
09.10.2018 – BAe20607
Technical support:
T +41 41 319 50 50
F +41 41 310 60 87
GWF MessSysteme AG
Obergrundstrasse 119
6005 Lucerne, Switzerland
Subject to modication,
Display Display description /
programming action
Pulse value
version for volume
Pulse value
version for energy
Battery exchange
(only available in case
of batterydisconnection)
Comma position: 0 digits 1m3(= 1000l) 1 MWh (= 1000kWh)
Comma position: 1 digit 0,1m3(= 100l) 0,1 MWh (= 100kWh)
Comma position: 2 digits 0,01m3(= 10l) 0,01 MWh (= 10kWh)
Comma position: 3 digits 0,001m3(= 1l) 0,001 MWh (= 1kWh)
Programming the meter offset. Flashing digits can be modified by keeping the push button pressed. The selected
value will be memorised by releasing the push bottom. Repeat pressing the push button to return to the program-
ming modus and select the next value on second position or leave the programming modus, as shown in example:
Restore last index before reset. (Only available 5 min after reset!)
hold
release hold
release
4.4 Finishing the installation
■Close the box cover and fix the front cover with screws to
back cover. Stick the needed label version on the box cover.
(Take attention to the chosen unit!)
■Protect the screws by user seals.
■Use the inscription field to indicate the meter point
(e.g. name of tenant, flat number etc.)
5. Reset and battery exchange
■Value-Setting: the index of theTC-E can be adjusted to any
value (see 4.3)
■Battery exchange (see 4.1): after removing the battery the
TC-E will switch to following states:
4.3 Programming of pulse value and reset of the index.
Press push-button (picture 3) for more than 2s and keep it pressed. A display loop will start(each display appr. 2s). An action (pro-
gramming) will occur, if the push button is released during the actual display.
Dimensions width = 64mm
length = 44,5mm
height = 20mm
Battery type Lithium SL-360 / P–3,6 V–2,3 Ah
Art.-Nr. 10128
Battery lifetime app. 10 years
(at 20°C environmental temperature)
Protection class IP64
Environment temperature -15– 55°C (Inside installation)
6. Technical Data
Characteristic of pulse emitter
Pulse/pause duration 100ms/100ms (minimal)
Max. pulse frequency 5Hz
Ron 200MΩ
(resistance during pulse)
Roff 1MΩ
(resistance during intervall)
Max. bounce time 15ms
Max. cable length 30m
■
TC-E without power ‹ 30s: Index and pulse value will be
kept, TC-E will start counting with old settings.
■
TC-E without power › 30s but ‹ 600s: Index and pulse
value will be kept, TC-E will start with a display test
(see 4.2) and starts counting with old settings.
■
TC-E without power ›600s: Index and pulse value will
be reset to default values, the pulse value has to be pro-
grammed.