Page 15
CONTROL PANEL
GENERAL:
See Figure 1 (Page 16). A typical prepackaged control
panel on units with liquid cooled engine includes: (a)
an auto-off-manual switch, (b) a fault indicator lamp,
(c) a 15 amp fuse, and (d) a set exercise switch.
AUTO-OFF-MANUAL SWITCH:
Use this switch to (a) select fully automatic operation,
(b) to crank and start the engine manually, and (c) to
shut the unit down or to prevent automatic startup.
1. AUTO position:
a.Select AUTO for fully automatic operation.
b.When AUTO is selected, circuit board will moni-
tor utility power source voltage.
c. Should utility voltage drop below a preset level
and remain at such a low level for a preset time,
circuit board action will initiate engine cranking
and startup.
d.Following engine startup, circuit board action
will initiate transfer of electrical loads to the
“Standby” source side.
e.On restoration of utility source voltage above a
preset level, circuit board action will initiate
retransfer back to the “Utility Source” side.
f. Following retransfer, circuit board will shut the
engine down and will then continue to monitor
utility source voltage.
2. OFF Position:
a.Set the switch to OFF to stop an operating
engine.
b.To prevent an automatic startup from occurring,
set the switch to OFF.
3. MANUAL Position:
a.Set switch to MANUAL to crank and start unit
manually.
b.Engine will crank cyclically and start (same as
automatic startup, but without transfer). The unit
will transfer if utility voltage is not available.
DANGER: WHEN THE GENERATOR IS
INSTALLED IN CONJUNCTION WITH AN
AUTOMATIC TRANSFER SWITCH, ENGINE
CRANKING AND STARTUP CAN OCCUR AT
ANY TIME WITHOUT WARNING (PROVIDING
THE AUTO-OFF-MANUAL SWITCH IS SET TO
AUTO). TO PREVENT AUTOMATIC STARTUP
AND POSSIBLE INJURY THAT MIGHT BE
CAUSED BY SUCH STARTUP, ALWAYS SET
THE AUTO-OFF-MANUAL SWITCH TO ITS
OFF POSITION BEFORE WORKING ON OR
AROUND THIS EQUIPMENT.
FAULT INDICATOR LAMP:
The fault indicator lamp will turn on in the event that
any one or more of the following engine fault condi-
tions should occur: (a) low oil pressure, (b) high
coolant temperature, (c) low coolant level, (d) over-
speed, and (e) overcrank.
15 AMP FUSE:
This fuse protects the DC control system, including
the control board, against overload. If the fuse has
blown, engine cranking and running will not be possi-
ble. Should fuse replacement become necessary, use
only an identical 15 amp replacement fuse.
THE SET EXERCISE SWITCH:
Use this switch to select the time and day for system
exercise.
TO SELECT AUTOMATIC OPERATION
The following procedure applies to those installations
in which the prepackaged home standby generator is
installed in conjunction with a prepackaged transfer
switch. Prepackaged transfer switches do not have an
intelligence circuit of their own. Instead, automatic
operation on prepackaged transfer switch and gener-
ator combinations is controlled by a control circuit
board housed in the generator.
To select automatic operation when a prepackaged
transfer switch is installed along with a prepackaged
home standby generator, proceed as follows:
1. Check that the prepackaged transfer switch main con-
tacts are at their “Utility” position, i.e., the load is connect-
ed to the utility power supply. If necessary, manually actu-
ate the switch main contacts to their “Utility” source side.
See Part 3 of this manual for instructions.
2. Check that utility source voltage is available to transfer
switch Terminal Lugs N1 and N2 (2-pole, 1-phase transfer
switches).
3. Set the generator’s AUTO-OFF-MANUAL switch to its
AUTO position.
4. Actuate the generator’s main line circuit breaker to its ON
or “Closed” position. With the preceding Steps 1 through
4 completed, a dropout in utility supply voltage below a
preset level will result in automatic generator cranking
and start-up. Following startup, the prepackaged transfer
switch will be actuated to its “Standby” source side, i.e.,
loads powered by the standby generator.
MANUAL TRANSFER TO “STANDBY” AND
MANUAL STARTUP
To transfer electrical loads to the "Standby" (genera-
tor) source and start the generator manually, proceed