K-BUS○
RIP/ KNX Convertor
User manual-Ver.1
BTIC-01/00.1
KNX/EIB Intelligent Installation Systems

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
2
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Contents
1. Summary--------------------------------------------------------------------------------------------------------- 3
2. Technical Properties & Dimension and Circuit Diagram---------------------------------------------- 4
2.1 Technical data -------------------------------------------------------------------------------------------------4
2.2 Dimension diagram-------------------------------------------------------------------------------------------5
2.3 Circuit diagram------------------------------------------------------------------------------------------------5
3. Project design and programming --------------------------------------------------------------------------- 6
3.1 Overview of the functions -----------------------------------------------------------------------------------6
3.2 Parameter setting description in the ETS -----------------------------------------------------------------7
3.2.1. Parameter window “IP settings” ---------------------------------------------------------------------7
3.2.2. Parameter window “IP address” ---------------------------------------------------------------------8
4. Communication Protocol ------------------------------------------------------------------------------------10
4.1 Default Communication Protocol ------------------------------------------------------------------------10
4.2 Command ID-------------------------------------------------------------------------------------------------11
4.3 READ GROUP ADDRESS-------------------------------------------------------------------------------12
4.4 WRITE GROUP ADDRESS------------------------------------------------------------------------------14
4.5 CHANGE THE MONITOR MODE---------------------------------------------------------------------16

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
3
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
1. Summary
The IP/ KNX convertor is designed for an intelligent building control system, which is used to connect the
KNX bus and the LAN. It serves as an interface between KNX installations and IP networks. TCP telegrams
from the client devices on the LAN can be converted to KNX telegrams via the convertor, and be sent to the
KNX bus to control KNX devices.
For convenient to control the KNX/EIB devices by a LAN devices, we define a communication protocol
which is transmitted on the data field of the IP packet transferred by the IP/ KNX convertor in the chapter 4 of
this manual. The users can configure or program the IP network devices according to the protocol to achieve
the control for KNX devices.
The IP/ KNX convertor has two working modes: the monitor mode and the filter mode. In the monitor mode,
all active telegrams can be forwarded. In the filter mode, only the telegrams those with a group address in the
filter table in the IP/KNX convertor will be forwarded to the other side.
The filter table can be set via the Filter Table Setting Command from the IP network.
The IP address of the IP/KNX convertor is fixed and can be configured before running. The power supply is
not only from the KNX bus, but also need an additional 30V DC supply.
The functions of the IP/ KNX convertor are summarized as follows:
Support TCP/IP protocol, always works in TCP server mode
Transfer the communication control telegrams transparently
Support up to10 TCP connections at the same time
Transfer the TCP telegram to the KNX/EIB system to control the KNX device
Monitor the telegrams on KNX bus and transfer them to all the clients connected
Read respond telegram will only be sent to the initiator
To read and write any data type which the max length is 14 bytes defined in the KNX standard
This manual provides the technical information about the IP/KNX Convertor as well as assembly and
programming in detail for users, and explains how to use the convertor by the application examples.
The IP/ KNX convertor is a modular installation device. It can be installed in the distribution board on 35mm
mounting rails according to EN 60 715. The device adopts an RJ45 interface to connect with LAN. The network
interface can be operated with a transmission speed of 10/100Mbit/s adaptively. The bus connection and
auxiliary power supply connection are carried out via EIB bus connection terminals.

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
4
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
The IP/KNX convertor is able to use the Engineering Tool Software ETS (ETS3 or later) which can import a
VD4 files to allocate the physical address and set the parameters.
2. Technical Properties, Dimension and Circuit Diagram
2.1 Technical data
Power supply
Operation voltage
21-30V DC, via the EIB bus
Current consumption, KNX
<12mA
Power consumption, KNX
<360mW
Auxiliary power supply
20-30V DC
Auxiliary power consumption
<2.5W
Connections
EIB / KNX Interface
Via bus connection terminals (black/red)
Auxiliary power supply
Via bus connection terminals(grey/yellow)
LAN
RJ45 socket for10/100Base-T, IEEE 802.3
network, Adaptively
Operating and
display
Programming LED and button
For assignment of the physical address
LED Green flashing
The device running indicator
LED ON
Network connection indicator
LAN/LINK LED flashing
Telegram traffic indicator
Temperature
Operation
–5 °C ... + 45 °C
Storage
–25 °C ... + 55 °C
Transport
–25 °C ... + 70 °C
Ambient
Humidity
<93%, except condensation
Design
Modular installation device, on 35mm mounting rail
Dimensions
90×36×64mm(H×W×D)
Weight
0.1kg
Housing, colour
Plastic housing, grey
Application program
Max. number of
communication objects
Max. number of
group address
Max. number of
associations
IP/KNX convertor
0
0
0

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
5
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
2.2 Dimension diagram
2.3 Circuit diagram
①LED ON,indicate that the network connect status.
②LAN/LINK LED flashing, indicate that telegram traffic is ongoing.
③Auxiliary power supply connection
④LAN connection RJ45
⑤Programming LED, red for assignment of physical address, green flashes for the device running well.
⑥Programming button
⑦EIB /KNX bus connection

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
6
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
3. Project design and application
3.1 Overview of the functions
Open communication protocols
The communication protocols for IP Interface is open, anyone can follow the text of the protocols to achieve
communication between the IP network devices and KNX devices via IP/KNX Converter. So you can easy to
connect the KNX/EIB bus system with the IP network into a whole, and ensure the reliability, commonality and
scalability of the system internal real-time communication, and really realize the openness of the system.
The IP/KNX convertor always works as a TCP server, support up to 10 TCP connections at the same time.
For receiving and sending communication control telegram
The communication control telegrams are received and sent in accordance to the format which described in
the chapter 4, “communication protocol”, i.e. command format. Each data in these command present different
meaning. The detail could be seen from the table in the chapter 4.
For converting the telegram
The telegram received from the IP client by the IP/KNX convertor should be generated in strict accordance
with the communication protocol format. While receives the telegram from the IP client, the IP/KNX convertor
extract the EIB information from the telegram, such as the group address, length, data type and value, etc, and
then converted them into the KNX/EIB telegram, and sent to the KNX/EIB system to control the KNX devices.
ACK report and executed result report
When receives a telegram from the IP client, the IP/KNX convertor will check the CRC in the telegram first.
If the telegram is correct, the IP/KNX convertor will respond to the IP client via sending an ACK report. If the
telegram is not correct, it will not respond. When the telegram is successfully transmitted to the EIB bus, the
IP/KNX convertor will send a successful telegram to the IP client. If failure transmitted, it will send a fail
telegram to the IP client (see “RESULTPKT” telegram).
Bus monitor and filter functions
The IP client can monitor the data on the EIB bus via the IP/KNX convertor. The IP/KNX convertor also
provides filter function to group address. When the filter function is set, the IP/KNX convertor only forwards the
telegram which group address is in the filter table to the EIB bus, and reverse. The filter table can be modified or
set by the IP client device. The Maximum number of group address in the filter table is 254. General, the bus
monitor mode is suitable for most of the users.

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
7
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Reading and writing data type
The data telegram that the length is less than or equal to14bytes can be sent to or read from the EIB bus via
the IP/KNX convertor.
The data which is read from the EIB bus is only forwarded to the client of the read request initiated.
3.2 Parameters setting description for the ETS
3.2.1. Parameter window “IP settings”
Parameter window “IP setting”is shown in fig. 3.2. Here can set the name and port number of the IP/KNX
Convertor.
Because IP convertor and RS485 convertor use the same product database, so before setting IP convertor
parameters, you must select devices first, as follow (fig.3.1):
Fig 3.1 Choose device

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
8
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Fig.3.2 parameter window “IP settings”
Parameter “Device name (Max. 30 Char.)”
This parameter defines the name of the IP convertor to identify the device on the LAN. Here can entry a
maximum of 30 characters in length. It is a spare parameter in current version.
Parameter “IP address assignment”
This parameter indicates that the IP address assignment of the convertor is fixed. The IP address can be
assigned in the follow parameter window “IP address”.
Parameter “Port Number of the IP Convertor”
This parameter defines the port number of the convertor, the port number of client devices must be the same
with the convertor, or their communications will fail.
3.2.2. Parameter window “IP address”
Parameter window “IP address”is shown in fig. 3.3. Here set the network connection information, such as IP
address, Subnet mask and Default gateway.

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
9
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Fig 3.3 parameter window “IP address”
Parameter “IP address”
This parameter defines the IP address of the IP convertor, the IP address is unique on the LAN, to avoid
collide. Option:
Byte x: 0…255
The IP address should be entered in a byte-by-byte manner, e.g. as follows for address 192.168.1.10:
Byte1: 192
Byte2: 168
Byte3: 1
Byte4: 10
Parameter “Subnet mask”
This parameter defines the subnet mask of the IP convertor. The subnet mask must be set to reflect the
number and structure of the subnet. Option:
Byte x: 0…255
In a small network the subnet mask 255.255.255.0 should be set as follows:
Byte1: 255
Byte2: 255
Byte3: 255

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
10
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Byte4: 0
Parameter “default gateway”
This parameter defines the default gateway. The default gateway must be the same network segment with the
IP address. Option:
Byte x: 0…255
The default gateway 192.168.1.1 should be set as follows:
Byte1: 192
Byte2: 168
Byte3: 1
Byte4: 1
4. Communication Protocol
4.1 Default Parameters
IP address: 192.168.1.10, port number: 1000, TCP Server mode, these mean that the device does not need to
configure via ETS and can be used directly after leave factory if the client information match with it.
Command packet
typedef struct {
BYTE Head1; // Always is 0x55=STX1.
BYTE Head2; // Always is 0xAA=STX2.
WORD MachineID; // Not use, default to 0.
WORD Reserved; // Reserved
WORD Command; // Command ID
DWORD Length; // Input Parameter 1
WORD InParam; // Input Parameter 2
WORD ChkSum; // Checksum
} CMDPKT; // Size of command packet is 16 Bytes.
Command acknowledge packet
typedef struct {
BYTE Head1; // Always is 0x5A=STX1.
BYTE Head2; // Always is 0xA5=STX2.
WORD MachineID; // Not use, default to 0.
WORD Response; // 0x00-NAK, 0x01-ACK.
WORD ChkSum; // Checksum

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
11
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
} ACKPKT; // Size of command acknowledge packet is 8 Bytes.
Command execution result packet
typedef struct {
BYTE Head1; // Always is 0xAA=STX1.
BYTE Head2; // Always is 0x55=STX2.
WORD MachineID; // Not use, default to 0.
WORD Reserved; // Reserved
WORD Ret; // 1: OK 0: Error
DWORD OutParam; // Output Parameter
WORD ChkSum; // Checksum
} RESULTPKT; // Size of command execution result packet is 14 Bytes.
Instruction:
A.The IP client send command using format of CMDPKT to the convertor. When the command is arrived, the
IP/KNX convertor will reply an ACK using the format of ACKPKT to the IP client, if the IP client does not
receive the ACK after a time, it will be considered that the transmission is failure and decide whether to
re-send.
B.After the command was executed, the convertor will report the execute result using the format of
structure RESULTPKT.
C.When write a Group Address Value which has more than 2 bytes Object Value, the Object Value should
be sent in another data packets, the Setting Data Command, to the Convertor.
D.When read a Group Address, need to ensure that the Communication Object has the read/write/transmit
enable. All the responds will be sent to the client in data packets.
E.The protocol for monitor mode and filtering mode is not suitable for all users now. We will provide them
in another document when need.
F.You should know the IP address and the port number of the IP Converter and have to link to it with TCP
protocol before using it. The IP Converter could be configured by ETS Tools!
G.The IP/KNX convertor always works as TCP server. In the monitor mode, the telegrams received from
the KNX bus will be sent to all the clients that have connected to IP/KNX convertor. But the read
respond telegram will only be sent to the initialize.
H.Only 10 TCP connections allowed at a time. Do not support UDP mode temporary.
4.2 Command ID
enum // The command ID for the connection.
{
CMD_SET_MONITOR_MODE = 0x101,

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
12
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
CMD_SET_FILTER_MODE,
CMD_SET_RANDOM_MODE, //This command is not available now
CMD_GROUP_ADDR_READ,
CMD_GROUP_ADDR_WRITE
};
4.3 BOOL ReadGroupAddr(CMDPKT* pCMD)
Function: Read the Group Address
Parameters:
Return: 1—OK;
0—Error;
PROTOCOL:
COMMAND(Client----IP/KNX Convertor)
Byte
Value
Meaning
1
0x55
Always is 0x55
2
0xAA
Always is 0xAA
3
1--255, 0 = default
Not use, default to 0.
4
5
0
Reserved
6
7
CMD_GROUP_ADDR_READ
Command ID
8
9
nConfig(NOTE 1)(We used the lowest 2
Input Parameter 1

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
13
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
bits as the priority, usually it equals
0x03)
10
nLength(NOTE 2)
11
DEST ADDR(NOTE 3)
12
13
0
Input Parameter 2
14
15
ChkSum
Checksum(NOTE 4)
16
ACK(IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0x5A
Always is 0x5A
2
0xA5
Always is 0xA5
3
1--255, 0 = default
Not use, default to 0.
4
5
0x00-NAK
0x01-ACK.
Response
6
7
ChkSum
Checksum(NOTE 4)
8
EXERESULT (IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0xAA
Always is 0xAA
2
0x55
Always is 0x55
3
1--255, 0 = default
Not use, default to 0.
4
5
0
Reserved
6
7
1: OK 0: Error
Result
8
9
0
Output Parameter
10
11
12
13
ChkSum
Checksum(NOTE 4)
14
Data respond(IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0xA5
Always is 0xA5
2
0x5A
Always is 0x5A
3
1--255, 0 = default
Not use, default to 0.
4

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
14
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
5
SRC ADDR(NOTE 5)
The Physical Address of the source
6
7
DEST ADDR(NOTE 3)
Destination Group Address
8
9
nLength
The Length of the Value
10
// Group communication Multicast
APCI_VALUE_READ 0x0000
APCI_VALUE_RESP 0x0040
APCI_VALUE_WRITE 0x0080
APCI of EIB telegram
11
1~14 Bytes of Value
19
ChkSum
Checksum(NOTE 4)
20
4.4 BOOL WriteGroupAddr(CMDPKT* pCMD)
Function: Write the Group Address
Parameters:
Return: 1—OK;
0—Error;
PROTOCOL:
COMMAND(Client----IP/KNX Convertor)
Byte
Value
Meaning
1
0x55
Always is 0x55
2
0xAA
Always is 0xAA

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
15
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
3
1--255, 0 = default
Not use, default to 0.
4
5
0
Reserved
6
7
CMD_GROUP_ADDR_WRITE
Command ID
8
9
nConfig(NOTE 1) (We used the lowest
2 bits as the priority, usually it
equals 0x03)
Input Parameter 1
10
nLength(NOTE 2)
11
DEST ADDR(NOTE 3)
12
13
(nLength <= 2) : Group Value
Else : 0
Input Parameter 2
14
15
ChkSum
Checksum(NOTE 4)
16
ACK(IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0x5A
Always is 0x5A
2
0xA5
Always is 0xA5
3
1--255, 0 = default
Not use, default to 0.
4
5
0x00-NAK
0x01-ACK.
Response
6
7
ChkSum
Checksum(NOTE 4)
8
EXERESULT (IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0xAA
Always is 0xAA
2
0x55
Always is 0x55
3
1--255, 0 = default
Not use, default to 0.
4
5
0
Reserved
6
7
1: OK 0: Error
Result
8
9
0
Output Parameter
10
11
12
13
ChkSum
Checksum(NOTE 4)

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
16
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
14
Setting Data(Client----IP/KNX Convertor)
Byte
Value
Meaning
1
0x5A
Always is 0x5A
2
0xA5
Always is 0xA5
3
1--255, 0 = default
Not use, default to 0.
4
5
3~14 Bytes of Value(nLength >= 3) : Group
Value
6~
17
18
19
ChkSum
Checksum(NOTE 4)
20
4.5 BOOL ComMonitorModeChange(CMDPKT* pCMD)
Function: Change the monitor mode;
Parameter:
Return: 1 —OK;
0 –- Error;
PROTOCOL:

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
17
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
COMMAND(Client----IP/KNX Convertor)
Byte
Value
Meaning
1
0x55
Always is 0x55
2
0xAA
Always is 0xAA
3
1--255, 0 = default
MachineID
4
5
0
Reserved
6
7
CMD_SET_MONITOR_MODE ||
CMD_SET_FILTER_MODE
Command ID
8
9
CMD_SET_MONITOR_MODE:0
CMD_SET_FILTER_MODE:(1~
254),the length of filter table.
Input Parameter 1
10
11
12
13
0
Input Parameter 2
14
15
ChkSum
Checksum(NOTE 4)
16
ACK(IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0x5A
Always is 0x5A
2
0xA5
Always is 0xA5
3
1--255, 0 = default
MachineID
4
5
0x00-NAK
0x01-ACK.
Response
6
7
ChkSum
Checksum(NOTE 4)
8
EXERESULT(IP/KNX Convertor ---- Client)
Byte
Value
Meaning
1
0xAA
Always is 0xAA
2
0x55
Always is 0x55
3
1--255, 0 = default
MachineID
4
5
0
Reserved
6
7
1: OK 0: Error
Result
8
9
0
Output Parameter
10
11

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
18
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
12
13
ChkSum
Checksum(NOTE 4)
14
Setting Filter Table(Client----IP/KNX Convertor)
Byte
Value
Meaning
1
0x5A
Always is 0x5A
2
0xA5
Always is 0xA5
3
1--255, 0 = default
MachineID
4
High Byte of the Group Address
Max Data:254*2 Bytes(The Lower Byte of
the Group Address follows the higher Byte,
and they should be marked in ascending
order, for example, Group Address 00-05
should be placed before 00-06, also 00-05
should be placed before 01-05).
Low Byte of the Group Address
High Byte of the Group Address
Low Byte of the Group Address
…High Byte
…Low Byte
…High Byte
…Low Byte
19
ChkSum
Checksum(NOTE 4)
20
NOTE 1: According to KNX Standard, it has 4 types, corresponding to 4 Transmission Priority:
11 = low operational priority
10 = high operational priority
01 = alarm priority
00 = system priority
Usually we use LOW priority, so the nConfig will be 0x03, others are not recommended.
NOTE 2: The length of the Communication Object which was linked to the DEST ADDR according to the KNX
standard, e.g. when the Communication Object less than 1 byte it equals to1, otherwise it equals to
length + 1.That is say, when we have a 1 bit CO, then the nLength should equals to 0x01, while a 1 byte
CO will have the nLength equals to 0x02.
NOTE 3: Destination Group Address which you want to read or write.
NOTE 4: The sum of all the data bytes before.
NOTE 5: The Physical Address of the device from whom sends out the telegram.

GVS K-BUS○
RKNX/EIB IP/KNX Convertor
19
www.video-star.com.cn marketing@video-star.com.cn Tel.:(8620)39338986
Fax:(8620)39338465
Other manuals for K-BUS
1
Table of contents
Popular Media Converter manuals by other brands

Transition Networks
Transition Networks SBFTF10XX-10X user guide

CYP
CYP CS-801H Operation manual

ClearClick
ClearClick Video2Digital manual

Omnitron Systems Technology
Omnitron Systems Technology FlexPoint 10FL/2 User instructions

madVR Labs
madVR Labs Envy Setup guide

HumanTechnik
HumanTechnik S/PDIF Operation instructions

LG-Nortel
LG-Nortel NS 161 series manual

StarTech.com
StarTech.com IC232485S instruction manual

Z-Band video
Z-Band video Gen 4 "GigaBUD 1000" installation guide

Verint
Verint nextiva s1800e series user guide

NTI
NTI VOPEX-DVI4K-2 Installation and operation manual

AJA
AJA FiDO Series Installation and operation guide