Domestic air conditioner
Functions and control
When Tr<Ts+5 , compressor, four-ways valve and outdoor fan motor is on, and the indoor fan motor runs as
in the mode of avoiding cold blast.
*Control of indoor fan motor:
Manual operation: The wind speed can be set to high, medium, low or automatic as required.
Automatic operation: When Tr Ts, the wind speed is high;
When Ts Tr Ts+2 , the wind speed is medium.
When Ts+2 Tr, the wind speed is low.
*Control of air door: setting the position of air door as required.
*Compressor control The compressor can’t be controlled by temperature sensor in 2 minutes after start
up and also can’t be started again at least 3 minutes later after shut down. There are 3-minute protection with
power on for the first time (over 3 minutes with power off). The compressor must be started again 3 minutes
later after shut down.
*Avoiding electrical shock: outlet air is available 2 seconds later after start up.
*Timer on, Timer off and sleep control are available.
*Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts running 10
●
seconds earlier than compressor does. After compressor stops running, the 4-way valve continues running for
2 minutes and then stops. If changing the unit from heating to cooling, the 4-way valve is shut off 2 minutes
later and compressor is started 3 minutes later.
●
*Cold draft prevention:
Compressor is interrupted during the defrosting operation and continues to run after defrosting is
completed. When the indoor exchanging temperature is below 23 , the indoor fan motor is off. When the
indoor exchanging temperature is above 23 , the indoor fan motor is running at weak speed.
If the temperature of coil pipe can’t be above 38 4 minutes later after start up fan motor is running
at the preset wind speed.
If the temperature of coil pipe is above 38 4 minutes later after start up, fan motor i
●
s running at the
preset wind speed.
If coil pipe descends to the temp. lower than 38 from 38 . fan motor is running at the preset wind
speed.
*Warm blast: If the temperature sensor is off. Compressor stops running. If the temperature of coil pipe is
above 23 , fan motor enter breeze mode; and if the temperature of coil pipe is below 20 , fan motor stops
running.
*High temperature protection and high temperature expiration protection:
High temperature prevention: When the temp. of coil pipe is above 53 , the outdoor fan motor stops.
When the temp descends to 49 , the outdoor fan motor is restarted and fan speed invertage frequency is
more than 45 seconds.
High temperature expiration prevention: When the temp.of coil pipe is above 60
●
, compressor and
outlet air stop running 10 seconds later, and inlet air runs as the temp. sensor is off. When compressor stands
by for 3 minute and the temp. of coil pipe is below 50 , the unit can be started again.
*Overcooling protection One and half a minutes later after compressor starts, if the temperature of coil
pipe is below 1 , compressor and air outlet stop, and air inlet runs according to the temp. setting.
Compressor can be restarted 3 minutes later.
*Defrosting:
Entry conditions of defrosting:
The entry conditions of defrosting are classified into two types: intelligentized defrosting and sensor
defrosting. Through selecting and judging, the models without outdoor sensor defrost according to
intelligentized defrosting, and others with sensor defrost according to sensor defrosting.