteries. An internal self resettable fuse is
incorporated in the battery output. Faulty and heavily discharged batteries will not damage the power supply.
UPS Mode: The full features of the unit are utilised when both battery and load are connected so that it operates as a power
supply with power fail protection. Under normal conditions an internal switch connects the battery in parallel with the load.
The average load must be less than 10 Amps to ensure there is a remainder (current) available to float charge the battery.
When mains failure occurs the unit no longer provides power. The battery remains switched in parallel with the load and
supports it without interruption. Restoration of the mains restarts the unit which will resume supporting the load and charging
the battery again without interruption.
During extended mains failure the unit disconnects the battery before it becomes excessively discharged. The battery
is automatically reconnected when mains power is restored enabling a quick charge to a workable voltage. This feature
contributes to long battery lifetime and allows unattended operation of a system with minimum service calls. The battery is
always being charged while mains are present. A heavily discharged battery will pull the unit into current limit and therefore
reduce the voltage supplied at load terminals. For batteries in good condition that have been protected from deep discharge
voltage should never be less than 10 Volts.
Installation & Safety Precautions:
1. This appliance is not meant for use by young children or infirm persons without supervision.
2. Young children should be supervised to ensure that they do not play with the appliance.
3. During charging process, do not use a naked flame near a battery, due to gases emitted from the battery, which may
ignite and explode.
4. Never smoke or light cigarettes near a battery.
5. Do not place tools on top of battery or allow tools to fall on battery.
6. Always wear eye protection near a charging battery.
7. Ensure a “well” ventilated area is used when testing or re-charging batteries.
8. Ensure ventilation is adequate and venting holes are not obstructed. Inadequate ventilation may over-heat the unit and
cause inefficient operation.
9. The UPS is intended for indoor use only. Do not expose it to extreme weather conditions e.g. rain or dampness.
10. If skin or clothing comes into contact with acid, flush the area(s) with water immediately. Seek medical attention if
necessary.
11. Use only 12V lead acid batteries never attempt to use non rechargeable batteries.
12. The UPS contains hazardous voltages. There are no user serviceable components inside. If the AC supply cord is
damaged, in order to avoid a hazard it must be replaced by the manufacturer or its service agent or a similarly
qualified person.
RPS12-R1
Should product require service, return it to place of purchase.
More information https://www.caravansplus.com.au

Page 2 of 2
Model:
UPS240-1210
Unit 2, 110 Station Road, Seven Hills ,NSW, 2147, Australia
12 Volt 10 Amp Switchmode
Uninterruptable Power Supply
Operating Instructions
Please read these instructions before use
RPS12-R1
Indicator Showing UPS Status
When the unit is operating under mains power, the indicator will illuminate GREEN when operating under
battery back-up, it will illuminate RED.
Battery Charging Times
The question of “how long will my battery take to re-charge” is always asked. Firstly, the charge rate (CR) of a battery is
rated in Amps and the battery capacity (C) in Amp Hours. The battery manufacturer for each battery type normally states
this CR. As a rule of thumb, a lead acid battery generally should be charged under 1/5 of C. For example if you have a
50Ah battery, the recommended max. charging current is: 50 / 5 = 10A. The majority of the battery capacity would normally
be charged in 5 hours with the UPS12-10 provided a negligible load. Similarly it would take approximately 10 hours to
charge the same battery with an average 5A load connected. The figures above represent a worst-case scenario since the
battery would generally have some remaining charge after a typical outage.
*Please note the figures quoted above could vary depending on the battery condition.
Battery
Battery
Load
Load
+
-
- +
-
+
-
+
(1) Power Supply
(2) Battery Charger
(3) Power Supply with
Power Fail Protection
Figure 1: Electrical Configurations
Figure 2: Dimensions (mm)
230.0
120.0
70.0
Load Battery
Specifications
AC Input Voltage 180 - 250V
AC Frequency 50 Hz
AC Current (A) 1.3A max
Float Charging Voltage 13.8V @ No Load
Output Current (A) approx.
max.
10A @ 13V >Vo > 6V
Battery low voltage discon-
nect protection
9.7V to 10V
Load regulation < 0.3V @ 9A > Io > 1A
Line regulation < 0.1V @ 250vac> Vin >180vac
Output noise < 0.1Vrms @ 60MHz BW on 1uF
Switching Frequency KHz 60KHz (typical)
Efficiency (Approx) 85%
Indicators AC power and Back up
Protection: Overload, Over Voltage, Short
Circuit, Reverse Polarity
Approvals:
Safety Standards No. N17018 AS/ANZ 60950:2000
C Tick No.N1408 (EMI, RFI) AS/NZS2064 Group 1, Class A
Cooling 60 x 60mm Fan, load activated
Dimensions (mm) 233L x 115W x 70H
Weight 1.3Kg
Warranty Conditions: Our products come with guarantees that cannot be excluded under the Australian Consumer Law.
The customer is entitled to a replacement or refund for a major failure and compensation for any other reasonably foreseeable loss or damage.
The customer is also entitled to have the products repaired or replaced if the products fail to be of acceptable quality and the failure does not amount to a
major failure.
GSL Electronics (GSL) warrants that its products will, under normal use and service, be free of defects in material and workmanship for a period of two (2)
years from the date of the original purchase by the customer as marked on the customer’s original invoice. Please refer to our website for full warranty and
return information.
More information https://www.caravansplus.com.au
Popular UPS manuals by other brands

Mustek
Mustek Power Must 400 user manual

Online
Online HU10kVA-RACK quick start guide

Toshiba
Toshiba Satellite 5000 Series Installation and operation manual

FRIEDHELM LOH
FRIEDHELM LOH RITTAL DK 7857.440 Installation

CyberPower
CyberPower CyberShield CSN30U12V user manual

OPTI-UPS
OPTI-UPS Power PS1000C user guide